WAGNER PC 15 Service Manual - page 12
Attention: The frequency converter is delivered in a non-programmed state. The required
settings (with grey background in the parameter list) should be programmed as
per the following instructions before the system is started up.
Frequency converter programming
1.
Connect to mains
2.
Move main switch to "I" position.
3.
Move rotation direction switch to "0".
Warning: do not touch any live components.
4.
Press "DSP/FUN" button, "F000" appears in display.
5.
Select required function number by pressing the "
왖" and "왔" buttons.
The "
6.
Switch from the function number display to the selected function number setting display using the
"READ/ENTER" button.
7.
Set the value as specified in the "Parameter list" using the "
왖" and "왔" buttons.
8.
Press "READ/ENTER" to store the setting. "FXXX" appears in the display again.
9.
Select next function number using "
왖" and "왔" and proceed in same order.
10. After storing the last setting, press the "DSP/FUN" button twice to leave programming mode and switch back to
the original display.
10
Program frequency converter
Frequency converter control panel and function overview
Red LED on for external frequency
specification (Fn_11=1/2/3)
Red LED on for external rotation
direction specification (Fn_10=1)
Red LED on for output frequency
or speed display
If red LED is on, FC is in programming mode
Start/stop command (Fn_10=0)
Rotation direction specification (Fn_10=0)
Potentiometer (Fn_11=1)
Red LED on for right-handed rotation
Red LED on for left-handed rotation
Red LED on: output voltage display
Red LED on: motor current display
Program selection
Increase/decrease values
Acknowledge error or move cursor from
ones to tens to hundreds digit
Key for displaying and storing
parameters