WAGO 750-880 Manual

Manual is about: WAGO-I/O-SYSTEM 750 ETHERNET Programmable Fieldbus Controller 10 / 100 Mbit/s; digitale und analoge Signale

Summary of 750-880

  • Page 1

    Pos: 2 /dokumentation allgemein/einband/einband deckblatt @ 9\mod_1285229289866_0.Doc @ 64941 @ @ 1 manual wago-i/o-system 750 ethernet programmable fieldbus controller 750-880, 750-880/025-000 10 / 100 mbit/s; digitale und analoge signale version 1.0.1 pos: 3 /alle serien (allgemeine module)/hinwei...

  • Page 2

    2 wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 © 2011 by wago kontakttechnik gmbh & co. Kg all rights reserved. Wago kontakttechnik gmbh & co. Kg hansastraße 27 d-32423 minden phone: +49 (0) 571/8 87 – 0 fax: +49 (0) 571/8 87 – 1 69 e-ma...

  • Page 3: Table of Contents

    Wago-i/o-system 750 table of contents 3 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 5 /dokumentation allgemein/verzeichnisse/inhaltsverzeichnis - Überschrift 1 und verzeichnis @ 3\mod_1219151230875_21.Doc @ 21063 @ @ 1 table of contents 1 notes about ...

  • Page 4

    4 table of contents wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 4.2.2 fieldbus connection........................................................................... 47 4.3 display elements ..................................................

  • Page 5

    Wago-i/o-system 750 table of contents 5 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 7.3.2 addressing.......................................................................................... 87 7.3.2.1 addressing of i/o modules ...............................

  • Page 6

    6 table of contents wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 9.6.2 transfer via fieldbus and ethernet ........................................... 159 10 configuring via the web-based management system (wbm)........... 161 10.1 inform...

  • Page 7

    Wago-i/o-system 750 table of contents 7 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.2.3.1 function code fc1 (read coils) ................................................ 224 12.2.3.2 function code fc2 (read input discretes).................................

  • Page 8

    8 table of contents wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.3.5.26 analog output point extended 1 (6c hex ).................................... 292 12.3.5.27 analog output point extended 2 (70 hex ) .................................

  • Page 9

    Wago-i/o-system 750 table of contents 9 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 13.2.4.2 4 channel analog output modules ............................................. 323 13.2.5 specialty modules ...........................................................

  • Page 10

    10 table of contents wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 13.3.4.1 2 channel analog output modules ............................................. 350 13.3.4.2 4 channel analog output modules ..........................................

  • Page 11

    Wago-i/o-system 750 table of contents 11 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 16.2.2 product group .................................................................................. 388 16.2.3 versions group.............................................

  • Page 12: 1.1

    12 notes about this documentation wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 7 /dokumentation allgemein/gliederungselemente/---seitenwechsel--- @ 3\mod_1221108045078_0.Doc @ 21810 @ @ 1 8 /alle serien (allgemeine module)/Überschri...

  • Page 13: 1.3

    Wago-i/o-system 750 notes about this documentation 13 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 12.3 /alle serien (allgemeine module)/hinweise zur dokumentation/symbole @ 3\mod_1217394197593_21.Doc @ 21010 @ 2 @ 1 1.3 symbols personal injury! Indica...

  • Page 14

    14 notes about this documentation wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 additional information: refers to additional information which is not an integral part of this documentation (e.G., the internet). Pos: 12.4 /dokumentation al...

  • Page 15: 1.4

    Wago-i/o-system 750 notes about this documentation 15 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 12.5 /alle serien (allgemeine module)/hinweise zur dokumentation/zahlensysteme @ 3\mod_1221059454015_21.Doc @ 21711 @ 2 @ 1 1.4 number notation table 1: ...

  • Page 16: 2 Important

    16 important notes wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 14 /alle serien (allgemeine module)/Überschriften für alle serien/wichtige erläuterungen - Überschrift 1 @ 4\mod_1241428899156_21.Doc @ 32170 @ 1 @ 1 2 important notes ...

  • Page 17: 2.1.4

    Wago-i/o-system 750 important notes 17 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 appropriate housing (per 94/9/eg) is required when operating the wago-i/o- system 750 in hazardous environments. Please note that a prototype test certificate must be obtain...

  • Page 18: 2.2

    18 important notes wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 15.8 /alle serien (allgemeine module)/Überschriften für alle serien/sicherheitshinweise - Überschrift 2 @ 6\mod_1260180299987_21.Doc @ 46724 @ 2 @ 1 2.2 safety advice (...

  • Page 19

    Wago-i/o-system 750 important notes 19 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 do not use any contact spray! Do not use any contact spray. The spray may impair contact area functionality in connection with contamination. Pos: 15.11.5 /alle serien (allg...

  • Page 20: 3 System

    20 system description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 17.1 /serie 750 (wago-i/o-system)/systembeschreibung/gerät und system/systembeschreibung @ 3\mod_1231491805015_21.Doc @ 25850 @ 1 @ 1 3 system description pos: 17.2 ...

  • Page 21: 3.1

    Wago-i/o-system 750 system description 21 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 17.6 /serie 750 (wago-i/o-system)/systembeschreibung/gerät und system/fertigungsnummer @ 3\mod_1225444612218_21.Doc @ 24889 @ 2 @ 1 3.1 manufacturing number the manu...

  • Page 22: 3.3

    22 system description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 17.9 /serie 750 (wago-i/o-system)/systembeschreibung/gerät und system/komponenten-update @ 3\mod_1231757422359_21.Doc @ 25928 @ 2 @ 1 3.3 component update for the ca...

  • Page 23: 3.6

    Wago-i/o-system 750 system description 23 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 17.13.1 /serie 750 (wago-i/o-system)/systembeschreibung/versorgung/spannungsversorgung @ 3\mod_1232950078953_21.Doc @ 26680 @ 2 @ 1 3.6 power supply pos: 17.13.2 /se...

  • Page 24: 3.6.2

    24 system description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 17.13.6 /serie 750 (wago-i/o-system)/systembeschreibung/versorgung/systemversorgung @ 3\mod_1232950096265_21.Doc @ 26748 @ 3 @ 1 3.6.2 system supply pos: 17.13.7 /se...

  • Page 25: Note

    Wago-i/o-system 750 system description 25 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 figure 5: system voltage for standard couplers/controllers and extended eco couplers pos: 17.13.11 /serie 750 (wago-i/o-system)/systembeschreibung/versorgung/systemversor...

  • Page 26: Note

    26 system description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 17.13.14 /serie 750 (wago-i/o-system)/systembeschreibung/versorgung/beispiel: @ 3\mod_1232630417843_21.Doc @ 26605 @ @ 1 example: pos: 17.13.15 /serie 750 (wago-i/o-...

  • Page 27: Note

    Wago-i/o-system 750 system description 27 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 coupler or controller i (5 v) total = sum of all the internal current consumption of the connected bus modules + internal current consumption coupler/controller internal ...

  • Page 28: 3.6.3

    28 system description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 17.13.23 /serie 750 (wago-i/o-system)/systembeschreibung/versorgung/feldversorgung @ 3\mod_1232950080953_21.Doc @ 26688 @ 3 @ 1 3.6.3 field supply pos: 17.13.24 /ser...

  • Page 29: Note

    Wago-i/o-system 750 system description 29 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 note re-establish the ground connection when the connection to the power jumper contacts is disrupted! Some bus modules have no or very few power contacts (depending on t...

  • Page 30: Notice

    30 system description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 figure 7: supply module with fuse carrier (example 750-610) notice observe the maximum power dissipation and, if required, ul requirements! In the case of power supply mo...

  • Page 31

    Wago-i/o-system 750 system description 31 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 figure 9: opening the fuse carrier figure 10: change fuse after changing the fuse, the fuse carrier is pushed back into its original position..

  • Page 32

    32 system description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 alternatively, fusing can be done externally. The fuse modules of the wago series 281 and 282 are suitable for this purpose. Figure 11: fuse modules for automotive fuses,...

  • Page 33: 3.6.4

    Wago-i/o-system 750 system description 33 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 17.13.32 /serie 750 (wago-i/o-system)/systembeschreibung/versorgung/ergänzende einspeisungsvorschriften (standard) @ 3\mod_1232950080218_21.Doc @ 26684 @ 3 @ 1 3.6.4...

  • Page 34: 3.6.5

    34 system description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 17.13.34 /serie 750 (wago-i/o-system)/systembeschreibung/versorgung/versorgungsbeispiel - Überschrift + hinweis @ 3\mod_1232949833531_21.Doc @ 26670 @ 3 @ 1 3.6.5 su...

  • Page 35

    Wago-i/o-system 750 system description 35 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 750-630 750-400 750-410 750-401 750-613 750-512 750-512 750-616 750-513 750-610 750-552 750-600 750-612 750-616 1) a) b) c) d) 1) 2) 2) 24v 24v 10 a 10 a l1 l2 l3 n pe 23...

  • Page 36: 3.6.6

    36 system description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 17.13.38 /serie 750 (wago-i/o-system)/systembeschreibung/versorgung/netzgeräte @ 3\mod_1232950093484_21.Doc @ 26728 @ 3 @ 1 3.6.6 power supply unit the wago-i/o-syst...

  • Page 37: 3.7

    Wago-i/o-system 750 system description 37 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 17.13.40 /serie 750 (wago-i/o-system)/systembeschreibung/versorgung/erdung @ 3\mod_1231246555687_21.Doc @ 25802 @ 234433 @ 1 3.7 grounding 3.7.1 grounding the din ra...

  • Page 38: 3.7.2

    38 system description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 3.7.2 grounding function the grounding function increases the resistance against disturbances from electro- magnetic interferences. Some components in the i/o system have...

  • Page 39: 3.7.3

    Wago-i/o-system 750 system description 39 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 3.7.3 grounding protection for the field side, the ground wire is connected to the lowest connection terminals of the power supply module. The ground connection is then c...

  • Page 40: 3.8

    40 system description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 17.13.42 /serie 750 (wago-i/o-system)/systembeschreibung/versorgung/schirmung @ 3\mod_1231251994828_21.Doc @ 25813 @ 23333 @ 1 3.8 shielding (screening) 3.8.1 genera...

  • Page 41: 3.8.4

    Wago-i/o-system 750 system description 41 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 3.8.4 wago shield (screen) connecting system the wago shield connecting system includes a shield clamping saddle, a collection of rails and a variety of mounting feet. To...

  • Page 42: 4 Device

    42 device description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 19 /alle serien (allgemeine module)/Überschriften für alle serien/gerätebeschreibung - Überschrift 1 @ 3\mod_1233756084656_21.Doc @ 27096 @ 1 @ 1 4 device descriptio...

  • Page 43

    Wago-i/o-system 750 device description 43 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 wago-i/o- pro creates application programs that adhere to iec 61131-3. Codesys by 3s (the standard programming system) serves as the basis of wago-i/o- pro , which was ex...

  • Page 44

    44 device description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 memory card is not included in the scope of delivery! Note, the fieldbus controller is delivered without memory card. To use a memory card, you must order one separately....

  • Page 45: 4.1

    Wago-i/o-system 750 device description 45 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 23 /alle serien (allgemeine module)/Überschriften für alle serien/ansicht - Überschrift 2 @ 4\mod_1240984217343_21.Doc @ 31958 @ 2 @ 1 4.1 view pos: 24.1 /serie 750 ...

  • Page 46

    46 device description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 24.4 /serie 750 (wago-i/o-system)/gerätebeschreibung/ansicht/feldbuskoppler/-controller/legende/ansicht - legende zur ansicht ethernet tcp/ip-controller (750-880,881...

  • Page 47: 4.2

    Wago-i/o-system 750 device description 47 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 26 /alle serien (allgemeine module)/Überschriften für alle serien/anschlüsse - Überschrift 2 @ 4\mod_1240984262656_21.Doc @ 31961 @ 2 @ 1 4.2 connectors pos: 27 /ser...

  • Page 48

    48 device description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 29.6 /alle serien (allgemeine module)/wichtige erläuterungen/sicherheitshinweise/achtung/achtung: nicht in telekommunikationsnetzen einsetzen! (zusatz rj-45) @ 3\mod...

  • Page 49: 4.3

    Wago-i/o-system 750 device description 49 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 31 /alle serien (allgemeine module)/Überschriften für alle serien/anzeigeelemente - Überschrift 2 @ 4\mod_1240984390875_21.Doc @ 31964 @ 2 @ 1 4.3 display elements p...

  • Page 50

    50 device description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 more information about the led signaling read the detailed description for the evaluation of the displayed led-signals in the chapter "diagnostics" > "led signaling". Pos...

  • Page 51: 4.4

    Wago-i/o-system 750 device description 51 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 34 /alle serien (allgemeine module)/Überschriften für alle serien/bedienelemente - Überschrift 2 @ 4\mod_1239191655456_21.Doc @ 30439 @ 2 @ 1 4.4 operating elements ...

  • Page 52: 4.4.2

    52 device description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 37.1 /serie 750 (wago-i/o-system)/gerätebeschreibung/bedienelemente/feldbuskoppler/-controller/betriebsartenschalter - Überschrift 3, ansicht und einleitung (control...

  • Page 53: Note

    Wago-i/o-system 750 device description 53 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 note mode selector switch position is negligible in software start/stop! The position of the mode selector switch is not important when starting or stopping the pfc appli...

  • Page 54: 4.4.3

    54 device description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 39.1 /serie 750 (wago-i/o-system)/gerätebeschreibung/bedienelemente/feldbuskoppler/-controller/adresswahlschalter - Überschrift 3 @ 4\mod_1239190509819_21.Doc @ 3042...

  • Page 55

    Wago-i/o-system 750 device description 55 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 only use recommended memory cards! Use only the sd memory card available from wago (item no. 758-879/000-001) since it is suitable for industrial applications under diffi...

  • Page 56

    56 device description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 4.4.4.2 removing the memory card 1. Use an activation tool or a screwdriver to open the transparent cover flap by folding it upwards. 2. To remove the memory card, first ...

  • Page 57: 4.5

    Wago-i/o-system 750 device description 57 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 42 /alle serien (allgemeine module)/Überschriften für alle serien/technische daten - Überschrift 2 @ 3\mod_1232967587687_21.Doc @ 26924 @ 2 @ 1 4.5 technical data po...

  • Page 58: 4.5.3

    58 device description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 4.5.3 supply table 19: technical data – supply voltage supply dc 24 v (-25 % ... +30 %) input current max. 500 ma at 24 v efficiency of the power supply 90 % internal cur...

  • Page 59: 4.5.7

    Wago-i/o-system 750 device description 59 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 4.5.7 climatic environmental conditions table 23: technical data - climatic environmental conditions operating temperature range 0 °c ... 55 °c operating temperature rang...

  • Page 60: 4.5.8

    60 device description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 4.5.8 mechanical strength table 24: technical data – mechanical strength acc. To iec 60068-2-6 comment to the vibration resistance: a) type of oscillation: sweep with a r...

  • Page 61: 4.6

    Wago-i/o-system 750 device description 61 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 45 /alle serien (allgemeine module)/Überschriften für alle serien/zulassungen - Überschrift 2 @ 3\mod_1224055364109_21.Doc @ 24030 @ 2 @ 1 4.6 approvals pos: 46 /ser...

  • Page 62: 4.7

    62 device description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 53 /alle serien (allgemeine module)/Überschriften für alle serien/normen und richtlinien - Überschrift 2 @ 4\mod_1242804031875_21.Doc @ 33646 @ 2 @ 1 4.7 standards a...

  • Page 63: 5 Assembly

    Wago-i/o-system 750 assembly 63 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 60 /alle serien (allgemeine module)/Überschriften für alle serien/montieren - Überschrift 1 @ 3\mod_1225446744750_21.Doc @ 24900 @ 1 @ 1 5 assembly pos: 61.1 /serie 750 (wago-...

  • Page 64: Note

    64 assembly wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 note increase total length using a wago internal data bus extension module! Using an internal data bus extension module from wago, you can increase the total length of the fieldbus...

  • Page 65: 5.3

    Wago-i/o-system 750 assembly 65 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 61.4 /serie 750 (wago-i/o-system)/montieren/montage auf tragschiene @ 3\mod_1225447227234_21.Doc @ 24906 @ 233 @ 1 5.3 assembly onto carrier rail 5.3.1 carrier rail properties...

  • Page 66: 5.3.2

    66 assembly wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 5.3.2 wago din rail wago carrier rails meet the electrical and mechanical requirements shown in the table below. Table 25: wago din rail item number description 210-113 /-112 35 x ...

  • Page 67: 5.5

    Wago-i/o-system 750 assembly 67 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 61.7 /serie 750 (wago-i/o-system)/montieren/montagereihenfolge @ 3\mod_1231770210031_21.Doc @ 25992 @ 2 @ 1 5.5 assembly sequence all system components can be snapped directly...

  • Page 68: 5.6

    68 assembly wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 61.13 /serie 750 (wago-i/o-system)/montieren/geräte einfügen und entfernen - Überschrift 2 @ 3\mod_1231768483250_21.Doc @ 25950 @ 2 @ 1 5.6 inserting and removing devices pos:...

  • Page 69: 5.6.1

    Wago-i/o-system 750 assembly 69 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 61.17 /serie 750 (wago-i/o-system)/montieren/feldbuskoppler/-controller einfügen @ 3\mod_1234168173031_21.Doc @ 27456 @ 3 @ 1 5.6.1 inserting the fieldbus coupler/controller 1...

  • Page 70: 5.6.3

    70 assembly wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 61.21 /serie 750 (wago-i/o-system)/montieren/busklemme einfügen @ 3\mod_1231769726703_21.Doc @ 25989 @ 3 @ 1 5.6.3 inserting i/o module 1. Position the i/o module so that the ...

  • Page 71: 5.6.4

    Wago-i/o-system 750 assembly 71 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 61.23 /serie 750 (wago-i/o-system)/montieren/busklemme entfernen @ 4\mod_1239169375203_21.Doc @ 30334 @ 3 @ 1 5.6.4 removing the i/o module 1. Remove the i/o module from the a...

  • Page 72: 6 Connect

    72 connect devices wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 63 /alle serien (allgemeine module)/Überschriften für alle serien/geräte anschließen - Überschrift 1 @ 3\mod_1234172889468_21.Doc @ 27460 @ 1 @ 1 6 connect devices pos:...

  • Page 73: 6.2

    Wago-i/o-system 750 connect devices 73 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 64.6 /serie 750 (wago-i/o-system)/anschließen/leistungskontakte/feldversorgung - Überschrift 2 @ 7\mod_1266320656354_21.Doc @ 50722 @ 2 @ 1 6.2 power contacts/field sup...

  • Page 74: 6.3

    74 connect devices wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 64.11 /serie 750 (wago-i/o-system)/anschließen/leiter an cage clamp anschließen - Überschrift 2 und text @ 3\mod_1225448660171_21.Doc @ 24928 @ 2 @ 1 6.3 connecting a c...

  • Page 75: 7 Function

    Wago-i/o-system 750 function description 75 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 66 /alle serien (allgemeine module)/Überschriften für alle serien/funktionsbeschreibung - Überschrift 1 @ 4\mod_1239025975389_21.Doc @ 30003 @ 1 @ 1 7 function des...

  • Page 76

    76 function description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 var i ab l es are set to 0 or f als e or to the i r i n i t i a l va l ue , f l ags rema i n i n the same status . Sw i tch i ng on the supp l y vo l tage i n i t i a l...

  • Page 77: 7.2

    Wago-i/o-system 750 function description 77 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 71 /alle serien (allgemeine module)/Überschriften für alle serien/prozessdatenaufbau - Überschrift 2 @ 5\mod_1245069543813_21.Doc @ 35310 @ 2 @ 1 7.2 process data ...

  • Page 78

    78 function description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 hardware changes can result in changes of the process image! If the hardware configuration is changed by adding, changing or removing of i/o modules with a data width >...

  • Page 79: 7.2.2

    Wago-i/o-system 750 function description 79 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 72.15 /serie 750 (wago-i/o-system)/funktionsbeschreibung/prozessabbild/beispiel für ein eingangsprozessabbild- beispiel für ein ausgangsprozessabbild @ 6\mod_12560...

  • Page 80: 7.2.3

    80 function description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 7.2.3 example of an output data process image the following example for the output process image comprises 2 digital and 4 analog outputs. It comprises 4 words for the ...

  • Page 81: 7.2.4

    Wago-i/o-system 750 function description 81 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 72.16 /serie 750 (wago-i/o-system)/funktionsbeschreibung/prozessabbild/prozessdaten modbus/tcp und ethernet/ip - Überschrift 3 @ 6\mod_1259149638329_21.Doc @ 44990...

  • Page 82: 7.3

    82 function description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 74 /alle serien (allgemeine module)/Überschriften für alle serien/datenaustausch - Überschrift 2 @ 4\mod_1241431718548_21.Doc @ 32202 @ 2 @ 1 7.3 data exchange pos...

  • Page 83

    Wago-i/o-system 750 function description 83 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 data exchange takes place between the fieldbus master and the i/o modules, between the plc function of the pfc (cpu) and the i/o modules and between the fieldbus master...

  • Page 84: 7.3.1

    84 function description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 75.9 /serie 750 (wago-i/o-system)/funktionsbeschreibung/datenaustausch/speicherbereiche modbus/speicherbereiche modbus - bild (750-841, -881) @ 6\mod_1256046946781...

  • Page 85: Note

    Wago-i/o-system 750 function description 85 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 the subsequent memory area, starting from word 1532, is reserved for future protocol expansion and other pfc variables. Pos: 75.13 /serie 750 (wago-i/o-system)/funktion...

  • Page 86: Note

    86 function description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 figure 41: example declaration of remanent flags by „var retain“ this breakdown can be varied (see following explanation). Note novram memory allocation can be changed ...

  • Page 87: 7.3.2

    Wago-i/o-system 750 function description 87 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 75.16 /alle serien (allgemeine module)/Überschriften für alle serien/adressierung - Überschrift 3 @ 8\mod_1279016771610_21.Doc @ 59781 @ 3 @ 1 7.3.2 addressing pos...

  • Page 88: Note

    88 function description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 75.19 /serie 750 (wago-i/o-system)/funktionsbeschreibung/datenaustausch/adressierung/adressierung - adressierung der busklemmen @ 7\mod_1265981710444_21.Doc @ 5059...

  • Page 89

    Wago-i/o-system 750 function description 89 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 75.21 /serie 750 (wago-i/o-system)/funktionsbeschreibung/datenaustausch/adressierung/adressbereiche - Überschrift 4 @ 6\mod_1256048478468_21.Doc @ 43268 @ 4 @ 1 7....

  • Page 90

    90 function description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 word 512...1275: second address range for i/o module data: table 30: address range, word 512 - 1275 data width address bit 512.0 ... 512.7 512.8 ... 512.15 513.0 ... 51...

  • Page 91

    Wago-i/o-system 750 function description 91 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 75.30 /serie 750 (wago-i/o-system)/funktionsbeschreibung/datenaustausch/adressierung/adressierung - iec-adressräume im Überblick (teil 1) @ 6\mod_1256049319406_21....

  • Page 92: Note

    92 function description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 75.34 /serie 750 (wago-i/o-system)/funktionsbeschreibung/datenaustausch/adressierung/adressierung - absolute adressierung @ 6\mod_1256049674828_21.Doc @ 43304 @ 4 ...

  • Page 93

    Wago-i/o-system 750 function description 93 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 flags bit %mx11.0 ... 15 %mx12.0 ... 15 byte %mb22 %mb23 %mb24 %mb25 word %mw11 %mw12 double word %md5 (top section) %md6 (bottom section) calculating addresses (as a f...

  • Page 94: 7.3.3

    94 function description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 75.37 /serie 750 (wago-i/o-system)/funktionsbeschreibung/datenaustausch/datenaustausch - datenaustausch modbus/tcp-master und busklemmen @ 6\mod_1256049861734_21.D...

  • Page 95: Information

    Wago-i/o-system 750 function description 95 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 0x0000 0x00 ff 0x0000 (0x0 2 00 ) 00x0 ff (0x0 2ff) 0x 6 000 0x 62f c 0x 6 000 (0x 7 000 ) 0x 62f c (0x 72f c ) pii = process input image pio = process output image m o...

  • Page 96: Information

    96 function description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 75.39 /serie 750 (wago-i/o-system)/funktionsbeschreibung/datenaustausch/datenaustausch - datenaustausch ethernet/ip-master und busklemmen @ 6\mod_1256050145625_21....

  • Page 97: 7.3.4

    Wago-i/o-system 750 function description 97 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 75.41 /serie 750 (wago-i/o-system)/funktionsbeschreibung/datenaustausch/datenaustausch - datenaustausch sps-funktionalität (cpu) und busklemmen @ 6\mod_12560498968...

  • Page 98: 7.3.5

    98 function description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 75.43 /serie 750 (wago-i/o-system)/funktionsbeschreibung/datenaustausch/datenaustausch - datenaustausch master und sps-funktionalität (cpu) @ 6\mod_1256049969000_2...

  • Page 99: Information

    Wago-i/o-system 750 function description 99 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 addresses are calculated based on the following equations for byte-based access: high byte address = word address*2 low byte address = (word address*2) + 1 addresses ar...

  • Page 100: 7.3.6

    100 function description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 7.3.6 application example b i t 1 b i t 4 wor d2 wor d1 wor d2 wor d1 wor d2 wor d1 d i a i wor d2 wor d2 wor d1 hi ghb y te lowb y te 0x000 1 %ix 2 . 1 0x0000 %ix 2 ....

  • Page 101: 7.4

    Wago-i/o-system 750 function description 101 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 77 /serie 750 (wago-i/o-system)/funktionsbeschreibung/speicherkarten-funktion (750-0880) @ 9\mod_1286788410389_21.Doc @ 65490 @ 233333333 @ 1 7.4 memory card func...

  • Page 102

    102 function description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 switch on the supply for the fieldbus controller. In normal operation, the fieldbus controller starts. The data from the /copy/ directory on the memory card is copied ...

  • Page 103: 7.4.2

    Wago-i/o-system 750 function description 103 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 7.4.2 back-up function (saving device settings on the memory card) the fieldbus nodes and the sps program are in operation and the memory card is plugged in. On the "f...

  • Page 104: 7.4.3

    104 function description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 38: possible errors during the backup function possible error procedure error message solution memory card is full the copy function is cancelled. Device setting...

  • Page 105

    Wago-i/o-system 750 function description 105 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 figure 47: wbm page „features“ the backup is triggered in the web-based management and the data from the /copy/ directory on the memory card is copied into the appropr...

  • Page 106

    106 function description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 39: possible errors during the restore function possible error procedure error message solution no /copy/ and /settings/ directories on the memory card fieldbus ...

  • Page 107: 7.4.4

    Wago-i/o-system 750 function description 107 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 7.4.4 inserting a memory card during operation the fieldbus nodes and the sps program are running. Insert a memory card during ongoing operation. During normal operati...

  • Page 108: 7.4.5

    108 function description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 7.4.5 removing the memory card during operation the fieldbus nodes and the sps program are in operation and the memory card is plugged in. Remove the memory card durin...

  • Page 109: 7.4.6

    Wago-i/o-system 750 function description 109 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 7.4.6 sps access to the file system of the memory card the fieldbus nodes and the sps program are in operation and the memory card is plugged in. The sps program acces...

  • Page 110: 7.4.7

    110 function description wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 7.4.7 ftp network access to the file system of the memory card the fieldbus node is in operation and the memory card is plugged in. The ftp client accesses the file sy...

  • Page 111: 7.4.8

    Wago-i/o-system 750 function description 111 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 7.4.8 directory structure for the correct operation of the fieldbus controller, a particular directory structure is expected on the internal drive. This structure is m...

  • Page 112: 8 Commissioning

    112 commissioning wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 79 /alle serien (allgemeine module)/Überschriften für alle serien/in betrieb nehmen - Überschrift 1 @ 4\mod_1240901452750_21.Doc @ 31570 @ 1 @ 1 8 commissioning pos: 80....

  • Page 113: 8.1

    Wago-i/o-system 750 commissioning 113 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 80.8 /serie 750 (wago-i/o-system)/in betrieb nehmen/feldbusknoten in betrieb nehmen/pc und feldbusknoten anschließen (Überschrift 2) @ 4\mod_1238677467406_21.Doc @ 29815...

  • Page 114: 8.2.1

    114 commissioning wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 80.17.1 /serie 750 (wago-i/o-system)/in betrieb nehmen/feldbusknoten in betrieb nehmen/ip-adresse mit dem adresswahlschalter vergeben - Überschrift 3 @ 5\mod_12439492796...

  • Page 115: Information

    Wago-i/o-system 750 commissioning 115 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 information more information about changing the static base address you can also change the base address currently saved in the fieldbus controller as required. Proceed as de...

  • Page 116: 8.2.2

    116 commissioning wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 80.19.1 /serie 750 (wago-i/o-system)/in betrieb nehmen/feldbusknoten in betrieb nehmen/ip-adresse mit dhcp vergeben - Überschrift 3, die beschr umfasst folg arbeitsschri...

  • Page 117: Note

    Wago-i/o-system 750 commissioning 117 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 note dhcp must be enabled on the web pages (for this, address selection switch must be on 0)! Note that dhcp must be enabled on the internal web pages of the wbm, html page "...

  • Page 118: Note

    118 commissioning wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 80.19.9 /serie 750 (wago-i/o-system)/in betrieb nehmen/feldbusknoten in betrieb nehmen/dhcp über adresswahlschalter deaktivieren (controller) @ 5\mod_1244626835987_21.Do...

  • Page 119

    Wago-i/o-system 750 commissioning 119 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 80.19.11 /serie 750 (wago-i/o-system)/in betrieb nehmen/feldbusknoten in betrieb nehmen/dhcp in dem web-based management-system deaktivieren - zwischenüberschrift @ 5\mo...

  • Page 120

    120 commissioning wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 figure 50: wbm page "port" pos: 80.19.16 /serie 750 (wago-i/o-system)/in betrieb nehmen/feldbusknoten in betrieb nehmen/deaktivieren sie dhcp, indem sie die option „bootp“ od...

  • Page 121: 8.2.3

    Wago-i/o-system 750 commissioning 121 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 80.21.1 /serie 750 (wago-i/o-system)/in betrieb nehmen/feldbusknoten in betrieb nehmen/ip-adresse mit einem bootp-server vergeben (controller) @ 6\mod_1265022423859_21.D...

  • Page 122: Information

    122 commissioning wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 the following steps are included: • note mac id • note ip address • assigning the ip address and enable bootp • disable bootp pos: 80.21.8 /serie 750 (wago-i/o-system)/in bet...

  • Page 123: Note

    Wago-i/o-system 750 commissioning 123 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 80.21.16 /dokumentation allgemein/gliederungselemente/---seitenwechsel--- @ 3\mod_1221108045078_0.Doc @ 21810 @ @ 1 pos: 80.21.17 /serie 750 (wago-i/o-system)/in betrieb...

  • Page 124

    124 commissioning wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 8.2.3.3 assigning the ip address and enable bootp 1. Based on the handling, which depends on the bootp program set, assign the required ip address for your fieldbus node. 2. ...

  • Page 125

    Wago-i/o-system 750 commissioning 125 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 3. As administrator, enter the user name: " admin " and the password " wago ". A start page is then displayed in the browser window with information about your fieldbus contr...

  • Page 126

    126 commissioning wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 the controller ip can be changed in the network by the dhcp server! If bootp is not deactivated and an isdn/dsl router is installed in the network (factory default setting wi...

  • Page 127

    Wago-i/o-system 750 commissioning 127 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 since communication for each protocol takes place via different ports, you can have several protocols activated simultaneously; communication takes place via these protocols....

  • Page 128

    128 commissioning wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 80.21.37 /serie 750 (wago-i/o-system)/in betrieb nehmen/feldbusknoten in betrieb nehmen/gründe für eine fehlgeschlagene ip-adressvergabe (bei bootp) (controller) @ 4\mod...

  • Page 129: 8.3

    Wago-i/o-system 750 commissioning 129 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 80.23.1 /serie 750 (wago-i/o-system)/in betrieb nehmen/feldbusknoten in betrieb nehmen/funktion des feldbusknotens testen - Überschrift 2 @ 5\mod_1244635054676_21.Doc @ ...

  • Page 130

    130 commissioning wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 if the error message: "timeout" appears, please compare your entries again to the allocated ip address and check all connections. 6. When the test has been performed successf...

  • Page 131: 8.4

    Wago-i/o-system 750 commissioning 131 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 80.25.1 /serie 750 (wago-i/o-system)/in betrieb nehmen/feldbusknoten in betrieb nehmen/flash-dateisystem vorbereiten - Überschrift 2 @ 5\mod_1244641182202_21.Doc @ 35222...

  • Page 132: Note

    132 commissioning wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 5. In the top menu bar, select format to format the file system. Formatting is complete when the status window displays "formatting flash disk successfully done". 6. In the t...

  • Page 133: 8.5

    Wago-i/o-system 750 commissioning 133 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 80.27.1 /serie 750 (wago-i/o-system)/in betrieb nehmen/feldbusknoten in betrieb nehmen/echtzeituhr synchronisieren - Überschrift 2 @ 5\mod_1244643344108_21.Doc @ 35241 @...

  • Page 134

    134 commissioning wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 figure 54: example of real-time clock synchronization in ethernet settings 6. Click on the "synchronize" button with the clock icon. Pos: 80.27.8 /serie 750 (wago-i/o-system)...

  • Page 135

    Wago-i/o-system 750 commissioning 135 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 figure 1: example of wbm clock configuration 5. Set the values in the fields "time on device", "date" and "timezone" to the current values and enable the "daylight saving tim...

  • Page 136: 8.6

    136 commissioning wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 80.29.1 /serie 750 (wago-i/o-system)/in betrieb nehmen/feldbusknoten in betrieb nehmen/werkseinstellungen wiederherstellen - Überschrift 2 und einleitung @ 5\mod_1244645...

  • Page 137: Pro

    Wago-i/o-system 750 programming the pfc using wago-i/o-pro 137 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 82.1 /serie 750 (wago-i/o-system)/in betrieb nehmen/in wago-i/o-pro programmieren/pfc mit wago-i/o-pro programmieren - Überschrift 1, mit beschr...

  • Page 138

    138 programming the pfc using wago-i/o-pro wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 3. Select the wago 750-880 ethernet controller 10 / 100 mbit/s; digitale und analoge signale 750-880, 750-880/025-000 by entering wago_750- 880 and t...

  • Page 139: 9.1

    Wago-i/o-system 750 programming the pfc using wago-i/o-pro 139 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 82.10 /serie 750 (wago-i/o-system)/in betrieb nehmen/in wago-i/o-pro programmieren/controller mit dem i/o-konfigurator konfigurieren @ 4\mod_124...

  • Page 140: Note

    140 programming the pfc using wago-i/o-pro wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 note the terminal bus structure in the wago i/o configurator must match the physical node structure! The number of modules that send or receive data ...

  • Page 141

    Wago-i/o-system 750 programming the pfc using wago-i/o-pro 141 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 abbildung 56: write access via module parameters pos: 82.17 /serie 750 (wago-i/o-system)/in betrieb nehmen/in wago-i/o-pro programmieren/zuordnen, pr...

  • Page 142: 9.1.1

    142 programming the pfc using wago-i/o-pro wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 82.21 /serie 750 (wago-i/o-system)/in betrieb nehmen/in wago-i/o-pro programmieren/controller mit der datei ea-config.Xml konfigurieren @ 4\mod_...

  • Page 143: Note

    Wago-i/o-system 750 programming the pfc using wago-i/o-pro 143 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 fb1 “ loc=“all“> fb1 “ loc=“all“> pos: 82.25 /serie 750 (wago-i/o-system)/in betrieb nehmen/in wago-i/o-pro programmieren/mit der datei ea-config.Xml...

  • Page 144: 9.2

    144 programming the pfc using wago-i/o-pro wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 82.27 /serie 750 (wago-i/o-system)/in betrieb nehmen/in wago-i/o-pro programmieren/ethernet-bibliotheken für wago-i/o-pro @ 4\mod_1240922020812_...

  • Page 145: Information

    Wago-i/o-system 750 programming the pfc using wago-i/o-pro 145 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 information additional information for a detailed description of the function blocks and use of the software, refer to the online help function for w...

  • Page 146: 9.3

    146 programming the pfc using wago-i/o-pro wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 82.31 /serie 750 (wago-i/o-system)/in betrieb nehmen/in wago-i/o-pro programmieren/einschränkungen im funktionsumfang @ 4\mod_1240813319046_21.D...

  • Page 147

    Wago-i/o-system 750 programming the pfc using wago-i/o-pro 147 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 codesys tasks with the command "tsk". If in a plc program, operating system functions are used; e.G., for the handling of "sockets" or the "file syst...

  • Page 148: Note

    148 programming the pfc using wago-i/o-pro wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 note note the maximum number of write cycles of the eeprom! Fieldbus couplers/controllers save some information such as ip addresses and ip parameter...

  • Page 149: 9.4

    Wago-i/o-system 750 programming the pfc using wago-i/o-pro 149 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 82.48 /serie 750 (wago-i/o-system)/in betrieb nehmen/in wago-i/o-pro programmieren/generelle hinweise zu den iec-tasks @ 4\mod_1240925127250_21....

  • Page 150: Note

    150 programming the pfc using wago-i/o-pro wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 the following applies to cyclic tasks with watchdog activated: note reference for watchdog settings! For each tasks created, a watchdog can be enable...

  • Page 151: Note

    Wago-i/o-system 750 programming the pfc using wago-i/o-pro 151 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 82.52 /serie 750 (wago-i/o-system)/in betrieb nehmen/in wago-i/o-pro programmieren/generelle hinweise zu den iec-tasks - keine zyklischen tasks ...

  • Page 152

    152 programming the pfc using wago-i/o-pro wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 plc-comm task (internal) the plc-comm task is active when logged in and takes up communication with the codesys gateway. Background task (iec-task pr...

  • Page 153: 9.5

    Wago-i/o-system 750 programming the pfc using wago-i/o-pro 153 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 82.60 /serie 750 (wago-i/o-system)/in betrieb nehmen/in wago-i/o-pro programmieren/systemereignisse @ 4\mod_1241096393312_21.Doc @ 32133 @ 23 @ ...

  • Page 154: Information

    154 programming the pfc using wago-i/o-pro wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 information additional information: allocation of the system events to the specific modules to be called up is clarified in the manual for the progra...

  • Page 155: 9.6

    Wago-i/o-system 750 programming the pfc using wago-i/o-pro 155 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 82.62 /serie 750 (wago-i/o-system)/in betrieb nehmen/in wago-i/o-pro programmieren/iec-programm auf den controller übertragen @ 4\mod_1241097223...

  • Page 156: 9.6.1

    156 programming the pfc using wago-i/o-pro wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 82.66 /serie 750 (wago-i/o-system)/in betrieb nehmen/in wago-i/o-pro programmieren/applikation mittels serieller schnittstelle übertragen (einle...

  • Page 157

    Wago-i/o-system 750 programming the pfc using wago-i/o-pro 157 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 figure 61: dialog window "communication parameters" 6. In the selection window, mark the required driver in the right side of the window, serial (rs-...

  • Page 158

    158 programming the pfc using wago-i/o-pro wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12. Once the program has been loaded, start program processing in the menu online , menu item start . This command starts the processing of your prog...

  • Page 159: 9.6.2

    Wago-i/o-system 750 programming the pfc using wago-i/o-pro 159 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 82.71 /serie 750 (wago-i/o-system)/in betrieb nehmen/in wago-i/o-pro programmieren/applikation via ethernet übertragen (881, 880) @ 8\mod_127894...

  • Page 160

    160 programming the pfc using wago-i/o-pro wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 depending on whether a program is already present in the controller, a window will appear asking whether a (new) program should be loaded. 8. Respond...

  • Page 161: System (Wbm)

    Wago-i/o-system 750 configuring via the web-based management system (wbm) 161 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 84.1 /serie 750 (wago-i/o-system)/web-based management-system/im web-based management-system konfigurieren (einleitung) @ 4\mod_1...

  • Page 162

    162 configuring via the web-based management system (wbm) wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 figure 62: wbm page "information" pos: 84.4 /serie 750 (wago-i/o-system)/web-based management-system/seite information/information - t...

  • Page 163: 10.2

    Wago-i/o-system 750 configuring via the web-based management system (wbm) 163 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 dns server 1 0.0.0.0 0.0.0.0 address of first dns server dns server 2 0.0.0.0 0.0.0.0 address of second dns server module status entry...

  • Page 164

    164 configuring via the web-based management system (wbm) wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 abbildung 63: wbm-seite „ethernet“ pos: 84.9 /serie 750 (wago-i/o-system)/web-based management-system/seite ethernet/ethernet - tabell...

  • Page 165: Note

    Wago-i/o-system 750 configuring via the web-based management system (wbm) 165 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 10 mbit half duplex 10 mbit full duplex 100 mbit half duplex 100 mbit full duplex select half or full duplex for the ethernet to confi...

  • Page 166: 10.3

    166 configuring via the web-based management system (wbm) wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 84.14 /serie 750 (wago-i/o-system)/web-based management-system/seite tcp/ip/tcp/ip - einleitung @ 4\mod_1242383515859_21.Doc @ 33...

  • Page 167: 10.4

    Wago-i/o-system 750 configuring via the web-based management system (wbm) 167 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 (s)ntp server 0.0.0.0 0.0.0.0 enter ip address of the (s)ntp server sntp update time (sec. Max. 65535) 0 0 enter the delay after which...

  • Page 168: 10.5

    168 configuring via the web-based management system (wbm) wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 activating "hypertext transfer protocol" http (port 80) enabled deactivating "hypertext transfer protocol" activating "simple network ...

  • Page 169: Note

    Wago-i/o-system 750 configuring via the web-based management system (wbm) 169 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 snmp is processed via port 161. The port number for snmp traps (agent messages) is 162. Note enable port 161 and 162 to use snmp! Enab...

  • Page 170

    170 configuring via the web-based management system (wbm) wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 figure 66: wbm page "snmp" pos: 84.27.10 /serie 750 (wago-i/o-system)/web-based management-system/seite snmp/snmp - tabelle snmp confi...

  • Page 171: 10.5.2  Snmp V3

    Wago-i/o-system 750 configuring via the web-based management system (wbm) 171 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 local community name public used community name snmp v1/v2 trap receiver configuration entry value (default) description trap receiver...

  • Page 172

    172 configuring via the web-based management system (wbm) wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 figure 67: wbm page "snmp v3" pos: 84.27.15 /serie 750 (wago-i/o-system)/web-based management-system/seite snmp/snmp - tabelle snmp v3...

  • Page 173: 10.6

    Wago-i/o-system 750 configuring via the web-based management system (wbm) 173 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 privacy key privacy key enter the password of at least 8 characters in the encryption with des activate the notification traps of the ...

  • Page 174: 10.7

    174 configuring via the web-based management system (wbm) wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 51: wbm page "watchdog" connection watchdog entry default description connection timeout value (100 ms) 600 monitoring period fo...

  • Page 175: Note

    Wago-i/o-system 750 configuring via the web-based management system (wbm) 175 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 error message in wago i/o check is possible after a power failure! If you are using the software "wago-i/o- check " after a loss of po...

  • Page 176

    176 configuring via the web-based management system (wbm) wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 84.39 /serie 750 (wago-i/o-system)/web-based management-system/seite clock/clock - tabelle @ 4\mod_1242630354890_21.Doc @ 33433 @...

  • Page 177: 10.8

    Wago-i/o-system 750 configuring via the web-based management system (wbm) 177 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 84.41 /serie 750 (wago-i/o-system)/web-based management-system/seite security/security - einleitung @ 4\mod_1242630881437_21.Doc ...

  • Page 178

    178 configuring via the web-based management system (wbm) wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 figure 70: wbm page "security" pos: 84.43 /serie 750 (wago-i/o-system)/web-based management-system/seite security/security - tabelle @...

  • Page 179: 10.9

    Wago-i/o-system 750 configuring via the web-based management system (wbm) 179 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 84.44 /serie 750 (wago-i/o-system)/web-based management-system/seite security/hinweis: nach software-reset zugriff erneuern! @ 6\...

  • Page 180: Note

    180 configuring via the web-based management system (wbm) wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 note return to wbm view via the ip address of the fieldbus controller! The "webvisu.Htm" page does not have any hyperlinks to the othe...

  • Page 181

    Wago-i/o-system 750 configuring via the web-based management system (wbm) 181 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table: wbm page "plc" plc features function default description activate, if the write authorizations must be assigned to the outputs ...

  • Page 182: 10.10  Features

    182 configuring via the web-based management system (wbm) wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 10.10 features use the "features" html page to enable or disable additional functions. Pos: 84.49 /serie 750 (wago-i/o-system)/web-bas...

  • Page 183: 10.11  I/o Config

    Wago-i/o-system 750 configuring via the web-based management system (wbm) 183 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 synchronize device settings from removable disk at start-up active synchronize device settings from removable disk at start-up synchro...

  • Page 184: Information

    184 configuring via the web-based management system (wbm) wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 information additional information for more detailed information about the wago-i/o- pro i/o configurator, refer to the section "start...

  • Page 185: 10.12  Disk Info

    Wago-i/o-system 750 configuring via the web-based management system (wbm) 185 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 84.59 /serie 750 (wago-i/o-system)/web-based management-system/seite disk info/disk info - einleitung (750-880, -882) @ 9\mod_128...

  • Page 186: 10.13  Webvisu

    186 configuring via the web-based management system (wbm) wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 84.63 /serie 750 (wago-i/o-system)/web-based management-system/seite webvisu/webvisu - einleitung 1 (750-841) @ 6\mod_12602718453...

  • Page 187

    Wago-i/o-system 750 configuring via the web-based management system (wbm) 187 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 configured application in a frame in the wbm window directly. The links to switch to the other wbm pages are still available with this...

  • Page 188: 11 Diagnostics

    188 diagnostics wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 86 /alle serien (allgemeine module)/Überschriften für alle serien/diagnose - Überschrift 1 @ 4\mod_1240831069471_21.Doc @ 31372 @ 1 @ 1 11 diagnostics pos: 87 /alle serien...

  • Page 189

    Wago-i/o-system 750 diagnostics 189 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 59: fieldbus diagnostics – solution in event of error led status meaning solution link act 1, 2 green the fieldbus node is connected to the physical network. - green flas...

  • Page 190

    190 diagnostics wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 88.10 /serie 750 (wago-i/o-system)/diagnose/feldbuskoppler/-controller/knotenstatus auswerten - i/o-led (alle koppler/controller) @ 6\mod_1259229729546_21.Doc @ 45457 @ 3 ...

  • Page 191

    Wago-i/o-system 750 diagnostics 191 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 ‘i /o ’ l e d i s b li n ki ng (red) test o .K.? N o y es ‘i /o ’- l e d i s sh i n i ng (green) read y for operat i on 2nd brea k 1st brea k ‘i /o ’ l e d 1st f l ash se q uen...

  • Page 192

    192 diagnostics wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 61: blink code- table for the i/o led signaling, error code 1 error code 1: "hardware and configuration error" error argument error description solution 1 overflow of the...

  • Page 193

    Wago-i/o-system 750 diagnostics 193 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 61: blink code- table for the i/o led signaling, error code 1 error code 1: "hardware and configuration error" error argument error description solution 8 timeout during ...

  • Page 194

    194 diagnostics wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 63: blink code table for the i/o led signaling, error code 3 error code 3: "protocol error, internal bus" error argument error description solution - internal data bus co...

  • Page 195

    Wago-i/o-system 750 diagnostics 195 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 64: blink code table for the i/o led signaling, error code 4 error code 4: "physical error, internal bus" error argument error description solution - internal bus data tr...

  • Page 196

    196 diagnostics wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 66: blink code- table for the i/o led signaling, error code 6 error code 6: "fieldbus specific errors" error argument error description solution 1 invalid macid 1. Turn o...

  • Page 197

    Wago-i/o-system 750 diagnostics 197 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 68: blink code table for the 'i/o' led signaling, error code 10 error code 10: "plc program fault" error argument error description solution 1 error when implementing the...

  • Page 198

    198 diagnostics wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 70: blink code table for the i/o led signaling, error code 14 error code 14: "error in external storage (memory card)" error argument error description solution 1 memory ...

  • Page 199

    Wago-i/o-system 750 diagnostics 199 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 11.1.2.1 usr led the bottom indicator led ("usr") is provided for visual output of information. Control of the led from the application program is conducted using the functions...

  • Page 200: 11.2

    200 diagnostics wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 88.23 /serie 750 (wago-i/o-system)/diagnose/feldbuskoppler/-controller/fehlerverhalten, feldbusausfall (750-830, -841, -849, -352,...) @ 6\mod_1259570148859_21.Doc @ 46112...

  • Page 201: Information

    Wago-i/o-system 750 diagnostics 201 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 information loss of fieldbus detection through modbus protocol: for detailed information about the watchdog register, refer to section "modbus functions", in particular section...

  • Page 202

    202 diagnostics wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 88.25 /serie 750 (wago-i/o-system)/diagnose/feldbuskoppler/-controller/klemmenbusfehler (alle controller) @ 6\mod_1259322394765_21.Doc @ 45998 @ 3 @ 1 11.2.2 internal data...

  • Page 203: 12 Fieldbus

    Wago-i/o-system 750 fieldbus communication 203 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 90 /alle serien (allgemeine module)/Überschriften für alle serien/feldbuskommunikation - Überschrift 1 @ 4\mod_1241433862621_21.Doc @ 32212 @ 1 @ 1 12 fieldbus ...

  • Page 204: Note

    204 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 ip addresses to allow communication over the network each fieldbus node requires a 32 bit internet address (ip address). Note ip address must be unique! For error fr...

  • Page 205: Note

    Wago-i/o-system 750 fieldbus communication 205 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 therefore, the address range of class c networks in the first byte is always between 192 and 223. • additional network classes (d, e): are only used for special task...

  • Page 206

    206 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 dependent upon the number of subnets to be addressed and the number of subscribers per subnet. Table 77: class b address with field for subnet ids 1 8 16 24 32 1 0 ....

  • Page 207: Note

    Wago-i/o-system 750 fieldbus communication 207 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 note specification of the network mask necessarily! Specify the network mask defined by the administrator in the same way as the ip address when installing the netwo...

  • Page 208

    208 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.1.1.2 tcp (transmission control protocol) as the layer above the internet protocol, tcp (transmission control protocol) guarantees the secure transport of data th...

  • Page 209: Note

    Wago-i/o-system 750 fieldbus communication 209 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.1.2 configuration and diagnostics protocols pos: 96 /alle serien (allgemeine module)/feldbuskommunikation/ethernet/bootp - beschreibungsanfang (boots trap protoko...

  • Page 210: Note

    210 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 82: bootp options option meaning [opt1] subnet mask 32-bit address mask that displays which bits of the ip address identify the network and which identify the ...

  • Page 211: Note

    Wago-i/o-system 750 fieldbus communication 211 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.1.2.2 dhcp (dynamic host configuration protocol) the fieldbus coupler/controller internal html page opened via the "port" link provides the option to configure th...

  • Page 212

    212 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 because of this time dependency, dhcp is also used to dynamically assign available ip addresses through client leases (lease time after which the client requests a n...

  • Page 213

    Wago-i/o-system 750 fieldbus communication 213 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 83: meaning of dhcp options option meaning [opt1] subnet mask 32-bit address mask that displays which bits of the ip address identify the network and which ide...

  • Page 214: Note

    214 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 the addresses of the dns server are configured via dhcp, bootp or web-based management. Up to 2 dns servers can be specified. The host identification can be achieved...

  • Page 215: Information

    Wago-i/o-system 750 fieldbus communication 215 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 information more information about the implemented protocols you can find a list of the exact available implemented protocols in the chapter "technical data" to the ...

  • Page 216: Information

    216 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.1.2.7.1 mib ii description pos: 105.4 /alle serien (allgemeine module)/feldbuskommunikation/snmp (mib)/snmp (simple network management protokoll) - beschreibung d...

  • Page 217: Note

    Wago-i/o-system 750 fieldbus communication 217 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 105.6 /alle serien (allgemeine module)/feldbuskommunikation/snmp (mib)/snmp (simple network management protokoll) - standard-traps (Überschrift 5) @ 7\mod_12707...

  • Page 218

    218 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 107 /alle serien (allgemeine module)/feldbuskommunikation/ethernet/anwendungsprotokolle - Überschrift 3 und einleitungstext @ 4\mod_1237212360010_21.Doc @ 28535...

  • Page 219: 12.2

    Wago-i/o-system 750 fieldbus communication 219 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 109.1 /alle serien (allgemeine module)/feldbuskommunikation/modbus/modbus-funktionen - allgemeines @ 3\mod_1234513607390_21.Doc @ 27530 @ 23 @ 1 12.2 modbus fun...

  • Page 220: Information

    220 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 information more information more information on the “open modbus/tcp specification” you can find in the internet: www.Modbus.Org . Therefore the modbus protocol bas...

  • Page 221: Note

    Wago-i/o-system 750 fieldbus communication 221 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 109.6 /alle serien (allgemeine module)/feldbuskommunikation/modbus/modbus-funktionen - eingabe adresse und funktionscode, hinweis @ 3\mod_1234955801125_21.Doc @...

  • Page 222

    222 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 109.8 /alle serien (allgemeine module)/feldbuskommunikation/modbus/anwendung der modbus-funktionen - einleitung @ 7\mod_1265623985585_21.Doc @ 49940 @ 33 @ 1 12...

  • Page 223: Note

    Wago-i/o-system 750 fieldbus communication 223 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 note use register functions to access analog signals and coil functions to access binary signals! It is recommended that analog data be accessed with register functi...

  • Page 224

    224 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.2.3.1 function code fc1 (read coils) this function reads the status of the input and output bits (coils) in a slave device. Request the request specifies the refe...

  • Page 225

    Wago-i/o-system 750 fieldbus communication 225 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 exception table 94: exception of function code fc1 byte field name example ... Byte 7 modbus function code 0x81 byte 8 exception code 0x01 or 0x02.

  • Page 226

    226 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.2.3.2 function code fc2 (read input discretes) this function reads the input bits from a slave device. Request the request specifies the reference number (startin...

  • Page 227

    Wago-i/o-system 750 fieldbus communication 227 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 exception table 98: exception of function code fc2 byte field name example ... Byte 7 modbus function code 0x82 byte 8 exception code 0x01 or 0x02.

  • Page 228

    228 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.2.3.3 function code fc3 (read multiple registers) this function reads the contents of holding registers from a slave device in word format. Request the request sp...

  • Page 229

    Wago-i/o-system 750 fieldbus communication 229 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.2.3.4 function code fc4 (read input registers) this function reads contents of input registers from the slave device in word format. Request the request specifies...

  • Page 230

    230 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.2.3.5 function code fc5 (write coil) this function writes a single output bit to the slave device. Request the request specifies the reference number (output addr...

  • Page 231

    Wago-i/o-system 750 fieldbus communication 231 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.2.3.6 function code fc6 (write single register) this function writes the value of one single output register to a slave device in word format. Request the request...

  • Page 232

    232 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 109.12 /alle serien (allgemeine module)/feldbuskommunikation/modbus/anwendung der modbus-funktionen - fc11, fc15, fc16 @ 4\mod_1235567470328_21.Doc @ 27730 @ 44...

  • Page 233

    Wago-i/o-system 750 fieldbus communication 233 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.2.3.8 function code fc15 (force multiple coils) this function sets a sequence of output bits to 1 or 0 in a slave device. The maximum number is 256 bits. Request ...

  • Page 234

    234 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 exception table 116: exception of function code fc15 byte field name example ... Byte 7 modbus function code 0x8f byte 8 exception code 0x01 or 0x02.

  • Page 235

    Wago-i/o-system 750 fieldbus communication 235 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.2.3.9 function code fc16 (write multiple registers) this function writes a sequence of registers in a slave device in word format. Request the request specifies t...

  • Page 236

    236 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 109.14 /alle serien (allgemeine module)/feldbuskommunikation/modbus/anwendung der modbus-funktionen (x41) - fc22 @ 4\mod_1235567699484_21.Doc @ 27737 @ 4 @ 1 12...

  • Page 237

    Wago-i/o-system 750 fieldbus communication 237 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 109.16 /alle serien (allgemeine module)/feldbuskommunikation/modbus/anwendung der modbus-funktionen - fc23 @ 4\mod_1235567802937_21.Doc @ 27740 @ 4 @ 1 12.2.3.1...

  • Page 238: Note

    238 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 note note that if the register ranges overlap, the results are undefined! If register areas for read and write overlap, the results are undefined. Pos: 109.17 /dokum...

  • Page 239

    Wago-i/o-system 750 fieldbus communication 239 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 109.18 /alle serien (allgemeine module)/feldbuskommunikation/modbus/modbus-register-mapping - einleitung (controller) @ 3\mod_1235386256031_21.Doc @ 27560 @ 3 @...

  • Page 240

    240 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 register access writing (with fc6, fc16, fc22 and fc23) table 127: register access writing (with fc6, fc16, fc22 and fc23) modbus address iec 61131 [dec] [hex] addre...

  • Page 241

    Wago-i/o-system 750 fieldbus communication 241 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 bit access reading (with fc1 and fc2) table 128: bit access reading (with fc1 and fc2) modbus address memory range [dec] [hex] description 0...511 0x0000...0x01ff ph...

  • Page 242: 12.2.5  Modbus Registers

    242 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 109.25 /alle serien (allgemeine module)/feldbuskommunikation/modbus/modbus-register (x41) - teil 1.0 (0x1000 bis 0x102a) @ 3\mod_1235399979343_21.Doc @ 27603 @ ...

  • Page 243

    Wago-i/o-system 750 fieldbus communication 243 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 109.31 /alle serien (allgemeine module)/feldbuskommunikation/modbus/zugriff auf registerwerte - watchdog-register bis tabelle @ 3\mod_1235460353828_21.Doc @ 276...

  • Page 244

    244 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 reading the minimum trigger time (register 0x1004) reveals whether a watchdog fault occurred. If this time value is 0, a fieldbus failure is assumed. The timer of wa...

  • Page 245

    Wago-i/o-system 750 fieldbus communication 245 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 134: register address 0x1002 register address 0x1002 (4098 dec ) value watchdog function coding mask, function code 17...32, wd_fcm_17_32 access read/write def...

  • Page 246

    246 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 139: register address 0x1007 register address 0x1007 (4103 dez ) value restart watchdog, wd_restart access read/write standard 0x0001 description this register...

  • Page 247

    Wago-i/o-system 750 fieldbus communication 247 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 setting the watchdog for a timeout of more than 1 second: 1. Write 0x000a in the register for time overrun (0x1000). Register 0x1000 works with a multiple of 100 ms;...

  • Page 248

    248 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 109.37 /alle serien (allgemeine module)/feldbuskommunikation/modbus/zugriff auf registerwerte - diagnoseregister 0x1020, 0x1021 @ 3\mod_1235461657984_21.Doc @ 2...

  • Page 249

    Wago-i/o-system 750 fieldbus communication 249 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 109.39 /alle serien (allgemeine module)/feldbuskommunikation/modbus/zugriff auf registerwerte - konfigurationsregister 0x1022 bis 0x1025 @ 3\mod_1235461775390_2...

  • Page 250

    250 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 152: register address 0x1029 register address 0x1029 (4137 dec ) with 9 words value modbus tcp statistics access read/write description 1 word slavedevicefailu...

  • Page 251

    Wago-i/o-system 750 fieldbus communication 251 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 109.45 /alle serien (allgemeine module)/feldbuskommunikation/modbus/zugriff auf registerwerte - konfigurationsregister 0x1035, 0x1036 (881) @ 8\mod_128022569834...

  • Page 252

    252 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 158: register address 0x2030 register address 0x2030 (8240 dec ) with a word count of up to 65 value description of the connected i/o modules access read modul...

  • Page 253

    Wago-i/o-system 750 fieldbus communication 253 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 161: register address 0x2033 register address 0x2033 (8243 dec ) with a word count of up to 65 value description of the connected i/o modules access read modul...

  • Page 254

    254 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 109.53 /alle serien (allgemeine module)/feldbuskommunikation/modbus/zugriff auf registerwerte - firmware-informationsregister 0x2010 bis 0x2014 @ 3\mod_12354619...

  • Page 255

    Wago-i/o-system 750 fieldbus communication 255 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 172: register address 0x2021 register address 0x2021 (8225 dec ) with a word count of up to 8 value description, info_description access read description time ...

  • Page 256

    256 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 109.56 /alle serien (allgemeine module)/feldbuskommunikation/modbus/zugriff auf registerwerte - konstantenregister 0x2000 bis 0x2008 @ 3\mod_1235462025437_21.Do...

  • Page 257

    Wago-i/o-system 750 fieldbus communication 257 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 181: register address 0x2006 register address 0x2006 (8198 dec ) value maximum negative number, gp_max_neg access read description constant in order to control...

  • Page 258: 12.3

    258 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 111.1 /alle serien (allgemeine module)/feldbuskommunikation/ethernetip/ethernetip - allgemein @ 3\mod_1233669829343_21.Doc @ 27044 @ 23333344 @ 1 12.3 ethernet/...

  • Page 259

    Wago-i/o-system 750 fieldbus communication 259 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.3.2 protocol overview in the osi model in order to clarify the interrelationships between devicenet, controlnet and ethernet/ip, the following diagram presents th...

  • Page 260: 12.3.4  Eds File

    260 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.3.3 characteristics of the ethernet/ip protocol software the ethernet/ip product classes are divided into 4 levels with each level containing a particular functio...

  • Page 261: 12.3.5  Object Model

    Wago-i/o-system 750 fieldbus communication 261 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.3.5 object model 12.3.5.1 general for network communication, ethernet/ip utilizes an object model in which all functions and data of a device are described. Each ...

  • Page 262

    262 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.3.5.2 class overview cip classes are included in the cip specification of odva. They describe the properties (volume 1, "common industrial protocol") of ethernet ...

  • Page 263

    Wago-i/o-system 750 fieldbus communication 263 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 111.2 /alle serien (allgemeine module)/feldbuskommunikation/ethernetip/allgemein - variables (nur controller) @ 3\mod_1233728715593_21.Doc @ 27050 @ @ 1 pos: 11...

  • Page 264: Note

    264 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.3.5.3 explanation of the table headings in the object descriptions table 188: explanation of the table headings in the object descriptions table heading descripti...

  • Page 265

    Wago-i/o-system 750 fieldbus communication 265 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 instance 1 table 190: identity (01 hex ) – instance 1 attribute id access name data type description default value 1 get vendor id uint manufacturer identification 4...

  • Page 266: Note

    266 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.3.5.5 message router (02 hex ) the "message router object" provides connection points (in the form of classes or instances), which can use a client for addressing...

  • Page 267

    Wago-i/o-system 750 fieldbus communication 267 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 common services table 194: message router (02 hex ) – common service service available service code class instance service-name description 01 hex yes no get_attribu...

  • Page 268

    268 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 197: static assembly instances – instance 101 (65 hex ) attribute id access name data type description default value 3 get/set data array of byte only analog a...

  • Page 269

    Wago-i/o-system 750 fieldbus communication 269 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 instance 105 (69 hex ) this assembly instance contains only digital input data, status (= value from class 100, instance 1, attribute 5) and fieldbus output variable...

  • Page 270

    270 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 instance 108 (6c hex ) this assembly instance contains only digital input data and fieldbus output variables. Table 204: static assembly instances – instance 108 (6c...

  • Page 271

    Wago-i/o-system 750 fieldbus communication 271 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 instance 198 (c6 hex ) “input only” this instance is used to establish a connection when no outputs are to be addressed or when inputs, which are already being used ...

  • Page 272

    272 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 for each connection (input and output data or explicit), another instance of the connection class is created. The connection parameters are extracted from the "forwa...

  • Page 273

    Wago-i/o-system 750 fieldbus communication 273 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 common services table 211: port class (f4 hex ) – common service service available service code class instance service-name description 01 hex yes yes get_attribute_...

  • Page 274

    274 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.3.5.10 tcp/ip interface (f5 hex ) the "tcp/ip interface object" provides for the configuration of the tcp/ip network interface of a fieldbus coupler/controller. E...

  • Page 275

    Wago-i/o-system 750 fieldbus communication 275 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 instance 1 table 213: tcp/ip interface (f5 hex ) – instance 1 attribute id access nv name data type description default value 1 get v status dword interface state - ...

  • Page 276

    276 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 instance 0 (class attributes) table 215: ethernet link (f5 hex ) – class attribute id access name data type description default value 1 get revision uint revision of...

  • Page 277

    Wago-i/o-system 750 fieldbus communication 277 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 instance 1 table 216: ethernet link (f6 hex ) – instance 1 attribute id access name data type description default value 1 get interface speed udint transfer rate 10 ...

  • Page 278

    278 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 216: ethernet link (f6 hex ) – instance 1 attribute id access name data type description default value 9 get/ set admin status usint admin status: value 0: res...

  • Page 279

    Wago-i/o-system 750 fieldbus communication 279 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 instance 2 – port 2 table 217: ethernet link (f6 hex ) – instance 2 attribute id access name data type description default value 1 get interface speed udint transfer...

  • Page 280

    280 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 217: ethernet link (f6 hex ) – instance 2 attribute id access name data type description default value 9 get/ set admin status usint admin status: value 0: res...

  • Page 281: Note

    Wago-i/o-system 750 fieldbus communication 281 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 instance 3 – internal port 3 table 218: ethernet link (f6 hex ) – instance 3 attribute id access name data type description default value 1 get interface speed udint...

  • Page 282

    282 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.3.5.12 coupler/controller configuration (64 hex ) the fieldbus coupler configuration class allows reading and configuration of some important fieldbus/controller ...

  • Page 283

    Wago-i/o-system 750 fieldbus communication 283 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 attribute id access nv name data type description default value 47 (0x2f) get v bk_diag_value uint contains the diagnostic byte note: this attribute has to be read o...

  • Page 284

    284 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 120 (0x78) set nv bk_header cfgot uint indicates whether the run/idle header is used originator target direction 0: is used 1: is not used 0x0000 121(0x79) set nv bk...

  • Page 285

    Wago-i/o-system 750 fieldbus communication 285 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 scope of the "discrete input point extended 1" class covers dips from 256 to 510 in the fieldbus node. Instance 0 (class attributes) table 226: discrete input point ...

  • Page 286

    286 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 common services table 231: analog input point (67 hex ) – common service service available service code class instance service name description 0e hex yes yes get_at...

  • Page 287

    Wago-i/o-system 750 fieldbus communication 287 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 instance 1 ... 255 (digital output value 1 up to 255) table 236: discrete output point (66 hex ) – instance 1...255 attribute id access name data type description de...

  • Page 288

    288 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.3.5.19 discrete output point extended 2 (6e hex ) the extension of the "discrete output point" class enables the exchange of data from a fieldbus node that contai...

  • Page 289

    Wago-i/o-system 750 fieldbus communication 289 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 instance 766 ... 1020 (digital output value 766 up to 1020) table 245: discrete output point extended 3 (72 hex ) – instance 766...1020 attribute id access name data...

  • Page 290

    290 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.3.5.22 analog input point extended 1 (6b hex ) the extension of the "analog input point" class enables the reading of data from a fieldbus node that contains over...

  • Page 291

    Wago-i/o-system 750 fieldbus communication 291 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 254: analog input point extended 2 (6f hex ) – instance 511 ... 765 attribute id access name data type description default value 1 get aipobj_value array of by...

  • Page 292

    292 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.3.5.25 analog output point (68 hex ) this class enables the reading of data of a particular analog output point (aop). An analog output point is part of an analog...

  • Page 293

    Wago-i/o-system 750 fieldbus communication 293 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 instance 256 ... 510 (analog output value 256 up to 510) table 263: analog output point extended 1 (6c hex ) – instance 256...510 attribute id access name data type ...

  • Page 294

    294 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 common services table 267: analog output point extended 2 (70 hex ) – common service service available service code class instance service name description 0e hex ye...

  • Page 295

    Wago-i/o-system 750 fieldbus communication 295 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.3.5.29 module configuration (80 hex ) instance 0 (class attributes) table 271: module configuration (80 hex ) – class attribute id access name data type descripti...

  • Page 296

    296 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 instance 256 (clamp 255) table 275: module configuration extended (81 hex ) – instance 256 attribute id access name data type description default value 1 get modulde...

  • Page 297

    Wago-i/o-system 750 fieldbus communication 297 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 111.16 /alle serien (allgemeine module)/feldbuskommunikation/ethernetip/input output fieldbus variable (extended) usint, uint, udint, a0 hex bis ad hex (nur con...

  • Page 298

    298 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.3.5.32 input fieldbus variable usint extended 1 (a1 hex ) the extension of the "input fieldbus variable usint" class enables the reading of plc input variable dat...

  • Page 299

    Wago-i/o-system 750 fieldbus communication 299 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.3.5.33 input fieldbus variable usint extended 2 (a2 hex ) the extension of the "input fieldbus variable usint" class enables the reading of plc input variable dat...

  • Page 300

    300 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.3.5.34 output fieldbus variable usint (a3 hex ) the class enables the exchange of data from a particular plc output variable. For wago-i/o-pro or codesys, that me...

  • Page 301

    Wago-i/o-system 750 fieldbus communication 301 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.3.5.35 output fieldbus variable usint extended 1 (a4 hex ) the extension of the "output fieldbus variable usint" class enables the exchange of plc output variable...

  • Page 302

    302 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.3.5.36 output fieldbus variable usint extended 2 (a5 hex ) the extension of the "output fieldbus variable usint" class enables the exchange of plc output variable...

  • Page 303

    Wago-i/o-system 750 fieldbus communication 303 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.3.5.37 input fieldbus variable uint (a6 hex ) this class allows the reading of data from a particular plc input variable. For wago-i/o- pro or codesys, that means...

  • Page 304

    304 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.3.5.38 input fieldbus variable uint extended 1 (a7 hex ) the extension of the "input fieldbus variable uint" class enables the reading of plc input variable data....

  • Page 305

    Wago-i/o-system 750 fieldbus communication 305 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.3.5.39 output fieldbus variable uint (a8 hex ) the class enables the exchange of data from a particular plc output variable. For wago-i/o- pro or codesys, that me...

  • Page 306

    306 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.3.5.40 output fieldbus variable uint extended 1 (a9 hex ) the extension of the "output fieldbus variable uint" class enables the exchange of plc output variable d...

  • Page 307

    Wago-i/o-system 750 fieldbus communication 307 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.3.5.41 input fieldbus variable udint (aa hex ) this class allows the reading of data from a particular plc input variable. For wago-i/o- pro or codesys, that mean...

  • Page 308: Information

    308 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.3.5.42 input fieldbus variable udint offset (ab hex ) this class allows the reading of data from a particular plc input variable. With an offset of 2 bytes to the...

  • Page 309

    Wago-i/o-system 750 fieldbus communication 309 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.3.5.43 output fieldbus variable udint (ac hex ) the class enables the exchange of data from a particular plc output variable. For wago-i/o-pro or codesys, that me...

  • Page 310: Information

    310 fieldbus communication wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 12.3.5.44 output fieldbus variable udint offset (ad hex ) the class enables the exchange of data from a particular plc output variable. With an offset of 2 bytes to ...

  • Page 311: 13 I/o

    Wago-i/o-system 750 i/o modules 311 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 113 /serie 750 (wago-i/o-system)/gerätebeschreibung/beschreibung/busklemmen - Überschrift 1, Übersicht - Überschrift 2, und allgemeine einleitung @ 4\mod_1237537660059_21....

  • Page 312: 13.2

    312 i/o modules wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 115.1 /serie 750 (wago-i/o-system)/prozessabbild mapping/ethernet - ethernet/ip - modbus/tcp/pa ethernet - modbus/tcp einleitung prozessdatenaufbau (750-830, -842, -849, c...

  • Page 313

    Wago-i/o-system 750 i/o modules 313 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 13.2.1 digital input modules digital input modules supply one bit of data per channel to specify the signal state for the corresponding channel. These bits are mapped into the ...

  • Page 314

    314 i/o modules wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 13.2.1.4 2 channel digital input module with diagnostics and output process data 750-418, 753-418 the digital input module supplies a diagnostic and acknowledge bit for each in...

  • Page 315

    Wago-i/o-system 750 i/o modules 315 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 13.2.1.7 16 channel digital input modules 750-1400, -1402, -1405, -1406, -1407 table 325: 16 channel digital input modules input process image bit 15 bit 14bit 13bit 12bit 11bi...

  • Page 316

    316 i/o modules wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 13.2.2 digital output modules digital output modules use one bit of data per channel to control the output of the corresponding channel. These bits are mapped into the output p...

  • Page 317

    Wago-i/o-system 750 i/o modules 317 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 13.2.2.3 2 channel digital input modules with diagnostics and input process data 750-507 (-508), -522, 753-507 the digital output modules have a diagnostic bit for each output ...

  • Page 318

    318 i/o modules wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 13.2.2.4 4 channel digital output modules 750-504, -516, -519, -531, 753-504, -516, -531, -540 table 330: 4 channel digital output modules output process image bit 7 bit 6 bit ...

  • Page 319

    Wago-i/o-system 750 i/o modules 319 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 13.2.2.7 8 channel digital output modules with diagnostics and input process data 750-537 the digital output modules have a diagnostic bit for each output channel. When an outp...

  • Page 320

    320 i/o modules wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 13.2.2.9 8 channel digital input/output modules 750-1502, -1506 table 335: 8 channel digital input/output modules input process image bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 ...

  • Page 321

    Wago-i/o-system 750 i/o modules 321 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 115.4 /serie 750 (wago-i/o-system)/prozessabbild mapping/ethernet - ethernet/ip - modbus/tcp/pa ethernet - ais-einleitung modbus/tcp (intel, mit word-alignment) @ 7\mod_12...

  • Page 322

    322 i/o modules wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 13.2.3.3 4 channel analog input modules 750-453, -455, -457, -459, -460, -468, (and all variations), 753-453, -455, -457, -459 table 338: 4 channel analog input modules input p...

  • Page 323

    Wago-i/o-system 750 i/o modules 323 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 115.9 /serie 750 (wago-i/o-system)/prozessabbild mapping/ethernet - ethernet/ip - modbus/tcp/pa ethernet - aos-einleitung modbus/tcp (intel, mit word-alignment) @ 7\mod_12...

  • Page 324: 13.2.5  Specialty Modules

    324 i/o modules wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 115.14 /serie 750 (wago-i/o-system)/prozessabbild mapping/ethernet - ethernet/ip - modbus/tcp/pa ethernet - sonderklemmen (intel, mit word-alignment) bis knx-klemme @ 7\mo...

  • Page 325

    Wago-i/o-system 750 i/o modules 325 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 750-404/000-005 the above counter modules have a total of 5 bytes of user data in both the input and output process image (4 bytes of counter data and 1 byte of control/ status...

  • Page 326: Note

    326 i/o modules wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 13.2.5.2 pulse width modules 750-511, (and all variations /xxx-xxx) the above pulse width modules have a total of 6 bytes of user data in both the input and output process imag...

  • Page 327: Note

    Wago-i/o-system 750 i/o modules 327 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 13.2.5.4 serial interface modules with standard data format 750-650/000-001, -014, -015, -016 750-653/000-001, -006 the above serial interface modules with standard data format...

  • Page 328

    328 i/o modules wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 the above ssi transmitter interface modules have a total of 4 bytes of user data in the input process image, which has 2 words mapped into the image. Word alignment is applied....

  • Page 329

    Wago-i/o-system 750 i/o modules 329 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 350: incremental encoder interface modules 750-634 input process image byte destination offset high byte low byte description 0 - s not used status byte 1 d1 d0 counter w...

  • Page 330

    330 i/o modules wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 750-635, 753-635 the above digital pulse interface module has a total of 4 bytes of user data in both the input and output process image (3 bytes of module data and 1 byte of c...

  • Page 331

    Wago-i/o-system 750 i/o modules 331 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 output process image byte destination offset high byte low byte description 0 c1 c0 control byte c1 control byte c0 1 d1 d0 setpoint position setpoint position (lsb) 2 d3 d2 se...

  • Page 332

    332 i/o modules wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 output process image byte destination offset high byte low byte description 0 reserved c0 reserved control byte c0 1 d1 d0 2 d3 d2 3 d5 d4 process data*) / mailbox**) 4 c3 d6 c...

  • Page 333

    Wago-i/o-system 750 i/o modules 333 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 output process image byte destination offset high byte low byte description 0 d0 c dali command, dsi dimming value control byte 1 d2 d1 parameter 2 dali address 2 d4 d3 command...

  • Page 334

    334 i/o modules wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 13.2.5.14 bluetooth ® rf-transceiver 750-644 the size of the process image for the bluetooth ® module can be adjusted to 12, 24 or 48 bytes. It consists of a control byte (inpu...

  • Page 335

    Wago-i/o-system 750 i/o modules 335 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 13.2.5.15 vibration velocity/bearing condition monitoring vib i/o 750-645 the vibration velocity/bearing condition monitoring vib i/o has a total of 12 bytes of user data in bo...

  • Page 336

    336 i/o modules wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 361: knx/eib/tp1 module 753-646 input process image byte destination offset high byte low byte description 0 - s0 not used status byte 1 s1 op extended status byte opcode...

  • Page 337

    Wago-i/o-system 750 i/o modules 337 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 in the operating mode with suppressible mailbox (mode 2), the mailbox and the cyclical process data are mapped next. The following words contain the remaining process dat. The ...

  • Page 338: 13.2.6  System Modules

    338 i/o modules wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 13.2.6 system modules 13.2.6.1 system modules with diagnostics 750-610, -611 the modules provide 2 bits of diagnostics in the input process image for monitoring of the internal...

  • Page 339: 13.3

    Wago-i/o-system 750 i/o modules 339 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 117.1 /serie 750 (wago-i/o-system)/prozessabbild mapping/ethernet - ethernet/ip - modbus/tcp/pa ethernet - ethernet/ip einleitung prozessdatenaufbau (750-841, controller) ...

  • Page 340

    340 i/o modules wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 13.3.1 digital input modules digital input modules supply one bit of data per channel to specify the signal state for the corresponding channel. These bits are mapped into the ...

  • Page 341

    Wago-i/o-system 750 i/o modules 341 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 13.3.1.3 2 channel digital input module with diagnostics 750-419, -421, -424, -425, 753-421, -424, -425 table 367: 2 channel digital input module with diagnostics input process...

  • Page 342

    342 i/o modules wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 13.3.1.5 4 channel digital input modules 750-402, -403, -408, -409, -414, -415, -422, -423, -428, -432, -433, -1420, -1421, -1422 753-402, -403, -408, -409, -415, -422, -423, -...

  • Page 343

    Wago-i/o-system 750 i/o modules 343 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 13.3.2 digital output modules digital output modules use one bit of data per channel to control the output of the corresponding channel. These bits are mapped into the output p...

  • Page 344

    344 i/o modules wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 13.3.2.2 2 channel digital output modules 750-501, -502, -509, -512, -513, -514, -517, -535, (and all variations), 753-501, -502, -509, -512, -513, -514, -517 table 373: 2 chan...

  • Page 345

    Wago-i/o-system 750 i/o modules 345 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 375: 2 channel digital input modules with diagnostics and input process data 75x-506 input process image bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0 diagnostic bit s ...

  • Page 346

    346 i/o modules wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 output process image bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0 controls do 4 channel 4 controls do 3 channel 3 controls do 2 channel 2 controls do 1 channel 1 and the out...

  • Page 347

    Wago-i/o-system 750 i/o modules 347 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 13.3.2.8 16 channel digital output modules 750-1500, -1501, -1504, -1505 table 380: 16 channel digital output modules output process image bit 15 bit 14 bit 13 bit 12 bit 11 bi...

  • Page 348: Note

    348 i/o modules wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 117.4 /serie 750 (wago-i/o-system)/prozessabbild mapping/ethernet - ethernet/ip - modbus/tcp/pa ethernet - ethernet/ip ab ais-rest (750-341/-841) @ 5\mod_1253705986108_21....

  • Page 349

    Wago-i/o-system 750 i/o modules 349 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 13.3.3.2 2 channel analog input modules 750-452, -454, -456, -461, -462, -465, -466, -467, -469, -472, -474, -475, 476, - 477, -478, -479, -480, -481, -483, -485, -492, (and al...

  • Page 350: Information

    350 i/o modules wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 13.3.4 analog output modules the hardware of an analog output module has 16 bits of measured analog data per channel and 8 bits of control/status. However, the coupler/controll...

  • Page 351: 13.3.5  Specialty Modules

    Wago-i/o-system 750 i/o modules 351 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 13.3.5 specialty modules wago has a host of specialty i/o modules that perform various functions. With individual modules beside the data bytes also the control/status byte is ...

  • Page 352

    352 i/o modules wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 output process image byte destination instance high byte low byte description - c control byte d1 d0 n d3 d2 counter setting value and the specialty modules represent 1x6 bytes...

  • Page 353

    Wago-i/o-system 750 i/o modules 353 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 389: counter modules 750-638, 753-638 input process image byte destination instance high byte low byte description - s0 status byte von counter 1 n d1 d0 counter value vo...

  • Page 354: Note

    354 i/o modules wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 note the process image of the / 003-000-variants depends on the parameterized operating mode! With the freely parametrizable variations /003 000 of the serial interface modules...

  • Page 355: Note

    Wago-i/o-system 750 i/o modules 355 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 13.3.5.5 data exchange module 750-654, (and the variation /000-001) the data exchange modules have a total of 4 bytes of user data in both the input and output process image. T...

  • Page 356

    356 i/o modules wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 750-630/000-004, -005, -007 in the input process image, ssi transmitter interface modules with status occupy 5 usable bytes, 4 data bytes, and 1 additional status byte. A total...

  • Page 357

    Wago-i/o-system 750 i/o modules 357 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 750-634 the above incremental encoder interface module has 5 bytes of input data (6 bytes in cycle duration measurement mode) and 3 bytes of output data. The following tables i...

  • Page 358

    358 i/o modules wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 750-635, 753-635 the above digital pulse interface module has a total of 4 bytes of user data in both the input and output process image (3 bytes of module data and 1 byte of c...

  • Page 359

    Wago-i/o-system 750 i/o modules 359 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 output process image byte destination instance high byte low byte description c1 c0 control byte c1 control byte c0 d1 d0 setpoint position setpoint position (lsb) n d3 d2 setp...

  • Page 360

    360 i/o modules wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 output process image byte destination instance high byte low byte description reserved c0 reserved control byte c0 d1 d0 d3 d2 d5 d4 process data*) / mailbox**) c3 d6 control b...

  • Page 361

    Wago-i/o-system 750 i/o modules 361 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 13.3.5.11 dali/dsi master module 750-641 the dali/dsi master module has a total of 6 bytes of user data in both the input and output process image (5 bytes of module data and 1...

  • Page 362

    362 i/o modules wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 13.3.5.13 mp bus master module 750-643 the mp bus master module has a total of 8 bytes of user data in both the input and output process image (6 bytes of module data and 2 byt...

  • Page 363

    Wago-i/o-system 750 i/o modules 363 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 406: bluetooth ® rf-transceiver 750-644 input and output process image byte destination instance high byte low byte description - c0/s0 not used control/status byte d1 d0...

  • Page 364

    364 i/o modules wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 13.3.5.16 as-interface master module 750-655 the length of the process image of the as-interface master module can be set to fixed sizes of 12, 20, 24, 32, 40 or 48 bytes. It c...

  • Page 365: 13.3.6  System Modules

    Wago-i/o-system 750 i/o modules 365 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 117.6 /serie 750 (wago-i/o-system)/prozessabbild mapping/ethernet - ethernet/ip - modbus/tcp/pa ethernet - systemklemmen ethernet/ip @ 7\mod_1272375855608_21.Doc @ 55821 @...

  • Page 366: 14 Application

    366 application examples wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 119 /alle serien (allgemeine module)/feldbuskommunikation/modbus/anwendungsbeispiele - test von modbus-protokoll und feldbuskn. - visualisierung und steuerung sca...

  • Page 367: Note

    Wago-i/o-system 750 application examples 367 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 the use of scada systems includes the areas of visualization and monitoring, data access, trend recording, event and alarm processing, process analysis and targeted in...

  • Page 368: Information

    368 application examples wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 example of the modbus addressing in the case of scada software lookout from national instruments the modbus function codes are used with a 6 digit coding, whereby the ...

  • Page 369

    Wago-i/o-system 750 use in hazardous environments 369 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 121.1 /alle serien (allgemeine module)/einsatz in ex-bereichen/einsatz in explosionsgefährdeten bereichen - Überschrift 1 @ 3\mod_1224075191281_21.Doc @ ...

  • Page 370: 15.1

    370 use in hazardous environments wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 121.4 /serie 750 (wago-i/o-system)/einsatz in ex-bereichen/kennzeichnung - Überschrift 2 @ 3\mod_1224157499140_21.Doc @ 24182 @ 2 @ 1 15.1 identification...

  • Page 371

    Wago-i/o-system 750 use in hazardous environments 371 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 121.8 /serie 750 (wago-i/o-system)/einsatz in ex-bereichen/bedruckung gemäß ex i und iec ex i @ 7\mod_1274338578856_21.Doc @ 56679 @ @ 1 figure 84: examp...

  • Page 372

    372 use in hazardous environments wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 413: description of the inscription inscription text description tÜv 07 atex 554086 x tun 09.0001x approving authority or certificate numbers dust ii de...

  • Page 373

    Wago-i/o-system 750 use in hazardous environments 373 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 121.10 /serie 750 (wago-i/o-system)/einsatz in ex-bereichen/kennzeichnung für amerika gemäß nec - Überschrift 3 @ 3\mod_1224158423187_21.Doc @ 24188 @ 3 ...

  • Page 374: 15.2

    374 use in hazardous environments wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 121.13 /alle serien (allgemeine module)/einsatz in ex-bereichen/errichtungsbestimmungen @ 3\mod_1232453624234_21.Doc @ 26370 @ 2 @ 1 15.2 installation re...

  • Page 375

    Wago-i/o-system 750 use in hazardous environments 375 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 121.20 /serie 750 (wago-i/o-system)/einsatz in ex-bereichen/besondere bedingungen für den sicheren atex- und iec-ex-betrieb gem. Demko 08 atex 142851x & ...

  • Page 376: Atex 554086 X)

    376 use in hazardous environments wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 121.22 /serie 750 (wago-i/o-system)/einsatz in ex-bereichen/besondere bedingungen für den sicheren ex-betrieb gem. Atex-zertifikat tÜv 07 atex 554086 x @...

  • Page 377: 09.0001 X)

    Wago-i/o-system 750 use in hazardous environments 377 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 121.24 /serie 750 (wago-i/o-system)/einsatz in ex-bereichen/besondere bedingungen für den sicheren ex-betrieb gem. Iec-ex-zertifikat tun 09.0001 x @ 7\mo...

  • Page 378: 15.2.4  Ansi/isa 12.12.01

    378 use in hazardous environments wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 121.26 /serie 750 (wago-i/o-system)/einsatz in ex-bereichen/errichtungsbestimmungen ansi isa 12.12.01 @ 3\mod_1224161936609_21.Doc @ 24200 @ 3 @ 1 15.2.4...

  • Page 379: 16 Appendix

    Wago-i/o-system 750 appendix 379 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 123 /alle serien (allgemeine module)/Überschriften für alle serien/anhang - Überschrift 1 @ 4\mod_1239874070437_21.Doc @ 30560 @ 1 @ 1 16 appendix pos: 124.1 /alle serien (al...

  • Page 380: 16.1.2  Interface Group

    380 appendix wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 124.3 /alle serien (allgemeine module)/feldbuskommunikation/snmp (mib)/mib-ii-gruppen - interface group (allgemein) @ 4\mod_1237887683328_21.Doc @ 28906 @ 3 @ 1 16.1.2 interf...

  • Page 381

    Wago-i/o-system 750 appendix 381 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 418: mib ii – interface group identifier entry access description 1.3.6.1.2.1.2.2.1.15 ifinunknown- protos r this entry indicates the number of received packets sent to an u...

  • Page 382: 16.1.3  Ip Group

    382 appendix wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 124.6 /alle serien (allgemeine module)/feldbuskommunikation/snmp (mib)/mib-ii-gruppen - ip group - iproute table group - icmp group - tcp group - udp group - snmp group @ 4\m...

  • Page 383

    Wago-i/o-system 750 appendix 383 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 16.1.4 iproute table group the ip route table contains information about the routing table in the coupler/controller. Table 420: mib ii – iproute table group identifier entry acce...

  • Page 384: 16.1.5  Icmp Group

    384 appendix wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 16.1.5 icmp group table 421: mib ii – icmp group identifier entry access description 1.3.6.1.2.1.5.1 icmpinmsgs r number of received icmp messages 1.3.6.1.2.1.5.2 icmpinerrors r n...

  • Page 385: 16.1.6  Tcp Group

    Wago-i/o-system 750 appendix 385 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 16.1.6 tcp group table 422: mib ii – tcp group identifier entry access description 1.3.6.1.2.1.6.1 tcprtoalgorithm r retransmission time: 1 = other, 2 = constant, 3 = rsre, 4 = va...

  • Page 386: 16.1.7  Udp Group

    386 appendix wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 16.1.7 udp group table 423: mib ii – udp group identifier entry access description 1.3.6.1.2.1.7.1 udpindatagrams r number of received udp frames that could be passed on to the ap...

  • Page 387: 16.1.8  Snmp Group

    Wago-i/o-system 750 appendix 387 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 16.1.8 snmp group pos: 125.1 /serie 750 (wago-i/o-system)/feldbuskommunikation/snmp (mib)/wago-mib-gruppen für 841, 881-teil 1 @ 4\mod_1237977560828_21.Doc @ 29010 @ 233 @ 1 table...

  • Page 388: 16.2

    388 appendix wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 16.2 wago mib groups 16.2.1 company group the company group contains general information about the company wago kontakttechnik gmbh & co. Kg. Table 425: wago mib – company group i...

  • Page 389: 16.2.3  Versions Group

    Wago-i/o-system 750 appendix 389 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 identifier entry access description 1.3.6.1.4.1.13576.10.1.7 wiodeviceclass r device class 10 = controller 20 = coupler 30 = switch 40 = display 50 = sensor 60 = actuator 1.3.6.1....

  • Page 390

    390 appendix wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 16.2.4 real-time clock group the real-time clock group contains information about the system’s real-time clock. Table 428: wago mib – real time clock group identifier entry access...

  • Page 391: 16.2.5  Ethernet Group

    Wago-i/o-system 750 appendix 391 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 16.2.5 ethernet group the ethernet group contains the settings for the controller on the ethernet. Table 429: wago mib – ethernet group identifier entry access description 1.3.6.1...

  • Page 392: 16.2.7  Plc Project Group

    392 appendix wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 125.6 /serie 750 (wago-i/o-system)/feldbuskommunikation/snmp (mib)/wago-mib_gruppen für 841, 881-teil 3 @ 7\mod_1275048206942_21.Doc @ 57175 @ 333333333333 @ 1 16.2.7 plc pro...

  • Page 393: 16.2.8  Http Group

    Wago-i/o-system 750 appendix 393 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 16.2.8 http group the http group contains information and settings for the controller's web server. Table 432: wago mib – http group identifier entry access description 1.3.6.1.4....

  • Page 394: 16.2.10  Sntp Group

    394 appendix wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 16.2.10 sntp group the sntp group contains information and settings for the controller's sntp server. Table 434: wago mib – sntp group identifier entry access description 1.3.6.1....

  • Page 395

    Wago-i/o-system 750 appendix 395 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 435: wago mib – snmp group identifier entry access description 1.3.6.1.4.1.13576.10.1.40.4.2.6 wiosnmp2- protocolenable r/w enable/disable first snmpv1/v2c agent default val...

  • Page 396

    396 appendix wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 435: wago mib – snmp group identifier entry access description 1.3.6.1.4.1.13576.10.1.40.4.3.12 wiosnmp2- authentication- key r/w authentication key for second snmpv3 user d...

  • Page 397

    Wago-i/o-system 750 appendix 397 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 16.2.13 snmp user trap string group the snmp user trap string group contains strings that can be attached to user- specific traps. These strings can be changed via snmp or wago_sn...

  • Page 398: 16.2.15  Modbus Group

    398 appendix wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 16.2.15 modbus group the modbus group contains information and settings about the controller's modbus server. Table 439: wago mib – modbus group identifier entry access descriptio...

  • Page 399: 16.2.16  Ethernet Ip Group

    Wago-i/o-system 750 appendix 399 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 16.2.16 ethernet ip group the ethernet ip group contains information and settings for the controller's ethernet ip. Table 440: wago mib – ethernet ip group identifier entry access...

  • Page 400: 16.2.18  Plc Data Group

    400 appendix wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 441: wago mib – process image group identifier entry access description 1.3.6.1.4.1.13576.10.1.50.8.1.3 wiomoduletype r type of module 1.3.6.1.4.1.13576.10.1.50.8.1.4 wiomod...

  • Page 401: List of Figures

    Wago-i/o-system 750 list of figures 401 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 127 /dokumentation allgemein/verzeichnisse/abbildungsverzeichnis - Überschrift 1 und verzeichnis @ 3\mod_1219222916765_21.Doc @ 21080 @ @ 1 list of figures figure 1: f...

  • Page 402

    402 list of figures wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 figure 43: data exchange between modbus master and i/o modules.............. 95 figure 44: data exchange between plc function (cpu) of the pfc and the i/o modules ............

  • Page 403: List of Tables

    Wago-i/o-system 750 list of tables 403 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 pos: 128 /dokumentation allgemein/gliederungselemente/---seitenwechsel--- @ 3\mod_1221108045078_0.Doc @ 21810 @ @ 1 pos: 129 /dokumentation allgemein/verzeichnisse/tabellenv...

  • Page 404

    404 list of tables wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 44: ethernet libraries for wago-i/o- pro ....................................... 144 table 45: task processing............................................................

  • Page 405

    Wago-i/o-system 750 list of tables 405 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 94: exception of function code fc1......................................................... 225 table 95: request of function code fc2....................................

  • Page 406

    406 list of tables wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 144: register address 0x100b................................................................... 247 table 145: register address 0x1020 ...................................

  • Page 407

    Wago-i/o-system 750 list of tables 407 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 194: message router (02 hex ) – common service ...................................... 267 table 195: assembly (04 hex ) – class...........................................

  • Page 408

    408 list of tables wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 244: discrete output point extended 3 (72 hex ) – class............................ 288 table 245: discrete output point extended 3 (72 hex ) – instance 766...1020.......

  • Page 409

    Wago-i/o-system 750 list of tables 409 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 290: output fieldbus variable usint extended 1 (a4 hex ) – instance 256...510.............................................................................................

  • Page 410

    410 list of tables wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 329: 2 channel digital input modules with diagnostics and input process data 75x-506......................................................................................

  • Page 411

    Wago-i/o-system 750 list of tables 411 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 371: 16 channel digital input modules.................................................... 342 table 372: 1 channel digital output module with input process data .........

  • Page 412

    412 list of tables wago-i/o-system 750 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 table 412: description of printing on................................................................. 370 table 413: description of the inscription............................

  • Page 413

    Wago-i/o-system 750 list of tables 413 750-880, 750-880/025-000 ethernet programmable fieldbus controller manual version 1.0.1 === ende der liste für textmarke verzeichnis_hinten ===.

  • Page 414

    Pos: 131 /dokumentation allgemein/einband/einband rückseite @ 9\mod_1285229376516_21.Doc @ 64944 @ @ 1 wago kontakttechnik gmbh & co. Kg postfach 2880 • d-32385 minden hansastraße 27 • d-32423 minden phone: +49/5 71/8 87 – 0 fax: +49/5 71/8 87 – 1 69 e-mail: info@wago.Com internet: http://www.Wago.C...