Vents VCN 100 User Manual

Manual is about: VCN series

Summary of VCN 100

  • Page 1

    User's manual 2012 vcn.

  • Page 2: Vcn

    2 use basic technical characteristics the centrifugal fans vcn series are designed for extract ventilation of living spaces, offices, shops, garages, kitchens, bathrooms and other residential and public premises. The fans are designed for top installation at ventilation shaft outlets. The fans are r...

  • Page 3: Vcn

    3 designation key example vents vcn 100 vents vcn 150 k centrifugal fan for mounting with 100 mm air duct. Centrifugal fan with a backdraft damper for mounting with 150 mm air duct. Ø Ø 1 table 1 fan type 1 casing; 2 cover; 3 bracket; 4 bracket; 5 turbine; 6 selftapping screw; 7 capacitor; 8 termina...

  • Page 4: Vcn

    4 table 2 fan type vcn / 100 100 К vcn vcn vcn 125 125 К / vcn vcn 150 150 К / vcn vcn 160 160 К / vcn vcn 200 200 К / 1~ 230 v, 50 hz w А m /h 3 r p m db(a) 0 c ip 1~ 230 1~ 230 1~ 230 1~ 230 71 75 96 95 96 0,31 0,33 0,42 0,41 0,42 325 (295*) 485 (450*) 630 (565*) 650 (590*) 700 (640*) 2530 2475 24...

  • Page 5: Vcn

    5 the fan ingress protection (ip) rating from solid objects and liquids ipx4 demands extra protection against water ingress. To protect the fan against water ingress mount a hood at the intake pipe or under the roof. Take steps to prevent ingress of smoke, carbon monoxide and other combustion produc...

  • Page 6: Vcn

    6 2 disconnect the fan from power mains prior to any wireworks (fig. 3). To install the fan on the wall remove the selftapping screws 6 and remove the cover 2 (fig. 4), drill the holes for dowels in compliance with mounting seats on the fan casing (fig. 5,6,7) and install the fan with screws (fig. 8...

  • Page 7: Vcn

    7 5 7 6 8 vcn.

  • Page 8: Vcn

    8 connectio to power mains connect the fan to singlephase power mains through the automatic circuit breaker integrated into the fixed power mains. Cut power supply off prior to wireworks. The contact gap on all poles must be at least 3 mm. Connect the power cable to the terminal block 8 following th...

  • Page 9: Vcn

    9 disconnect the fan from power mains prior to all maintenance operations. Maintenance of the fans means periodic cleaning of the fan surfaces from dirt and dust when the fan is switched off. Use a soft cloth or compressed air to remove dust (fig. 13). The impeller blades require thorough cleaning e...

  • Page 10: Vcn

    10 storage rules store the fan in manufacturer's packaging in a ventilated room at temperatures between +5°c and +40°c and relative humidity not more than 80% at +20°c. The fan is not rated for operation in a medium containing acid or alkali vapours or other aggressive admixtures. Manufacturer's war...

  • Page 11: Vcn

    11 all the defects and faults resulting from mechanical effect during operation process or natural wearandtear shall not be covered by the warranty conditions. The malfunctions caused by violence of operation, servicing and maintenance guidelines either by customer or third parties or caused by unau...

  • Page 12: Vcn

    Acceptance certificate centrifugal fan vents vcn __________ " " the fan is recognized as serviceable. Stamp of the acceptance inspector date of production (name of the vendor, stamp of the shop) date of sale v06 03 en warranty card vcn 12.