Wattstopper CX-105 Installation Instructions Manual

Manual is about: PIR Occupancy Sensor

Summary of CX-105

  • Page 1

    Ins tallation ins tructions cx-105 pir occupancy sensor specifications voltage .................................................................................... 24vdc current consumption ............................................................... 8ma* power supply ...............................

  • Page 2: Unit Description

    Unit description the cx-105 is a 24vdc passive infrared (pir) occupancy sensor which controls lighting and hvac systems based on occupancy. Pir sensing systems are passive systems which react to changes in infrared energy (moving body heat) within the coverage area. Pir sensors must directly “see” m...

  • Page 3: Installation

    Parallel to vertical at 10 foot mounting height parallel to wall at 10 foot mounting height reference surface angle ceiling mounted wall mounted fig. B installation the cx-105 sensors can be mounted to walls or ceilings with the supplied swivel bracket, and the supplied junction box cover plate if n...

  • Page 4: Sensor Angle Adjustment

    5. Insert the tightening screw and nut into the base bracket as illustrated. 6. Use the reference surface angle to adjust the sensor for optimum coverage. When mounted at ten feet, the reference surface angle should be parallel to the wall or the vertical (see figure b). (as the mounting height decr...

  • Page 5: Wiring Directions

    Wiring directions caution turn power off at the circuit breaker before installing power packs or sensors. Each wattstopper bz series power pack can supply power for up to 14 cx-105 sensors. When using more sensors than this, multiple power packs are required. Refer to the wiring diagrams on the next...

  • Page 6: Occupancy

    Control output 24vdc +24vdc white (neutral) red (load) red (line) white black hot n power pack red black blue switch control return blu wires red blk lighting load cx-105 white (neutral) red (load) red (line) white black hot n power pack red black blue switch control output 24vdc (blu) +24vdc (red) ...

  • Page 7: Sensor Adjustment

    Sensor adjustment the sensors are factory preset to allow for quick installation in most applications. Ho wever, verification of proper wiring or coverage, or customizing of the sensor’s settings can be done through the following steps. Before starting, make sure the office furniture is installed, l...

  • Page 8: Troubleshooting

    Troubleshooting lights do not turn on with occupancy, and the following condition exists: led does not flash: when power is initially applied to the sensor, there is a warm-up period of up to 60 seconds before the led is active. 1. Check that the circuit breaker has been turned back on. 2. Check the...

  • Page 9: Override:

    Unwanted sensor activations (led flashes): possible causes 1. Improper sensor location or angle adjustment causing detection outside of desired coverage area. 2. Sensitivity set too high. 3. Sensor located too close to hvac or vav vents with heavy air flow. Possible solutions 1. Mask the lens to red...

  • Page 10: Ordering Information

    Ordering information cx-105-3 occupancy sensor, two-sided aisleway lens mb-1 industrial mount bracket cx-105 cx-105-1 occupancy sensor, dense wide angle lens (std) occupancy sensor, long range lens cx-105-4 occupancy sensor, one-sided aisleway lens bz-50 power pack: 120/277vac, 50/60hz, 24vdc, 225ma...