Venmar 1200 cfm Installation And Operation Manual - 4  Airflow Measurement

Manual is about: Venmar Light Commercial Heat Recovery Ventilators Installation Manual

Summary of 1200 cfm

  • Page 1

    Light commercial heat recovery ventilators vb0002 vb0003 vb0001 600 cfm 700 cfm 1200 cfm installation, operation and service instructions 06/00 04597.

  • Page 2: Contents

    Page 2 contents 1 safety considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2 installation 2.1 inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2.2 mounting location re...

  • Page 3: 1  Safety Considerations

    Page 3 1 safety considerations hazards may exist within this equipment because it contains electrical and powerful moving components. Only qualified service personnel should install or service this equipment. Untrained personnel can perform basic maintenance such as maintaining filters. Observe prec...

  • Page 4

    Page 4 the supply and exhaust ducts connected to outside, as well as any ducts passing through an unconditioned space, must have a minimum insulation value of r5. In addition, a continuous integral vapor barrier over the duct insulation must be used. Air balancing dampers are recommended for both su...

  • Page 5: 3  Controls

    Page 5 2.8 electrical connections power a terminal block and strain relief bushing or a junction box is provided for line voltage to make the necessary power connections. The electrical requirements are as follows: control box access for low speed setting (600 cfm/1200 cfm only) disconnect power to ...

  • Page 6: 4  Airflow Measurement

    Page 6 recirculation defrost module (optional - factory installed) the recirculation defrost module is only available with the 600 cfm and 1200 cfm units. The defrost cycle is electronically controlled in response to the outside temperature 23°f to -22°f (-5°c to -30°c). On a call for defrost, the s...

  • Page 7: 5 Maintenance and Service

    Page 7 4.2 balancing procedure before proceeding with balancing, all windows, overhead doors and walk-in doors should be closed and exhaust systems should be turned off. The connections between the flow stations and the ducts must be sealed with tape. Mount the magnehelic gauge in a convenient locat...

  • Page 8

    Page 8 allow the heat recovery core to soak for three hours in warm water and mild soap. Rinse under a heavy stream of water. Fans blower wheels and fan housing should be checked for dirt build-up. If they appear dirty, it may be necessary to remove the blower assembly and then vacuum the dust out t...

  • Page 9: Appendix A

    Page 9 3/8" (10mm) threaded rod (supplied by others) rubber vibration isolater cabinet mounted u channel wooden curb (supplied by others) bolt to floor space must be left to allow connection of drain lines with adequate slope for drainage dry contacts dry contacts vd0003a space must be left to allow...

  • Page 10: Appendix B

    Page 10 8.000" [203] 4.000" [102] 8.000" [203] 3.535" [90] 4.000" [102] 28.005" [71 1 ] 14.000" [356] 5.859" [149] 13.375" [340] 23.500" [597] 2.750" [70] 14.000" [356] 6.500" [165] 8.000" [203] 8.000" [203] 14.103" [358] 7.705" [196] 4.000" [102] 24.500" [622] 12.005" [305] 4.028" [102] 34.000" [86...

  • Page 11: Appendix B Continued

    28.12" [714] 14.00" [356] 4.00" [102] 1.75" [44] 8.00" [203] 2.75" [70] 19.207" [488] 5.125" [130] access door strap mounting location drain fitting note: for units with the reversed door option, interior components will appear as a mirror image of the above diagram. 49.550" [1259] line power contro...

  • Page 12: Appendix B Continued

    Page 12 41.206" [1047] 40.326" [1024] 20.000" [508] 5.715" [145] 20.620" [524] 14.250" [362] 34.000" [864] 5.125" [130] 19.207" [488] 4.028" [102] 1 1.325" [288] 12.000" [305] 15.000" [381] 20.000" [508] 4.000" [102] 2.750" [70] 1 1.000" [279] 20.000" [508] 9.878" [251] 24.500" [622] 8.000" [203] 8....

  • Page 13: Appendix B Continued

    Page 13 8.00" [203] 1.75" [44] 10.00" [254] 20.00" [508] 2.75" [70] alimentation électrique borniers 49.550" [1259] localisation de la courroie de fixation aspiration d’air frais Évacuation d’air vicié 5.125" [130] noyau de récupération de chaleur option de porte inversée porte d’accès 15.00" [381] ...

  • Page 14: Appendix B Continued

    Page 14 10.000" [254] dimensions in [ ] are in millimeters center of gravity direction of airflow hr v700i lbs kg 32.74 14.85 68.46 31.05 35.20 15.97 73.60 33.38 210.00 1.875" [48] exhaust air opening suppl y air opening 20.750" [527] 8.000" [203] 10.750" [273] 7.500" [191] 10.605" [269] 12.104" [30...

  • Page 15: Appendix C

    Page 15 flow measuring station (fms) balancing damper canvas vibration isolator min. 12" (305mm) min. 30" (762mm) reverse door option exhaust air from building fresh air from outside min. 8" (203mm) (optional) canvas vibration isolator min. 12" (305mm) vp0001a min.12" (304mm) flow measuring station ...

  • Page 16: Appendix D

    Page 16 to drain copper or plastic pipe plastic drain fittings plastic hose water trap coupler 3/4"npt note: all hose, pipe & couplers to be supplied by others t d i all hose, pipe, and couplers to be supplied by others. Plastic hose water trap 3/4" npt to drain copper or plastic pipe plastic drain ...

  • Page 17: Appendix E

    Page 17 wall control class 2 voltage black occupied timer/ sensor f f low common high red green yellow note: connections are all dry contacts except wall control and 24vac power supply. Use of 24vac circuit requires isolating contacts (ex. Thermostat) to prevent interconnection of class 2 outputs. V...

  • Page 18: Appendix E Continued

    Page 18 jumper (factory installed) occ. Control (field installed) nsb timer venmar pn 1604128 1 m 2 3 4 5 jumper wall control class 2 voltage black occupied timer/ sensor f f low common high red green yellow note: connections are all dry contacts except wall control and 24vac power supply. Use of 24...

  • Page 19: Appendix F

    Page 19 control cover plate control box remote control access plate remote wiring terminal block hrv cabinet ve0001a r ed low speed (red) remove power before installing or removing ju1-f extended defrost jumper 12 pin 2 pin med speed (blue) low to medium, move the fork connector: to change the minim...

  • Page 20: Appendix G

    Page 20 although the 600 cfm, 700 cfm and 1200 cfm models have good ef ficiencies, the supply air could be colder than the ambient room air . It is possible to eliminate the discomfort associated with this temperature dif ference by installing an electric duct heater . This will temper the air befor...

  • Page 21: Appendix H

    Page 21 appendix h wiring diagram wiring diagram for 600 cfm unit interlock (ff) w all control black ve0023a 48445 power control board -t 8 9 10 11 12 13 14 t7 1 2 3 4 5 6 7 t7 bl bl g r y bk j3 1 j3 2 j3 8 j3 7 j3 6 j3 9 w all control red occ./ unocc. Remote f a n common autotransformer al terna te...

  • Page 22: Appendix H Continued

    Page 22 appendix h continued wiring diagram wiring diagram for 700 cfm unit ve0024a j1 6 j1 9 j1 2 k7 j1 3 lo gnd l1 neut 120vca 60hz color code 110 vol ts low vol t age and field wire j1 8 1 2 3 4 5 6 7 t7 interlock (ff) w all control black 8 9 10 11 12 13 14 t7 w all control red occ./ unocc. Remot...

  • Page 23: Appendix H Continued

    Page 23 appendix h continued wiring diagram wiring diagram for 1200 cfm unit interlock (ff) w all control black ve0022a . . . . . . Ju1 j4 2 1 a b c d e f g 1 2 3 4 5 6 7 8 9 j3 f f i oc ol y r g b 4 7 6 9 48445 power control board j1 3 2 1 8 1 2 3 j2 comm. N/c n/o -t defrost temp . Sensor 8 9 10 11...

  • Page 24: Appendix I

    For technical assistance and warranty information, please call your local supplier. Appendix i trouble shooting symptoms possible causes solutions inside air is too dry over ventilation - speed setting adjust speed setting too high dehumidistat setting is too low set dehumidistat control in a higher...