Vent-a-Hood CILH9 ISLAND RANGE HOOD Installation Instructions Manual - page 4
Page 4
L123 1210A
8” Transition
Opening 9”
Above Top
of Hood
5” x 16”
Exhaust
Opening
Centerline
of Hood
Vent Holes
Electrical
Centerline
of Hood
¾”
2 ⁄ ”
Centerline
of Hood
Centerline
of Hood
Vent Holes
Electrical (2)
11”
11”
7 ¼”
8” Transition
Opening (2)
3” Below Top
of Hood
5” x 16”
Exhaust
Opening (s)
9"
16"
5"
8" Round
8" Round
9"
16"
5"
8" Round
8" Round
9"
9"
9"
9"
Brass Screws
A
Blower Wheel
B
Blower Housing
Installation Details Continued
8) Turn the hood over on the protective surface. Attach the transition to each dual blower assembly and seal with duct
tape. The transition must fit inside the exhaust collar on the blower assembly.
7) Remove the three screws retaining the blower motors. Unplug
and remove the motors, taking care not to damage the blower
wheels. It is not necessary to remove the blower wheels from
the motors.
Connection Diagram (36”- 54” Widths)
(Note: CILH9 is not available in 36" width.)
550 CFM T200 Dual Blower
(Top View)
VP565 Transition
(Included)
Transition Installed
(Side View)
Connection Diagram (60”- 66” Widths)
1100 CFM T2+200 Dual Blower
(Top View)
VP565 Transition
(Two included)
Transitions Installed
(Side View)
Warning: Make sure power is off and locked at the service disconnecting
means on the service panel during installation.
9) Install an appropriate 1/2” UL listed electrical wire clamp through each motor box electrical opening on the top of the
hood. Install electrical wiring from the service panel to the hood location for each motor box. Consult the connection
diagrams (below) for further details on electrical placement. Support the hood beneath the location where it will hand
and feed the electrical wire(s) through the wire clamp(s). Tighten the wire clamp(s).
Model
Volts
Amps*
Hz
RPM
CFM
SP@0.0" Equivalent CFM
•
CFM
SP@0.1"
CFM
SP@0.2"
CFM
SP@0.3"
Minimum Round
Duct Size
Sones
#
T200 Island Dual
115
2.9
60
1550
550
900
507
471
431
8" (50 in.
2
)
6.0
* Add 0.5 amp for each halogen light.
• Because the Magic Lung
®
blower uses centrifugal filtration rather than conventional baffle or mesh filters, the Magic Lung
®
blower can handle cooking equipment with higher cubic feet per minute (CFM) requirements and can deliver equivalent CFM much more
efficiently than other than other filtration systems. When comparing the Magic Lung
®
with other blower units made by other manufacturers, use the “Equivalent CFM”.
#
Ratings in accordance with the Standard Test Code by the Energy Systems Laboratory of the Texas Engineering Experiment Station.
6) Remove the blower shields (A) by loosening the two brass screws on the bottom of the shield. Gently close the back
draft dampers from the top side of the hood. To remove the blower housings, unsnap the suitcase latches (B) (one on
each side of the housing). The housings should be pulled forward and gently “tipped” to clear the blower wheels and
then out of the hood. Place the hood upside-down on the protective surface.