Watts LF909 Installation, maintenance & repair

Summary of LF909

  • Page 1

    Rp/is-909/909rpda watts 909 osy shown designed for inline servicing important: inquire with governing authorities for local installa- tion requirements. Notice for australia and new zealand, line strainers should be installed between the upstream shutoff valve and the inlet of the backflow pre- vent...

  • Page 2: Series 909/lf909

    2 figure 2 valve size typical flow rates as sized by floor drain manufacturers drain size in. Mm in. Mm 2 1 ⁄ 2 ” 65 55 gpm 2 50 3” 80 112 gpm 3 65 4” 100 170 gpm 4 100 6”, 8”, 10” 150,200,250 350 gpm 5 125 figure 1 series 909/lf909 relief valve dis charge rates zo ne pre ssu re ( psi g) flow rate (...

  • Page 3: Installation

    3 installation a. Series 909/lf909 should be installed in a horizontal and upright position. This positions the relief valve below the first check valve, enabling the zone to drain through the relief valve outlet. The shutoff valve with the test cock is to be mounted on the inlet side of the backflo...

  • Page 4: Test Procedure For

    4 the following test procedure is one of several that is rec og nized through out the unit ed states for ver i fi ca tion of the func tion ing of backflow pre ven ters. The following procedure is not a specific rec om men da tion. The watts se ries of test kits are ca pa ble of per form ing any of t...

  • Page 5: Sizes: 2

    5 servicing first and second checks sizes: 2 1 ⁄ 2 " – 10" (65-250mm) 1. Remove the hatch cover bolts. Note: the 909 is designed so that when the bolts are backed off 1 ⁄ 2 ", all the spring load is re leased from the cover and retained by the check module. Caution ! Be sure to verify this before re...

  • Page 6: Servicing The Relief Valve

    6 servicing the relief valve sizes: 2 1 ⁄ 2 " – 10" (65-250mm) 1. Remove the relief valve cover bolts. Note the 909/lf909 is designed so that when the bolts are backed off 1 ⁄ 2 " all the relief valve spring load is retained by the bottom plug spring module. Caution ! Be sure to verify this before r...

  • Page 7

    7 troubleshooting guide - backflow preventers problem cause solution a. Valve spits periodically from the vent a.1 fluctuating supply pressure. A.1 install a soft seated check valve immediately upstream of the de vice. A.2 fluctuating downstream pressure a.2 install a soft seated check valve downstr...

  • Page 8

    Rp-is-909-909rpda 1319 edp# 1915172 © 2013 watts usa: tel: (978) 688-1811 • fax: (978) 794-1848 • www.Watts.Com canada: tel: (905) 332-4090 • fax: (905) 332-7068 • www.Watts.Ca limited warranty: watts regulator co. (the “company”) warrants each product to be free from defects in material and workman...