SECTION 7 INSTRUCTING THE USER
7.1
Hand over the copy of the Users Instructions
and the boiler log book supplied with the
appliance, together with these instructions.
Explain how to operate the boiler correctly
and how to use the timeclock and room
thermostat if fitted.
7.2
Show the user how to switch off the appli-
ance and indicate the position of the electric
supply isolator.
7.3
Inform the user of the location of all drain
cocks and air vents.
6.12.4
Re-check the flue system for soundness and
adequacy of supports.
6.13
Concluding Operations
6.13.1
If external/internal controls have been
disconnected and terminals 2 & 3 temporar-
ily linked, remove the link and reconnect the
controls circuit. Check the operation of the
controls.
6.14
Disconnect filling loop, fit filling loop cap.
Leave filling loop in a safe and accessible
place.
6.14.1
Reposition the front control panel and fit the
front boiler casing panel (fig. 18).
6.15
Supplementary Instructions for Fitting &
Removing Optional Time Clock and for
Wiring to External Controls.
Section 10 Appendices A and B at the rear
of this manual provides full instruction for
fitting and wiring the optional built-in time
switches and for wiring to external controls.
6.16
Complete details of the boiler, controls,
installation and commissioning in the log
book supplied with the boiler. This is an
important document which must be correctly
completed and handed to the user. Failure
to install and commission this appliance to
the manufacturers instructions may invali-
date the warranty.
7.4
Explain how to turn the appliance off for both
short and long periods and advise on the
precautions necessary to prevent damage
should the appliance be inoperative when
freezing conditions may occur.
7.5
Show the user the filling loop position its
function and how to repressurise the system
using the filling/inlet valve.
7.6
Finally, advise the user that, for continued
safe and efficient operation, the appliance
must be serviced by a competent person at
least once a year.
SECTION 8 SERVICING INSTRUCTIONS
8.1
General
To ensure the continued safe and efficient
operation of the appliance, it is recom-
mended that it is checked and serviced as
necessary at regular intervals.
The frequency of servicing will depend upon
the particular installation conditions and
usage, but in general, once per year should
be adequate.
It is the law that any servicing work is
carried out by a competent person such as
a Vokèra service engineer, approved
service agent, British Gas or other CORGI
registered personnel.
The following instructions apply to the boiler
and its controls, but it should be remem-
bered that the central heating and domestic
hot water systems will also require attention
from time to time.
8.2
Important Notes
WARNING: Having carried out preliminary
flame checks and before starting any
servicing work, switch OFF the mains
electricity supply and disconnect the plug at
the main isolating switch and socket. (If a
switch is used remove the fuse.)
Turn off gas supply at the gas service tap
fitted to the appliance.
Always test for gas soundness after any
service work and after exchanging any gas
carrying component.
8.3
Recommended Routine Servicing
8.3.1
Annual Servicing
When servicing is required the following
procedures should be carried out.
1. Inspect exterior for signs of damage and
deterioration, particularly of flue pipework
and electrical connections.
2. Turn off mains electricity and remove
front casing (see clause 8.4.).
3. Replace fuse if previously removed (8.2.
above) and turn on electricity. Run the boiler
for a few minutes in the domestic hot water
mode to permit inspection of its operation.
This is accomplished by opening a domestic
hot water draw off tap and inspecting burner
for yellowing of flame tip, flame lift off or
sooting.