WEG DeviceNet CFW500 Installation And Operation Manual - 5 Configurations
Flash Memory Module
E
ng
lis
h
CFW500 | 7
5 CONFIGURATIONS
In order to configure transfer data direction selection key,
proceed as indicated in
figure A.1
. The CFW500-MMF
accessory LEDs, at the end of the transfer operation, blink
indicating the transfer status codes shawed in
table 1
.
Table 1: Accessory LEDs indication
Led Blinker Indication
Transfer Status
2 x Status LED (green)
Parameters (Ok), SoftPLC (Ok)
1 x Status LED (green) and
then 1 x Fault LED (red)
Parameters (Ok), SoftPLC
(Not ok)
1 x Fault LED (red) and then 1
x Status LED (green)
Parameters (Not ok), SoftPLC
(Ok)
Status LED (green) intermittent Transferring
2 x Fault LED (red)
Error: disconnected, software
version or transfer failure
3 x Fault LED (red)
Error: Low battery
For further information about the SoftPLC user’s program
copy configurations, refer to the CFW500 SoftPLC
user's manual.
NOTE!
The CFW500-MMF Flash Memory Module is
able to transfer and store only two memory
areas for the parameters, as shown in the figure
below. Therefore, in order to keep the data of
user 2, you must load user 2 (P0204 = 8) before
shutting down the source inverter (Drive A),
make the data transfer with the CFW500-MMF
and, on the destination inverter (Drive B), save
user 2 (P0204 = 10).
CFW500-MMF
Drive A
Drive B
Actual
Actual
User 1
User 1
User 2
User 2
Figure 1: Area of data transferred by the CFW500-MMF