Installation
1. Disconnect power prior to the installation. Use a properly rated voltage sensing device to ensure power is off.
2. Cut a mounting hole and install the E61 as shown.
CLIC
K
CLIC
K
CLA
CK
CL
AC
K
3. Wire the meter (see the Wiring section).
4. Reconnect power to the meter.
5. Configure the meter (see the Configuration section).
Wiring
For all terminals, apply the correct torque.
Voltage Inputs
0.82 - 3.31 mm
2
(18 - 12 AWG)
0.5 - 0.6 N·m (4.4 - 5.3 in·lb)
Control Power
0.82 - 3.31 mm
2
(18 - 12 AWG)
0.5 - 0.6 N·m (4.4 - 5.3 in·lb)
Status Input/Digital Output
0.33 - 2.08 mm
2
(22 - 14 AWG)
0.5 - 0.6 N·m (4.4 - 5.3 in·lb)
Current Inputs
0.82 - 3.31 mm
2
(18 - 12 AWG)
0.9 - 1.0 N·m (8.0 - 9.0 in·lb)
Voltage Inputs
UL CAT III, 20-347V
L-N
/35-600V
L-L
IEC CAT III, 20-400V
L-N
/35-690V
L-L
V1 V2 V3 V4
(1) (2) (3) (4)
L1 L2
(8) (9)
Control Power
100-277V
L-N
/415V
L-L
±10% ~
50/60 ± 5 Hz
125-250V ± 20%
Status Input/Digital Output
40V max.
20mA max. 36V max.
24V
8mA max.
D1+ D2+
(60) (62)
S1+ S2+
(40) (42)
−/C +
(57) (56)
Current Inputs
1A/5A nom., 0.0005-5(6)A
(10) (11) (12) (13) (14) (15)
I1+ I1- I2+ I2- I3+ I3-
Modbus TCP/IP
(30)
Act Link
10/100
The ground terminal is not available on the meter. Connect shield to ground at the other end.
Control power terminals (L1 and L2) are not polarity sensitive. If using an AC power supply with neutral, connect the neutral
to the meter’s L2 terminal. Always use a fuse on L1. Fuse L2 when connecting an ungrounded neutral to the control power.
If using a control power transformer, fuse both the primary and the secondary sides of the transformer. Use fuses/circuit
breakers that are rated for the installation voltage and sized for the available fault current.
Use shielded ethernet cable. There is no ground terminal on the meter, so connect shield to ground at the other end of the
cable. Install the meter in a location that minimizes the overall ethernet cable rounting length.
ZL0142-0B Page 3 of 6 ©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 1214
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
ZL0142-0B Page 4 of 6 ©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 1214
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
CT Wiring
Clearly label the device’s disconnect circuit mechanism and install it within easy reach of the operator. Use fuses/circuit
breakers that are rated for the installation voltage and sized for the available fault current. A fuse for neutral is required if the
source neutral is not grounded.
1 Phase
1 Phase, 2 Wire, L-N
1 Phase, 2 Wire, L-L
1 Phase, 3 Wire, L-L-N
Shorting
Block
Fuses and
Disconnect
V1 V2 V3 Vn
(I1)
(I3)
(I2)
+
L
N
+ - + - + -
Shorting
Block
Fuses and
Disconnect
V1 V2 V3 Vn
(I1)
(I3)
(I2)
+
L1
L2
+ - + - + -
Shorting
Block
Fuses and
Disconnect
V1 V2 V3 Vn
(I1)
(I3)
(I2)
+
+
L1
L2
N
+ - + - + -
3 Phase, 3 Wire
1 CT, Balanced Load
2 CT
3 CT
Shorting
Block
Fuses and
Disconnect
V1 V2 V3 Vn
(I1)
(I3)
(I2)
+
L1
L2
L3
+ - + - + -
Shorting
Block
Fuses and
Disconnect
V1 V2 V3 Vn
(I1)
(I3)
(I2)
+
+
L1
L2
L3
+ - + - + -
Shorting
Block
Fuses and
Disconnect
V1 V2 V3 Vn
(I1)
(I3)
(I2)
+
+
+
L1
L2
L3
+ - + - + -
1 CT, 2 PT, Balanced Load
2 CT, 2 PT
3 CT, 2 PT
Fuses and
Disconnect
Shorting
Block
PT Primary Fuses and
Disconnect Switch
V1 V2 V3 Vn
(I1)
(I3)
(I2)
+
L1
L2
L3
+ - + - + -
Fuses and
Disconnect
Shorting
Block
PT Primary Fuses and
Disconnect Switch
V1 V2 V3 Vn
(I1)
(I3)
(I2)
+
+
L1
L2
L3
+ - + - + -
Fuses and
Disconnect
Shorting
Block
PT Primary Fuses and
Disconnect Switch
V1 V2 V3 Vn
(I1)
(I3)
(I2)
+
+
+
L1
L2
L3
+ - - + -
Wiring (cont.)