Vega VEGADIS 81 Operating Instructions Manual

Other manuals for VEGADIS 81: Operating Instructions Manual
Manual is about: External display and adjustment unit for plics sensors

Summary of VEGADIS 81

  • Page 1

    Operating instructions external display and adjustment unit for plics ® sensors vegadis 81 document id: 43814.

  • Page 2: Contents

    2 contents vegadis 81 • 43814-en-170913 contents 1 about this document ............................................................................................................... 4 1.1 function .........................................................................................................

  • Page 3

    3 contents vegadis 81 • 43814-en-170913 10.2 disposal ......................................................................................................................... 33 11 supplement ..............................................................................................................

  • Page 4: 1  About This Document

    4 1 about this document vegadis 81 • 43814-en-170913 1 about this document 1.1 function this operating instructions manual provides all the information you need for mounting, connection and setup as well as important instruc- tions for maintenance, fault rectification, the exchange of parts and the ...

  • Page 5: 2  For Your Safety

    5 2 for your safety vegadis 81 • 43814-en-170913 2 for your safety 2.1 authorised personnel all operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator. During work on and with the device the required person...

  • Page 6

    6 2 for your safety vegadis 81 • 43814-en-170913 reasons, only the accessory specified by the manufacturer must be used. To avoid any danger, the safety approval markings and safety tips on the device must also be observed and their meaning looked up in this operating instructions manual. 2.5 eu con...

  • Page 7: 3  Product Description

    7 3 product description vegadis 81 • 43814-en-170913 3 product description 3.1 configuration the type label contains the most important data for identification and use of the instrument: 2 3 1 5 6 4 12 12 10 9 8 7 fig. 1: layout of the type label (example) 1 instrument type 2 product code 3 field fo...

  • Page 8

    8 3 product description vegadis 81 • 43814-en-170913 the display and adjustment module can be optionally equipped with heating to ensure good readability at low temperatures down to -40 °c (-40 °f). The scope of delivery encompasses: • display and adjustment unit vegadis 81 • unassembled cable gland...

  • Page 9

    9 3 product description vegadis 81 • 43814-en-170913 4 1 3 2 5 4 6 fig. 3: connection of vegadis 81 with heating to the sensor 1 voltage supply/signal output sensor 2 sensor 3 connection cable, sensor - vegadis 81 4 vegadis 81 with integrated heating 5 display and adjustment module 6 voltage supply,...

  • Page 10

    10 3 product description vegadis 81 • 43814-en-170913 1 3 2 6 45 4 4 fig. 5: connection of vegadis 81 to the sensor and the pc 1 voltage supply/signal output sensor 2 sensor 3 connection cable vegadis 81 - sensor 4 vegadis 81 5 vegaconnect 6 pc with pactware/dtm the wireless sensor adjustment is car...

  • Page 11

    11 3 product description vegadis 81 • 43814-en-170913 3.3 packaging, transport and storage your instrument was protected by packaging during transport. Its capacity to handle normal loads during transport is assured by a test based on iso 4180. The packaging of standard instruments consists of envir...

  • Page 12: 4 Mounting

    12 4 mounting vegadis 81 • 43814-en-170913 4 mounting 4.1 general instructions vegadis 81 functions in any installation position. Protect your instrument against moisture ingress through the following measures: • use the recommended cable (see chapter " connecting to power supply ") • tighten the ca...

  • Page 13

    13 4 mounting vegadis 81 • 43814-en-170913 1 2 fig. 8: vegadis 81 with plastic housing for carrier rail mounting 1 base 2 carrier rail the versions with aluminium or stainless steel housing for carrier rail mounting according to en 50022 are supplied with unassembled mounting accessories. The kit co...

  • Page 14

    14 4 mounting vegadis 81 • 43814-en-170913 2 1 3 fig. 10: vegadis 81 for tube mounting 1 4 screws m6 x 100 2 mounting brackets 3 tube (diameter 1" to 2").

  • Page 15

    15 5 connecting to the sensor vegadis 81 • 43814-en-170913 5 connecting to the sensor 5.1 preparing the connection always keep in mind the following safety instructions: warning: connect only in the complete absence of line voltage. • the electrical connection must only be carried out by trained per...

  • Page 16

    16 5 connecting to the sensor vegadis 81 • 43814-en-170913 information: the terminal block is pluggable and can be removed from the electronics. To do this, lift the terminal block with a small screwdriver and pull it out. When reinserting the terminal block, you should hear it snap in. Proceed as f...

  • Page 17

    17 5 connecting to the sensor vegadis 81 • 43814-en-170913 9. Tighten the compression nut of the cable entry gland. The seal ring must completely encircle the cable 10. Reinsert the display and adjustment module, if one was installed 11. Screw the housing lid back on 5.3 wiring plan 3 2 1 display fi...

  • Page 18

    18 5 connecting to the sensor vegadis 81 • 43814-en-170913 5 3 4 1 2 display power supply fig. 13: electronics and terminal compartment - vegadis 81 with heating 1 contact pins for the display and adjustment module 2 spring-loaded terminals for conntection of the voltage supply for the heating 3 spr...

  • Page 19

    19 5 connecting to the sensor vegadis 81 • 43814-en-170913 power supply display (+)1 2(-) 5 6 7 8 4 3 2 1 fig. 15: wiring plan vegadis 81 for 4 … 20 ma/hart sensors, display and adjustment module with heating 1 to the sensor 2 ground terminal for connection of the cable screen 3) 3 voltage supply fo...

  • Page 20

    20 5 connecting to the sensor vegadis 81 • 43814-en-170913 power supply display (+)1 2(-) 5 6 7 8 4 2 1 fig. 17: wiring plan vegadis 81 for pa/ff sensors, display and adjustment module with heating 1 to the sensor 2 voltage supply for the heating 5.4 connection examples 4 … 20 ma/hart 5 6 7 8 4 2 3 ...

  • Page 21

    21 5 connecting to the sensor vegadis 81 • 43814-en-170913 the connection between vegadis 81 and sensor is made with a standard cable according to the table. Vegadis 81 sensor terminal 5 terminal 5 terminal 6 terminal 6 terminal 7 terminal 7 terminal 8 terminal 8 5 6 7 8 4 2 3 1 fig. 20: connection ...

  • Page 22

    22 5 connecting to the sensor vegadis 81 • 43814-en-170913 5.5 connection examples profibus pa, foundation fieldbus 5 6 7 8 4 2 3 1 fig. 21: connection example profibus pa, foundation fieldbus - connection via m12 plug connector and open cable end 1 sensor 2 vegadis 81 3 connection cable connection ...

  • Page 23: Module

    23 6 set up with the display and adjustment module vegadis 81 • 43814-en-170913 6 set up with the display and adjustment module 6.1 short description the display and adjustment module is used for measured value display, adjustment and diagnosis. It can be mounted in the following housing versions an...

  • Page 24

    24 6 set up with the display and adjustment module vegadis 81 • 43814-en-170913 fig. 22: mounting of the display and adjustment module 6.3 adjustment system 1 2 fig. 23: display and adjustment elements 1 lc display 2 adjustment keys • [ok] key: – move to the menu overview – confirm selected menu – e...

  • Page 25

    25 6 set up with the display and adjustment module vegadis 81 • 43814-en-170913 – change measured value presentation – select list entry – select menu items in the quick setup menu – select editing position • [+] key: – change value of the parameter • [esc] key: – interrupt input – jump to next high...

  • Page 26

    26 6 set up with the display and adjustment module vegadis 81 • 43814-en-170913 approx. 60 minutes after the last pressing of a key, an automatic reset to measured value indication is triggered. Any values not confirmed with [ok] will not be saved..

  • Page 27: 7  Setup Via Pactware

    27 7 setup via pactware vegadis 81 • 43814-en-170913 7 setup via pactware 7.1 connect the pc the pc is connected via the interface adapter vegaconnect to vegadis 81. 3 1 2 fig. 25: connection of the pc via interface adapter 1 usb cable to the pc 2 interface adapter vegaconnect 3 vegadis 81 the wirel...

  • Page 28

    28 7 setup via pactware vegadis 81 • 43814-en-170913 2 3 1 4 fig. 26: connection of the pc via bluetooth usb adapter 1 display and adjustment module 2 vegadis 81 3 bluetooth usb adapter 4 pc 7.2 parameter adjustment for parameter adjustment of the instrument via a windows pc, the configuration softw...

  • Page 29

    29 7 setup via pactware vegadis 81 • 43814-en-170913 fig. 27: example of a dtm view all device dtms are available as a free-of-charge standard version and as a full version that must be purchased. In the standard version, all functions for complete setup are already included. An assistant for simple...

  • Page 30: 8  Setup Via App

    30 8 setup via app vegadis 81 • 43814-en-170913 8 setup via app 8.1 connect with smartphone/tablet the display and adjustment module with integrated bluetooth func- tionality allows connection of the vegadis 81 to smartphones/tablets with ios or android operating system. 2 1 3 fig. 28: connection of...

  • Page 31

    31 8 setup via app vegadis 81 • 43814-en-170913 fig. 29: example of an app view for sensor adjustment.

  • Page 32

    32 9 maintenance and fault rectification vegadis 81 • 43814-en-170913 9 maintenance and fault rectification 9.1 maintenance if the instrument is used correctly, no maintenance is required in normal operation. 9.2 rectify faults the operator of the system is responsible for taking suitable meas- ures...

  • Page 33: 10 Dismount

    33 10 dismount vegadis 81 • 43814-en-170913 10 dismount 10.1 dismounting steps warning: before dismounting, be aware of dangerous process conditions such as e.G. Pressure in the vessel or pipeline, high temperatures, cor- rosive or toxic products etc. Take note of chapters " mounting " and " connect...

  • Page 34: 11 Supplement

    34 11 supplement vegadis 81 • 43814-en-170913 11 supplement 11.1 technical data materials and weights materials Ʋ plastic housing plastic pbt (polyester) Ʋ aluminium housing aluminium die-casting alsi10mg, powder-coated (basis: polyester) Ʋ stainless steel housing 316l precision casting, blasted Ʋ s...

  • Page 35

    35 11 supplement vegadis 81 • 43814-en-170913 ambient temperature Ʋ without display and adjustment module -40 … +80 °c (-40 … +176 °f) Ʋ with display and adjustment module -20 … +70 °c (-4 … +158 °f) Ʋ with heated display and adjustment module -40 … +70 °c (-40 … +158 °f) process conditions vibratio...

  • Page 36

    36 11 supplement vegadis 81 • 43814-en-170913 materials Ʋ housing abs Ʋ inspection window polyester foil functional safety sil non-reactive interface to the sensor data transmission digital (i²c-bus) configuration, connection cable four-wire, depending on the sensor version, screened cable length se...

  • Page 37

    37 11 supplement vegadis 81 • 43814-en-170913 approvals instruments with approvals can have different technical specifications depending on the version. For that reason the associated approval documents of these instruments have to be carefully noted. They are part of the delivery or can be download...

  • Page 38

    38 11 supplement vegadis 81 • 43814-en-170913 vegadis 81, aluminium housing 1 ø 86 mm (3.39") ~ 75,2 mm (2.95") 87 mm (3.43" ) 82 mm (3.23" ) 97 mm (3.82" ) 5 mm (0.2") 97 mm (3.82") fig. 31: vegadis 81 with aluminium housing 1 cable gland with version with heated display and adjustment module.

  • Page 39

    39 11 supplement vegadis 81 • 43814-en-170913 vegadis 81, stainless steel precision cast housing 1 ø 86 mm (3.39") ~ 75 mm (2.95") 87 mm (3.43" ) 82 mm (3.23" ) 97 mm (3.82" ) 5 mm (0.2") 97 mm (3.82") fig. 32: vegadis 81 with stainless steel, precision cast housing 1 cable gland with version with h...

  • Page 40

    40 11 supplement vegadis 81 • 43814-en-170913 ø 29...60 mm (1.14"...2.36") 82 mm (3.23") 15 mm (0.59") 97 mm (3.82") 20 mm (0.79") m6 2 mm (0.08") 20 mm (0.79") 2 mm (0.08") 20 mm (0.79") 48...84 mm (1.89"...3.31") fig. 34: brackets for tube mounting of vegadis 81.

  • Page 41

    41 11 supplement vegadis 81 • 43814-en-170913 11.3 industrial property rights vega product lines are global protected by industrial property rights. Further information see www.Vega.Com. Vega produktfamilien sind weltweit geschützt durch gewerbliche schutzrechte. Nähere informationen unter www.Vega....

  • Page 42

    42 notes vegadis 81 • 43814-en-170913.

  • Page 43

    43 notes vegadis 81 • 43814-en-170913.

  • Page 44

    Printing date: vega grieshaber kg am hohenstein 113 77761 schiltach germany 43814-en-170913 all statements concerning scope of delivery, application, practical use and operat- ing conditions of the sensors and processing systems correspond to the information available at the time of printing. Subjec...