Voltronic Power 1K User Manual

Summary of 1K

  • Page 1

    1k/2k/3k online ups uninterruptible power supply system user manual.

  • Page 2

    Table of contents 1. Important safety warning ............................................................................................... 1 1-1. Transportation ..................................................................................................... 1 1-2. Preparation ..................

  • Page 3

    1 1. Important safety warning please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating i...

  • Page 4

    2 1-5. Maintenance, service and faults  the ups system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel.  caution - risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet), components inside the ups sys...

  • Page 5

    3 2. Installation and setup note: before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use. 2-1. Rear panel view 1k india type iec type nema type schuko type universal type 1kl india type iec typ...

  • Page 6

    4 2kl india type iec type schuko type universal type 3k india type iec type nema type schuko type universal type 3kl india type iec type schuko type universal type 1. Ac input 2. Input circuit breaker 3. Usb communication port 4. Rs-232 communication port 5. Snmp intelligent slot (option) 6. Externa...

  • Page 7

    5 2-2. Setup the ups step 1: ups input connection plug the ups into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords.  for 200/208/220/230/240vac models: the power cord is supplied in the ups package.  for 100/110/115/120/127vac models: the power cord is attached to th...

  • Page 8

    6 step 6: external battery connection this ups is not including batteries. Please connect external batteries as below chart..

  • Page 9

    7 3. Operations 3-1. Button operation button function on/mute button  turn on the ups: press and hold on/mute button for at least 2 seconds to turn on the ups.  mute the alarm: when the ups is on battery mode, press and hold this button for at least 5 seconds to disable or enable the alarm system....

  • Page 10

    8 display function remaining backup time information indicates the remaining backup time in pie chart. Indicates the remaining backup time in numbers. H: hours, m: minute, s: second fault information indicates that the warning and fault occurs. Indicates the warning and fault codes, and the codes ar...

  • Page 11

    9 3-3. Audible alarm battery mode sounding every 4 seconds low battery sounding every second overload sounding twice every second fault continuously sounding bypass mode sounding every 10 seconds 3-4. Lcd display wordings index abbreviation display content meaning ena enable dis disable esc escape h...

  • Page 12

    10 230: presents output voltage is 230vac (default) 240: presents output voltage is 240vac for 100/110/150/120/127 vac models, you may choose the following output voltage: 100: presents output voltage is 100vac 110: presents output voltage is 110vac 115: presents output voltage is 115vac 120: presen...

  • Page 13

    11 for 100/110/115/120/127 vac models, the setting voltage in parameter 3 is from -3v to -12v of the nominal voltage. (default: -6v)  06: bypass enable/disable when ups is off interface setting parameter 3: enable or disable bypass function. You may choose the following two options: ena: bypass ena...

  • Page 14

    12 3-6. Operating mode description operating mode description lcd display online mode when the input voltage is within acceptable range, ups will provide pure and stable ac power to output. The ups will also charge the battery at online mode. Eco mode energy saving mode: when the input voltage is wi...

  • Page 15

    13 3-7. Faults reference code fault event fault code icon fault event fault code icon bus start fail 01 x inverter voltage low 13 x bus over 02 x inverter output short 14 bus under 03 x battery voltage too high 27 bus unbalance 04 x battery voltage too low 28 inverter soft start fail 11 x over tempe...

  • Page 16

    14 4. Troubleshooting if the ups system does not operate correctly, please solve the problem by using the table below. Symptom possible cause remedy no indication and alarm even though the mains is normal. The ac input power is not connected well. Check if input power cord firmly connected to the ma...

  • Page 17

    15 symptom possible cause remedy battery backup time is shorter than nominal value batteries are not fully charged charge the batteries for at least 5 hours and then check capacity. If the problem still persists, consult your dealer. Batteries defect contact your dealer to replace the battery..

  • Page 18

    16 5. Storage and maintenance operation the ups system contains no user-serviceable parts. If the battery service life (3~5 years at 25°c ambient temperature) has been exceeded, the batteries must be replaced. In this case, please contact your dealer. Storage before storing, charge the ups 5 hours. ...

  • Page 19

    17 6. Specifications model 1k 2k 3k capacity* 1000 va / 800 w 2000 va / 1600 w 3000 va / 2400 w input voltage range low line transfer 85vac/75vac/65vac/55vac± 5% or 160vac/140vac/120vac/110vac± 5% (ambient temp. 0 c) ( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0) low li...