Vega PLICSRADIO T61 Operating Instructions Manual

Manual is about: Wireless Gateway

Summary of PLICSRADIO T61

  • Page 1

    Operating instructions plicsradio t61 wireless gateway wireless emitting unit (single channel) signal conditioning instruments and communication in out.

  • Page 2: Contents

    Contents 1 about this document 1.1 function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.2 target group . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.3 symbolism used . . . . . . . . . . . . . . . . . . . . . . . 4 2 for your safety 2.1 authorised personnel . . . . . . . ....

  • Page 3

    8 maintenance and fault rectification 8.1 maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . 33 8.2 fault clearance . . . . . . . . . . . . . . . . . . . . . . . . 33 8.3 instrument repair . . . . . . . . . . . . . . . . . . . . . . . 35 9 dismounting 9.1 dismounting steps . . . . . . . ...

  • Page 4: 1 A

    1 a bout this document 1 .1 function this operating instructions manual provides all the information you need for mounting, connection and setup as well as important instructions for maintenance and fault rectification. Please read this information before putting the instrument into operation and kee...

  • Page 5: 2 F

    2 f or your safety 2 .1 authorised personnel all operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the operator. During work on and with the device the required personal protection equipment must always be worn. 2 .2 app...

  • Page 6

    During the entire duration of use, the user is obliged to determine the compliance of the required occupational safety measures with the current valid rules and regulations and also take note of new regulations. 2 .5 safety approval markings and safety tips the safety approval markings and safety ti...

  • Page 7

    2 .8 environmental instructions protection of the environment is one of our most important duties. That is why we have introduced an environment management system with the goal of continuously improving company environmental protection. The environment man- agement system is certified according to di...

  • Page 8: 3 P

    3 p roduct description 3 .1 configuration the scope of delivery encompasses: l plicsradio t 61 l antenna l documentation - this operating instructions manual - ex-specific "safety instructions" (with ex-versions) - if necessary, further certificates plicsradio t 61 consists of the following components:...

  • Page 9

    L plicsradio t 61 (single channel emitting unit) l plicsradio t 62 (multiple channel emitting unit) l plicsradio r 61 (single channel receiving unit) l plicsradio r 62 (multiple channel receiving unit) l plicsradio d 61 (single channel indicating unit) l plicsradio c 62 (multiple channel processing ...

  • Page 10

    4... 20 ma ser. No. 12345678 on ok esc com plicsradio c62 3 2 1 4 2 3 5 8 6 7 1 fig. 3: example plicsradio - multiple channel application 1 2x hart sensor 2 4 … 20 ma instrument 3 2x switching instruments 4 emitting unit plicsradio t62 5 receiving unit plicsradio r62 6 processing unit plicsradio c62...

  • Page 11

    The entered parameters are generally saved in plicsradio t 61, when used with pactware™ and pc optionally also on the pc. Information: when using pactware™ and corresponding vega dtms, additional settings can be carried out which are not possible or only partly possible with the integrated indicatin...

  • Page 12: 4 M

    4 m ounting 4 .1 general instructions select an installation position you can easily reach for mounting and connecting as well as later retrofitting of an indicating and adjustment module. The housing can be rotated by 330° without the use of any tools. You can also install the indicating and adjustm...

  • Page 13

    L allen key size 4 l phillips head size 2 or torx size t10 l slotted screwdriver 3 mm plicsradio t 61 in ex version is a corresponding, intrinsi- cally safe piece of equipment and must not be installed in hazardous areas. Safe operation is only ensured if the operating instructions and eg type appro...

  • Page 14

    Warning: the four screws for the socket housing must only be hand- screwed. A torque >5 nm can damage the wall mounting plate. 14 plicsradio t 61 - wireless emitting unit (single channel) mounting 32865 -en -070801.

  • Page 15: 5 C

    5 c onnecting to power supply 5 .1 preparing the connection always keep in mind the following safety instructions: l connect only in the complete absence of line voltage l if overvoltage surges are expected, overvoltage arresters should be installed in hazardous areas you should take note of the app...

  • Page 16

    1 loosen the four screws on the housing socket with an allen key 2 remove the housing socket from the mounting plate 3 2 1 fig. 6: remove the mounting plate from the housing socket 1 hexagon screws 2 wall mounting plate 3 cable gland 3 lead the connection cable through the cable gland on the housing...

  • Page 17

    6 tighten the compression nut of the cable entry. The seal ring must completely encircle the cable 7 attach the mounting plate again and tighten the screws 5 .3 connection steps voltage supply proceed as follows: 1 unscrew the housing cover 2 if an indicating and adjustment module is installed, remo...

  • Page 18

    Fig. 7: connection steps 6 and 7 (connect voltage supply) 9 press down the opening levers of the terminals, you will hear the terminal spring closing 10 check the hold of the wires in the terminals by lightly pulling on them 11 tighten the compression nut of the cable entry. The seal ring must compl...

  • Page 19

    5 .4 wiring plan 1 2 fig. 8: connection voltage and sensor supply 1 electronics housing with terminals for voltage supply 2 socket housing with terminals for sensor connection overview plicsradio t 61 - wireless emitting unit (single channel) 19 connecting to power supply 32865 - en -070801.

  • Page 20

    1 2 1 2 3 fig. 9: connection of the sensor in the socket housing 1 + 2 - 3 grounding information: two-wire or four-wire instruments can be connected. In the menu you can switch over between active (standard setting) and passive operation of the measuring data input. The connection assignment is the ...

  • Page 21

    1 1 2 l ( + ) n ( - ) fig. 10: connection of the voltage supply in electronics housing 1 voltage supply wiring plan, voltage supply in electronics housing plicsradio t 61 - wireless emitting unit (single channel) 21 connecting to power supply 32865 - en -070801.

  • Page 22: 6 S

    6 s et up with the indicating and adjustment module 6 .1 short description the indicating and adjustment module is used for measured value indication, adjustment, and diagnostics. It can be used in all instruments of the plics ® series: note: you will find detailed information on adjustment in the op...

  • Page 23

    Fig. 11: installation of the indicating and adjustment module note: if you intend to retrofit plicsradio t61 with an indicating and adjustment module for continuous measured value indication, a higher cover with an inspection glass is required. Plicsradio t 61 - wireless emitting unit (single channel...

  • Page 24

    6 .3 adjustment system 1.1 2 3 1 fig. 12: indicating and adjustment elements 1 lc display 2 indication of the menu item number 3 adjustment keys l [ok] key: - move to the menu overview - confirm selected menu - edit parameter - save value l [->] key to select: - menu change - list entry - select edit...

  • Page 25

    6 .4 setup procedure setup is comprised mainly of the radio connection adjustment (selection radio channel and safe operation). The selection of the requested indication value, e.G. In percent, linearized percent or scaled are further adjustment options (only when connecting vega sensors). Setup of ...

  • Page 26

    Device-tag device name à enter the requested values via the appropriate keys and save your settings with [ok]. The emitting and receiving units must be always set to the same radio channel. When using several independent radio links, each radio link must be provided with a different channel. In total...

  • Page 27

    Safe operating mode activated radio pin 0815 à enter the values via the appropriate keys and save your settings with [ok]. The displayed value determines which measured value is displayed. For vega sensors "percent", "lin. Percent", "s caled" and "sensor value" are available. The parameter- isation ...

  • Page 28

    L passive (for connection of four-wire insturments with separate power supply, not available with ex version) input hart active ▼ à enter the requested parameters via the appropriate keys and save your settings with [ok]. With a reset to default, all settings will be reset to default except the lang...

  • Page 29

    6 .5 menu schematic device settings ▶ device settings display diagnostics service info device-tag device name radio channel 1 address 4 safe operating mode activated radio pin 1234 display device settings ▶ display diagnostics service info displayed value percent ▼ diagnostics device settings displa...

  • Page 30

    Service device settings display diagnostics ▶ service info input hart active ▼ reset factory setting reset now? Language deutsch ▼ pin enable? Info device settings display diagnostics service ▶ info sensor type plicsradio xx serial number 12345678 date of manufacture 03 . February 2004 software vers...

  • Page 31: 7 S

    7 s etup with pactware™ 7 .1 connecting the pc as an alternative to the setup via indicating and adjustment module, the parameter adjustment is also possible via pc. For connection you require the vegaconnect 4 interface converter. This converter can be inserted into plicsradio t 61 instead of the i...

  • Page 32

    7 .2 parameter adjustment with pactware™ to adjust plicsradio t61 via a windows-pc, the config- uration software pactware™ and a suitable instrument driver (dtm) according to fdt standard are necessary. The vega dtms can be also integrated in other frame applications according to fdt standard. All cu...

  • Page 33: 8 M

    8 m aintenance and fault rectification 8 .1 maintenance when used as directed in normal operation, plicsradio t61 is completely maintenance free. 8 .2 fault clearance the operator of the system is responsible for taken suitable measures to remove interferences. Plicsradio t 61 offers maximum reliabili...

  • Page 34

    à send sensor for repair ? E 030 l sensor in boot phase l invalid measured value à check sensor parameter adjustment ? E 034 l eeprom defective à carry out a reset à send instrument for repair ? E 035 l eeprom crc error à carry out a reset à send instrument for repair ? E 036 l instrument software n...

  • Page 35

    Depending on the failure reason and measures taken, the steps described in chapter "set up" must be carried out again, if necessary. 8 .3 instrument repair if a repair is necessary, please proceed as follows: you can download a return form (23 kb) from the internet on our homepage www.Vega.Com under...

  • Page 36: 9 D

    9 d ismounting 9 .1 dismounting steps take note of chapters "mounting" and "connecting to power supply" and carry out the listed steps in reverse order. 9 .2 disposal the instrument consists of materials which can be recycled by specialised recycling companies. We use recyclable materials and have d...

  • Page 37: 10 S

    10 s upplement 10 .1 technical data general data 316l corresponds to 1.4404 or 1.4435, 316ti corresponds to 1.4571 materials - housing plastic pbt, alu die-casting, 316l - inspection window in housing cover for indicating and adjustment mod- ule polycarbonate (ul-746-c listed) - ground terminal 316t...

  • Page 38

    Radio transmission radio frequency - standard version 2.4000 … 2.4835 ghz - version increased range 902 … 928 mhz antenna connection r-sma antenna type, standard isotropic (omni) antenna emitted power, standard antenna - standard version 17 dbm (50 mw) - version increased range 21.5 dbm (140 mw) ant...

  • Page 39

    Electromechanical data cable entry/plug - housing socket l 1x cable entry m20x1.5 (cable-ø 5 … 9 mm), 2x blind stopper m20x1.5 or: l 1x closing cap ½ npt, 2x blind stopper ½ npt - electronics housing l 1x cable entry m20x1.5 (cable-ø 5 … 9 mm), 1x antenna connection (r-sma) or: l 1x closing cap ½ np...

  • Page 40

    Fm fm ci.I, div2 (ni)+ci.Ii, iii, div1 (dip) csa csa ci.I, div2 (ni)+ci.Ii, iii, div1 (dip) radio approvals - standard version fcc id: our-24xstream - version increased range fcc id: our-9xstream ic (industry canada) - standard version 4214a 12008 - version increased range 4214a-9xstream supplement ...

  • Page 41

    10 .2 dimensions electronics housing 1 2 138 m m (5 7 / 16 ") ~ 69 mm (2 23 / 32 ") ~ 88 mm (3 15 / 32 ") ø 77 mm (3 1 / 32 ") ~ 116 mm (4 9 / 16 ") ~ 87 mm (3 27 / 64 ") ø 84 mm (3 5 / 16 ") m20x1,5/ ½ npt m20x1,5/ ½ npt m20x1,5/ ½ npt fig. 14: electronics housing, the height of the plastic housing...

  • Page 42

    Housing socket with connection compartment 90mm (3 35 / 64 ") 110mm (4 21 / 64 ") ~ 66mm (2 19 / 32 ") 59mm (2 21 / 64 ") fig. 15: housing socket with connection compartment supplement 42 plicsradio t 61 - wireless emitting unit (single channel) 32865 -en -070801.

  • Page 43

    Remote antenna 90mm (3 35 / 64 ") 110mm (4 21 / 64 ") ~ 66mm (2 19 / 32 ") 138 mm (5 7 / 16 ") 19 mm ( 3 / 4 ") 59mm (2 21 / 64 ") max . 5 0mm (2 31 / 32 ") 250mm (9 27 / 32 ") 3 2 1 fig. 16: remote antenna 1 antenna 2 strap for tube mounting 3 antenna cable 3 m supplement plicsradio t 61 - wireless...

  • Page 44

    10 .3 industrial property rights vega product lines are global protected by industrial property rights. Further information see http://www.Vega.Com. Only in u.S.A.: further information see patent label at the sensor housing. Vega produktfamilien sind weltweit geschützt durch gewerbliche schutzrechte...

  • Page 45

    Supplement plicsradio t 61 - wireless emitting unit (single channel) 45 32865 - en -070801.

  • Page 46

    Supplement 46 plicsradio t 61 - wireless emitting unit (single channel) 32865 -en -070801.

  • Page 47

    Supplement plicsradio t 61 - wireless emitting unit (single channel) 47 32865 - en -070801.

  • Page 48

    Vega grieshaber kg am hohenstein 113 77761 schiltach germany phone +49 7836 50-0 fax +49 7836 50-201 e-mail: info@de.Vega.Com www.Vega.Com iso 9001 all statements concerning scope of delivery, application, practical use and operating conditions of the sensors and processing systems correspond to the...