    1 107284-01 - 9/16 warning if installing boiler sizes 080 or 180, do not attempt to convert 080 for use with lp at altitudes above 2000 ft (610 m). Also, do not attempt to convert 180 for use with lp gas at altitudes above 7800 ft (2377 m). Attempts to do so may result in unreliable operation, prope...

  • Page 2

    2 high altitude start-up instructions for natural gas 1. Install boiler in accordance with the installation, operating and service instructions manual supplied with the boiler. Follow all instructions in section xi (start-up and checkout) up through step 14. Skip step 10. 2. Verify the gas inlet pre...

  • Page 3

    3 e. Allow boiler to operate for approximately 5 minutes before taking combustion readings. At both high and low fi re, co readings should be less than 200ppm air-free. Acceptable co 2 and o 2 ranges are shown in table 3. Adjust the throttle at high fi re if fl ue gases are not in range: • to reduce...

  • Page 4

    4 figure 1b: gas valve detail (150mbh, 180mbh) table 2: starting number of throttle turns for conversion to lp gas boiler size # counterclockwise turns (from fully closed) 080 100 3 120 4 150 5-3/4 180 6-1/2 warning throttle adjustments shown in table 2 are approximate. The fi nal throttle setting m...

  • Page 5

    5 boiler size fuel acceptable combustion readings approximate derate per 1000 ft. Measured % co 2 measured % o 2 max co (pm air-free) 4501 - 7800 ft. * (1350 - 2377 m) 7801 - 10200 ft. ** (2377 - 3109 m) 80 ng 8.7-9.1 4.9-5.6 200 0.0% 3.1% lp 100 ng 8.5-9.3 4.5-6.0 200 0.0% 3.1% lp 9.9-10.2 5.4-5.8 ...