115 Volt 30 aMP ConVerSIon (DaSH
™
SPa MoDel)
To ensure you will have an opportunity to use your spa soon after delivery, it is very important that the required
electrical service has been installed. Unless otherwise stipulated by your dealer,
tHIS IS Your reSPonSIbIlItY.
IMPortant:
All electrical circuits must be installed by a qualified, licensed electrician.
230 Volt InStallatIon
(teMPo
™
, relaY
™
& SPrInt
™
SPa MoDelS)
Your spa contains a control box designed to operate at 230V, 60Hz. Installation of a 50 amp. dedicated circuit is
required. The control box must be hard
wired directly to a
subpanel protected
by a Ground Fault
Circuit Interrupter
(GFCI). The
subpanel containing
GFCI breakers is
included with the
spa.
IMPortant
note:
All electrical
connections to the
control box must be
accomplished by a qualified electrician in accordance with the National Electrical Code and in accordance with any
local electrical codes in effect at the time and place of installation.
All electrical connections must be made in accordance with the wiring information contained in this manual and on
the back of the field wiring access panel of the control box. A licensed electrician should install a four-wire electrical
service (two line voltages, one neutral, one ground) from the main electrical service panel to the subpanel.
Your electrician should mount the subpanel in the vicinity of the spa but it should not be closer than five (5) feet from
the spa water edge (NEC 680-38 to 41-A-3).
InStallatIon note:
After the spa has been installed, your electrician can connect the conduit from the subpanel
to the spa’s control box and then complete the wiring connections in the control box.
note:
Complete step-by-step
Installation and Wiring Instructions for all models are included in the Owner’s Manual.
WarnInG:
Removing or bypassing the GFCI breakers in the subpanel at any time will result in an unsafe spa and
will void the warranty.
Pre-Delivery Instructions
Page 10
VERIFY FACTORY JUMPER
REMAINS BETWEEN “
N”
& “
L2”
*
*
See
Owner’s Manual
for Spa Wiring
and Jumper
Configuration
CONTROL BOX
PANEL
ELECTRICAL
MAIN SERVICE
LESS THAN 100 FT.
#8 AWG RED, L2
#8 AWG BLACK, L1
#8 AWG GREEN, GROUND
#8 AWG WHITE, NEUTRAL
50A
WITHIN SIGHT OF THE SPA
THE SUB-PANEL MUST BE
MORE THAN 5 FEET
DO NOT EXCEED 50 FEET
WITH GFCI
BREAKERS
50A
SUB-PANEL
L2
GRD
L2, HOT, #8 AWG RED
L1, HOT, #8 AWG BLACK
GROUND, #8 AWG GREEN*
N, NEUTRAL, #8 AWG WHITE
L1
L2
N
PERMANENTLY CONNECTED
230 VAC, 50A, 60Hz, MODELS
230VAC, 50 Amp
2-POLE
CIRCUIT BREAKER
(NON GFCI)
N
L1
GN
D
ILLUSTRATION
SEE WIRING
230 VAC PERMANENTLY CONNECTED SPA
L1
L2
N
CONVERTED 230VAC SPA MODELS
JUMPERS REQUIRED
NO POWER
JP1
JP2
JP6
JP3
JP4
JP5
JP8
JP7
See
owner’s Manual
for Spa Wiring
and Jumper
Configuration