Vega PULS SR 68 Quick Setup Manual - page 16
16
5 Set up the sensor with the display and adjustment module
VEGAPULS SR 68 • Modbus and Levelmaster protocol
47164-EN-140129
The radar sensor as a distance measuring instrument measures the
distance from the sensor to the product surface. For indication of the
reallevel,anallocationofthemeasureddistancetothepercentage
height must be carried out.
2
1
3
100%
0%
1
m
(39.37
")
35
m
(1378
")
Fig. 11: Parameterization example
1 Min. level ≙ max. meas. distance
2 Max. level ≙ min. meas. distance
Forthisadjustment,thedistanceisenteredformin.andmax.level.
Ifthesevaluesarenotknown,anadjustmentwithdistances,for
example,of10%and90%isalsopossible.Startingpointforthese
distancespecificationsisalwaysthesealsurfaceofthethreador
flange.
With the function "Echocurvememory" the echo curve can be saved
at the time of setup. This is generally recommended; for using the As-
setManagementfunctionsitisabsolutelynecessary.Ifpossible,the
curve should be saved with a low level in the vessel.
WiththeadjustmentsoftwarePACTwareandthePC,thehighresolu-
tionechocurvecanbedisplayedandusedtorecognizesignal
changesovertheoperatingtime.Inaddition,theechocurveofthe
setup can be also displayed in the echo curve window and compared
with the actual echo curve.
Parameterization example
Diagnostics - Echo curve
memory