Vega VEGACAP 63 Operating Instructions Manual

Manual is about: VEGACAP 60 series Relay (DPDT)

Summary of VEGACAP 63

  • Page 1

    Operating instructions vegacap 63 - relay (dpdt) document id: 30008 capacitive.

  • Page 2: Contents

    Contents 1 about this document 1.1 function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.2 target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.3 symbolism used. . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 2 for your safety 2.1 authorised...

  • Page 3

    Supplementary documentation information: supplementary documents appropriate to the ordered version come with the delivery. You can find them listed in chapter "product description". Instructions manuals for accessories and replacement parts tip: to ensure reliable setup and operation of your vegacap...

  • Page 4: About This Document

    1 about this document 1 .1 function this operating instructions manual provides all the information you need for mounting, connection and setup as well as important instructions for maintenance and fault rectification. Please read this information before putting the instrument into operation and keep...

  • Page 5: For Your Safety

    2 for your safety 2 .1 authorised personnel all operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator. During work on and with the device the required personal protective equipment must always be worn. 2 ....

  • Page 6

    2 .5 safety label on the instrument the safety approval markings and safety tips on the device must be observed. 2 .6 ce conformity this device fulfills the legal requirements of the applicable ec guidelines. By attaching the ce mark, vega provides a confirmation of successful testing. You can find the...

  • Page 7: Product Description

    3 product description 3 .1 configuration the scope of delivery encompasses: l vegacap 63 point level sensor l documentation - this operating instructions manual - safety manual - 31814 "vegacap series 60 - relay (dpdt)" (optional) - supplementary instructions manual "plug connector for level sensors"...

  • Page 8

    The serial number allows you to access the delivery data of the instrument via www.Vega.Com, "vega tools" and "serial number search". In addition to the type label outside, you can also find the serial number on the inside of the instrument. 3 .2 principle of operation vegacap 63 is a point level sen...

  • Page 9

    Vegacap 63 is a compact instrument, i.E. It can be operated without external evaluation system. The integrated electronics evaluates the level signal and outputs a switching signal. With this switching signal, a connected device can be operated directly (e.G. A warning system, a plc, a pump etc.). T...

  • Page 10

    L protected against solar radiation l avoiding mechanical shock and vibration l storage and transport temperature see chapter "supplement - technical data - ambient conditions" l relative humidity 20 … 85 % storage and transport temperature 10 vegacap 63 • - relay (dpdt) 3 product description 30008 ...

  • Page 11: Mounting

    4 mounting 4 .1 general instructions make sure that all parts of the instrument exposed to the process, in particular the sensor element, process seal and process fitting, are suitable for the existing process conditions. These include above all the process pressure, process temperature as well as th...

  • Page 12

    Do not hold vegacap 63 on the probe. Especially with heavy flange versions or long rod versions, the sensor can be damaged simply by the weight of the instrument. The process fitting must be sealed if there is gauge or low pressure in the vessel. Before use, check if the seal material is resistant aga...

  • Page 13

    Fig. 4: inflowing medium the probe should protrude into the vessel to avoid buildup. For that reason, avoid using mounting bosses for flanges and screwed fittings. This applies particularly to use with adhesive products. To compensate the normal voltage loss due to sealing materials, you have to additi...

  • Page 14: Connect To Power Supply

    5 connect to power supply 5 .1 prepare the connection always keep in mind the following safety instructions: l connect only in the complete absence of line voltage connect the operating voltage according to the following diagrams. The electronics module with relay output is designed in protection cl...

  • Page 15

    9 tighten the compression nut of the cable entry. The seal ring must completely encircle the cable 10 if necessary, carry out a fresh adjustment 11 screw the housing cover on the electrical connection is finished. Fig. 5: connection steps 5 and 6 5 .3 wiring plan, single chamber housing 1 4 4 4 2 3 f...

  • Page 16

    4 5 6 2 1 3 fig. 7: electronics and connection compartment 1 potentiometer for switching point adaptation 2 dil switch for measuring range selection 3 dil switch for mode adjustment 4 ground terminal 5 connection terminals 6 control lamp we recommend connecting vegacap 63 in such a way that the swit...

  • Page 17

    3 2 1 fig. 8: wiring plan 1 relay output 2 relay output 3 power supply vegacap 63 • - relay (dpdt) 17 5 connect to power supply 30008 - en -090604.

  • Page 18: Set Up

    6 set up 6 .1 general information the figures in brackets refer to the following illustrations. On the electronics module you will find the following indicating and adjustment elements: l potentiometer for switching point adaptation l dil switch for measuring range selection l dil switch for mode adju...

  • Page 19

    Note: screw the housing cover tightly up to the thread stop so that the inspection glass is above the control lamp (led). To adjust vegacap 63, first of all remove the housing cover. You can adapt the switching point to the solid with the potentiometer. With the potentiometer (1) and the measuring ra...

  • Page 20

    In some cases the lowest range (range 1 = highest sensitivity) is not sufficient to adjust the full switch point. This would make another filling procedure necessary. For this reason we recommend setting and noting the empty switching point in all three meas. Ranges. Set the meas. Range selection switc...

  • Page 21

    The measuring system is now ready for operation. 1 set mode switch (3) to mode min. 2 set meas. Range selection switch (2) to range 1. 3 lower the level to the requested min. Level. 4 turn the potentiometer (1) to 0, the control lamp (6) lights green. 5 turn the potentiometer (1) very slowly clockwi...

  • Page 22

    7 maintenance and fault rectification 7 .1 maintenance when used in the correct way, no special maintenance is required in normal operation. 7 .2 remove interferences the operator of the system is responsible for taken suitable measures to remove interferences. A maximum of reliability is ensured. Ne...

  • Page 23

    L shortcircuit in the probe, e.G. Because of moisture in the housing à remove the electronics module and check the resistance between the marked plug connections according to the following illustration. 1 2 3 fig. 26: check the resistance in the probe 1 shielding 2 probe 3 ground potential à there s...

  • Page 24

    7 .3 exchange of the electronics module in general, all electronics modules of series cp60 can be inter- changed. If you want to use an electronics module with a different signal output, you can download the corresponding operating instructions manual from our homepage under downloads. Proceed as fol...

  • Page 25

    11 insert the wire ends into the open terminals according to the wiring plan 12 press down the opening levers of the terminals, you will hear the terminal spring closing 13 check the hold of the wires in the terminals by lightly pulling on them 14 check cable gland on tightness. The seal ring must c...

  • Page 26: Dismounting

    8 dismounting 8 .1 dismounting steps warning: before dismounting, be aware of dangerous process conditions such as e.G. Pressure in the vessel, high temperatures, corrosive or toxic products etc. Take note of chapters "mounting" and "connecting to power supply" and carry out the listed steps in reve...

  • Page 27: Supplement

    9 supplement 9 .1 technical data general data material 316l corresponds to 1.4404 or 1.4435 materials, wetted parts - process fitting - thread 316l - process fitting - flange 316l - process seal klingersil c-4400 - insulation (fully insulated) ptfe, pe - probe (rod fully insulated: ø 16 mm/ 0.63 in) 31...

  • Page 28

    Turn-on voltage - min. 10 mv - max. 253 v ac, 253 v dc switching current - min. 10 µa - max. 3 a ac, 1 a dc breaking capacity - min. 50 mw - max. 750 va ac, 54 w dc if inductive loads or stronger currents are switched through, the gold plating on the relay contact surface will be permanently damaged...

  • Page 29

    1 2 3 -50˚c (-58˚f) 50˚c (122˚f) 40˚c (104˚f) -40˚c (-40˚f) 80˚c (176˚f) 0˚c (32˚f) 100˚c (212˚f) 150˚c (302˚f) 200˚c (392˚f) fig. 29: ambient temperature - process temperature 1 process temperature 2 ambient temperature 3 temperature range with temperature adapter dielectric figure ≥ 1.5 electromech...

  • Page 30

    20 … 253 v ac, 50/60 hz, 20 … 72 v dc (at u > 60 v dc, the ambient temperature can be max. 50 °c/122 °f) power consumption 1 … 8 va (ac), approximately 1 w (dc) electrical protective measures protection rating ip 66/ip 67 overvoltage category iii protection class i functional safety (sil) functional...

  • Page 31

    9 .2 dimensions vegacap 63 ~ 69 mm (2 23 / 32 ") ø 77 mm (3 1 / 32 ") 112 mm (4 13 / 32 ") m20x1,5/ ½ npt ~ 69 mm (2 23 / 32 ") ø 77 mm (3 1 / 32 ") 117 mm (4 39 / 64 ") m20x1,5/ ½ npt ~ 116 mm (4 9 / 16 ") ø 84 mm (3 5 / 16 ") 116 mm (4 9 / 16 ") m20x1,5 m20x1,5/ ½ npt ~ 59 mm (2 21 / 64 ") ø 80 mm...

  • Page 32

    ø16mm ( 5 / 8 ") l g 3 / 4 a, g 1 a, g 1 1 / 2 a 56 mm (2 13 / 64 ") 22mm ( 55 / 64 ") fig. 31: vegacap 63 - threaded version g1 a (iso 228 t1) l = sensor length, see chapter "technical data" 32 vegacap 63 • - relay (dpdt) 9 supplement 30008 -en -090604.

  • Page 33

    102 mm (4.02") ø 40 mm (1.58") fig. 32: temperature adapter vegacap 63 • - relay (dpdt) 33 9 supplement 30008 - en -090604.

  • Page 34

    9 .3 industrial property rights vega product lines are global protected by industrial property rights. Further information see http://www.Vega.Com . Only in u.S.A.: further information see patent label at the sensor housing. Vega produktfamilien sind weltweit geschützt durch gewerbliche schutzrechte...

  • Page 35

    Vegacap 63 • - relay (dpdt) 35 9 supplement 30008 - en -090604.

  • Page 36

    Iso 9001 all statements concerning scope of delivery, application, practical use and operating conditions of the sensors and processing systems correspond to the information avail- able at the time of printing. © vega grieshaber kg, schiltach/germany 2009 subject to change without prior notice 30008...