Xantrex XW4024-120 Operation Manual - Using The Setup Menus

Manual is about: XW Series Hybrid Inverter/Charger

Summary of XW4024-120

  • Page 1

    Hybrid inverter/charger xw series hybrid inverter/charger operation guide xw4024-120/240-60 xw4548-120/240-60 xw6048-120/240-60

  • Page 3: Xw Series Inverter/charger

    Xw series inverter/charger operation guide.

  • Page 4

    About xantrex xantrex technology inc. Is a world-leading supplier of advanced power electronics and controls with products from 50 watt mobile units to one mw utility-scale systems for wind, solar, batteries, fuel cells, microturbines, and backup power applications in both grid-connected and stand-a...

  • Page 5: About This Guide

    975-0240-01-01 iii about this guide purpose the purpose of this operation guide is to provideexplanations and procedures for configuring, operating, maintaining, and troubleshooting the xw series inverter/ charger. Scope the guide provides safety guidelines, detailed setup information, and informati...

  • Page 6: Conventions Used

    About this guide iv 975-0240-01-01 conventions used the following conventions are used in this guide. Related information xw power system installation overview (975-0238-01-01) xw power system installation guide (975-0239-01-01) you can find more information about xantrex technology inc. As well as ...

  • Page 7

    975-0240-01-01 v important safety instructions 1. Before using the xw inverter/charger, read all instructions and cautionary markings on the xw inverter/charger, the batteries, and all appropriate sections of this guide. 2. Ensure the xw inverter/charger is installed according to the guidelines and ...

  • Page 8: Explosive Gas Precautions

    Safety vi 975-0240-01-01 explosive gas precautions 1. Working in the vicinity of batteries may be dangerous. Batteries can generate explosive gases during normal operation. Therefore, you must read this guide and follow the instructions exactly before installing or using your xw inverter/charger. 2....

  • Page 9: Fcc Information to The User

    Safety 975-0240-01-01 vii fcc information to the user this equipment has been tested and found to comply with the limits for a class b digital device, pursuant to part 15 of the fcc rules. These limits are designed to provide reasonable protection against harmful interference in a residential instal...

  • Page 10

    Viii.

  • Page 11: Contents

    975-0240-01-01 ix important safety instructions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -v 1 introduction basic features- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–2 basic operation-...

  • Page 12

    Contents x 975-0240-01-01 using the low battery cut out and lbco delay settings - - - - - - - - - - - - - - - - - - - - - - - 3–7 using search mode - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–8 charger settings menu - - - - - - - - - - - - - ...

  • Page 13

    Contents 975-0240-01-01 xi fault messages - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–15 fault types - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4–16 inverter operation after fau...

  • Page 14

    Xii.

  • Page 15: Introduction

    1 introduction chapter 1, “introduction”, describes the operational features of the xw series inverter/charger. Topics in this chapter include: • “basic features” on page 1–2 • “basic operation” on page 1–3.

  • Page 16: Basic Features

    Introduction 1–2 975-0240-01-01 basic features congratulations on your purchase of a xw series inverter/charger from xantrex technology inc. The xw inverter/charger is one of the finest inverter/chargers on the market today, incorporating state-of-the-art technology, high reliability, and convenient...

  • Page 17: Basic Operation

    Basic operation 975-0240-01-01 1–3 basic operation the xw series inverter/charger is a modular “building block” sine-wave inverter/charger that can be used for both residential and commercial stand-alone, grid-backup, and grid-tie applications with battery energy storage. The xw inverter/charger is ...

  • Page 18

    Introduction 1–4 975-0240-01-01 continually flash the ac led on their respective information panels. If the system was in pass-through and ac fails on any unit, all units transfer to invert simultaneously. Faults when an xw inverter/charger in a multi-unit system has a fault, only the affected devic...

  • Page 19

    Basic operation 975-0240-01-01 1–5 islanding protection islanding protection is an essential safety feature that ensures no person working on the utility grid is harmed by a distributed energy source, such an xw inverter/ charger. Islanding protection also prevents loads connected to the inverter fr...

  • Page 20: Monitoring The Inverter

    Introduction 1–6 975-0240-01-01 monitoring the inverter you can monitor xw inverter/charger operation using either the factory-installed inverter information panel or the optional xw system control panel. You can configure the inverter only with the system control panel. Inverter information panel t...

  • Page 21

    Monitoring the inverter 975-0240-01-01 1–7 xw system control panel the xw system control panel is required for configuring the xw inverter/ charger and other xanbus-enabled system components. The system control panel features: • liquid crystal display that provides graphics and text describing opera...

  • Page 22

    1–8.

  • Page 23: Monitoring Operation

    2 monitoring operation chapter 2, “monitoring operation”, contains information about monitoring xw inverter/charger operation using the inverter information panel or the xw system control panel. The topics in this chapter include: • “monitoring operation with the inverter information panel” on page ...

  • Page 24

    Monitoring operation 2–2 975-0240-01-01 monitoring operation with the inverter information panel the inverter information panel displays basic information that enables you to monitor a single xw inverter/charger. The inverter information panel also allows you to turn the xw inverter/charger on and o...

  • Page 25

    Monitoring operation with the inverter information panel 975-0240-01-01 2–3 when one ac input led is on and the other ac input led is flashing, ac input is present on both ac1 and ac2. However, the xw inverter/charger can qualify and receive ac input from only one source at a time. The qualified sou...

  • Page 26

    Monitoring operation 2–4 975-0240-01-01 equalizing batteries button pressing the equalize button (indicated by the symbol) for five seconds turns battery equalization on and off. After this button is pressed, the xw inverter/ charger begins the equalization charge after the next charge cycle is comp...

  • Page 27

    Monitoring operation with the inverter information panel 975-0240-01-01 2–5 turning the xw inverter/charger on and off on/off control when the xw inverter/charger is operating, pressing and holding the on/off button () for five seconds turns the unit off. Pressing the on/off button momentarily retu...

  • Page 28

    Monitoring operation 2–6 975-0240-01-01 monitoring battery level the row of five leds indicates the approximate capacity of the batteries connected to the system. The capacity reading is based on current-compensated battery voltage. There are four battery states: empty, low, medium, and full. When t...

  • Page 29

    Monitoring operation with the xw system control panel 975-0240-01-01 2–7 monitoring operation with the xw system control panel the xw system control panel provides remote configuration and monitoring capability for the xw inverter/charger and other xanbus-enabled devices in the power system. You can...

  • Page 30

    Monitoring operation 2–8 975-0240-01-01 using the standby button the standby button has two functions, depending on how it is pressed. The standby button can disable inverting and charging for all xw inverter/chargers in the system, or, when pressed simultaneously with the exit button, put the entir...

  • Page 31

    Monitoring operation with the xw system control panel 975-0240-01-01 2–9 system status screen the system status screen appears after the startup screen. The system status screen displays aggregated status information for the entire power system. For example, a single system may have three xanbus™ ne...

  • Page 32

    Monitoring operation 2–10 975-0240-01-01 xw inverter/charger home screen the xw inverter/charger home screen is the first of the device home screens. Each xw inverter/charger installed in the system has its own home screen. The xw inverter/charger home screen displays status information for the xw i...

  • Page 33

    Monitoring operation with the xw system control panel 975-0240-01-01 2–11 reading the system status screen the system status screen displays: • qualified ac source (if applicable) and total power to and from the source • battery voltage and capacity level • net battery input or output current • tota...

  • Page 34

    Monitoring operation 2–12 975-0240-01-01 pressing the down arrow button from the xw inverter/charger home screen displays the home screens for other xw inverter/chargers and other xanbus- enabled devices in the system. Figure 2-6 xw inverter/charger home screen setup system xw6048 00:home invert -26...

  • Page 35

    Monitoring operation with the xw system control panel 975-0240-01-01 2–13 fault the xw inverter/charger has an active fault. The fault/warning light on the system control panel is on. Gen support there is ac input from the generator, and the xw inverter/charger is supporting the generator by supplyi...

  • Page 36

    Monitoring operation 2–14 975-0240-01-01 reading the meters screen the meters screen displays total system power production, grid voltage and current status, and load voltage and current status. To view the meters screen: u on the xw inverter/charger setup menu, highlight “meters” and press enter. S...

  • Page 37

    Monitoring operation with the xw system control panel 975-0240-01-01 2–15 table 2-2 meters screen screen item description ac1 ac input power connected to the xw inverter/charger ac1 terminals, in watts and volt-amps. Ac1 is assumed to be connected to the utility grid, but can be connected to any oth...

  • Page 38

    2–16.

  • Page 39: Configuration

    3 configuration chapter 3, “configuration” explains how to navigate through the xw system control panel menus and configure the xw inverter/charger. Topics in this chapter include: • “using the xw system control panel” on page 3–2 • “using the setup menus” on page 3–4.

  • Page 40

    Configuration 3–2 975-0240-01-01 using the xw system control panel the xw inverter/charger is configured using the xw system control panel. The system control panel provides access to settings relating to ac input and output, battery charging, and grid-tie operation. Xw inverter/charger setup menu t...

  • Page 41

    Using the xw system control panel 975-0240-01-01 3–3 setting the time and date xw inverter/charger advanced features such as peak load shaving, charger block, and time-stamped events (faults and warnings and logged historical data) require that the system be set to the correct time. The system contr...

  • Page 42: Using The Setup Menus

    Configuration 3–4 975-0240-01-01 using the setup menus basic menu the xw inverter/charger configuration settings can be viewed in basic and advanced formats (see figure 3-3, “basic and advanced settings” on page 3–6). The basic settings include configuration items you may have to adjust routinely, o...

  • Page 43

    Using the setup menus 975-0240-01-01 3–5 to select the advanced or basic settings: u from the setup menu, with basic settings or advanced settings highlighted, press enter. See figure 3-2. To select and change a configurable setting: 1. On the desired configuration menu, press the up arrow or down a...

  • Page 44

    Configuration 3–6 975-0240-01-01 figure 3-3 basic and advanced settings xw6048 00:ac xw6048 00:inv xw6048 00: multi xw6048 00:gen xw6048 00: aux xw6048 00:grid xw6048 00:chg custom settings xw6048 00: adv connections [44v] [10s] [70v] [50w] [2s] [disabled] [64.0v] [57.6v] [57.6v] [54.0v] [108mv/c] [...

  • Page 45: Inverter Settings Menu

    Inverter settings menu 975-0240-01-01 3–7 inverter settings menu the inverter settings menu contains settings that control when the xw inverter/ charger turns on and off when it is inverting. For default settings, see “inverter menu” on page b–3. Using the low battery cut out and lbco delay settings...

  • Page 46

    Configuration 3–8 975-0240-01-01 bring the battery level back above the low batt cut out setting. After shutdown, the inverter does not support any ac loads, and ac loads must be powered by either a generator or grid power. If using an automatic generator starting system, it is recommended to set th...

  • Page 47

    Inverter settings menu 975-0240-01-01 3–9 notes: • search mode, by function, cannot work with clocks and timers or devices that need power 24 hours a day. Examples of devices with timers include video recorders, coffee makers with brew timers, refrigerators, and freezers with defrost timers. Example...

  • Page 48: Charger Settings Menu

    Configuration 3–10 975-0240-01-01 charger settings menu the charger settings menu gives you options for configuring the xw inverter/ charger to operate from your battery bank. For default settings, see “charger menu” on page b–3. Table 3-3 charger menu items item description batt type batt type sele...

  • Page 49

    Charger settings menu 975-0240-01-01 3–11 battery charger functions when ac power is available, the xw inverter/charger can operate as a battery charger. Different battery types and chemistries require different charging voltage levels. Not charging batteries at the required levels can shorten batte...

  • Page 50

    Configuration 3–12 975-0240-01-01 absorption stage absorption charge is the second stage of battery charging and provides the batteries a controlled, constant voltage. During this stage, the current supplied to the batteries slowly decreases. When this current falls below 2% of the battery capacity,...

  • Page 51

    Charger settings menu 975-0240-01-01 3–13 equalize charging the batteries many battery manufacturers recommend periodic equalize charging to level out the voltage between individual cells, improving battery performance and lifespan. Over time, the battery’s electrolyte can become “stratified,” causi...

  • Page 52

    Configuration 3–14 975-0240-01-01 using charger block the charger block feature halts charging on ac1 (grid) for a period of time each day. This period of time is defined by the chg block start and chg block stop settings. In areas where the utility charges variable rates for electricity, it is pref...

  • Page 53

    Charger settings menu 975-0240-01-01 3–15 custom battery settings menu the custom settings menu can be selected after “custom” is selected under batt type. The custom settings menu allows you to adjust charging and equalization voltage for batteries with specifications that fall outside the default ...

  • Page 54: Ac Settings

    Configuration 3–16 975-0240-01-01 ac settings the ac settings menu configures the voltage and frequency limits for ac line 1 (grid) and ac line 2 (generator). These are the limits at which the xw inverter/ charger considers input voltage qualified—that is, suitable for charging batteries or powering...

  • Page 55: Grid Support Settings

    Grid support settings 975-0240-01-01 3–17 grid support settings the grid support settings menu contains configuration options for grid-tie operation. To enable all these settings, grid support must be enabled in the setup menu (see “xw inverter/charger setup menu” on page 3–2). Important: to allow g...

  • Page 56

    Configuration 3–18 975-0240-01-01 for default settings, see “grid support menu” on page b–5. Energy management the xw inverter/charger can be programmed to control how and when to use utility power. Advanced features allow management of peak loads and time-of- use billing. Charger block see “using c...

  • Page 57

    Grid support settings 975-0240-01-01 3–19 grid support enabled, sell enabled in this mode all available excess dc power is first used to power local loads, and any excess is exported to the utility grid. Peak load shaving many utilities impose a surcharge on their customers based on the peak load us...

  • Page 58

    Configuration 3–20 975-0240-01-01 when using the system for time-of-use metering, the system should be designed with a battery capacity large enough to support loads during the entire peak rate period without reaching the low battery cut out setting. To further ensure the batteries are able to suppo...

  • Page 59: Generator Support Settings

    Generator support settings 975-0240-01-01 3–21 generator support settings generator support allows power to be automatically drawn from the batteries to assist an ac generator to support heavy loads (loads that exceed the available current from the generator). Generators have a limited output curren...

  • Page 60

    Configuration 3–22 975-0240-01-01 for default settings, see “aux menu” on page b–6. Trigger source descriptions low batt voltage activates the auxiliary output when the battery voltage falls below the low batt voltage setting for the trigger delay time. The auxiliary output turns off when the batter...

  • Page 61: Multi-Unit Config Menu

    Multi-unit config menu 975-0240-01-01 3–23 clear delay time. Battery temperature is measured with a battery temperature sensor. Do not use this setting if a battery temperature sensor is not installed. With this setting, the auxiliary output can turn on a fan to cool the battery compartment. Fault a...

  • Page 62

    Configuration 3–24 975-0240-01-01 setting the device name the “dev name” setting allows you to customize the name of the xw inverter/ charger as it is displayed on other screens and menus. The characters available are: • a to z • a to z • 0 to 9 • space. To customize the xw inverter/charger name: 1....

  • Page 63

    Multi-unit config menu 975-0240-01-01 3–25 setting the device number setting the device number gives a xanbus-enabled device a unique identity when several devices of the same type are installed in the networked power system. When each identical device has a unique number, the system control panel c...

  • Page 64: Connections Menu

    Configuration 3–26 975-0240-01-01 connections menu the connections menu contains additional settings to allow the xw inverter/ charger to function as part of a multi-unit networked system. Setting the connections for a xanbus-enabled device provides a way of identifying non-network connections for x...

  • Page 65

    Connections menu 975-0240-01-01 3–27 operating without connections ac1 and ac2 connections can be set to “none” if operating without a connection to a specific power source. Only stand-alone devices (in a system that includes only the device and an scp) may be configured this way. Note that this is ...

  • Page 66

    Configuration 3–28 975-0240-01-01 copying settings from another unit the “copy from” command allows quick configuration of an xw inverter/ charger. After selecting another xw inverter/charger in the system to copy settings from, common parameters are copied from the selected xw inverter/ charger to ...

  • Page 67: Troubleshooting

    4 troubleshooting chapter 4, “troubleshooting”, contains information and procedures for solving possible problems with the xw inverter/charger..

  • Page 68: Troubleshooting Reference

    Troubleshooting 4–2 975-0240-01-01 troubleshooting reference this section provides you with troubleshooting tips to identify and solve most problems that can occur with the xw inverter/charger. This chapter is divided into the following sections: 1. “general troubleshooting guidelines” on page 4–2 2...

  • Page 69: Inverter Applications

    Inverter applications 975-0240-01-01 4–3 p are the battery cables adequately sized and short enough? See the xw power system installation guide for more information. P is the battery in good condition and are all dc connections tight? P are the ac input and output connections and wiring in good cond...

  • Page 70

    Troubleshooting 4–4 975-0240-01-01 problem loads very small loads if the power consumed by a device is less than the threshold of the search mode circuitry, and search mode is enabled, the inverter will not run. Most likely the solution will be to disable the search mode feature or lower the sense t...

  • Page 71: Inverter Troubleshooting

    Inverter troubleshooting 975-0240-01-01 4–5 inverter troubleshooting to determine the cause of an inverter error condition, refer to the troubleshooting solutions below to resolve the situation. Problem possible cause solution unit will not come on (no leds are on) and the inverter information panel...

  • Page 72

    Troubleshooting 4–6 975-0240-01-01 low ac power output or low surge power. Invert led is on. Ac inductive loads are not running at full speed. Insufficient dc current being provided to the inverter to operate the ac loads. Check the battery voltage, fuses or breakers and cable connections. Ensure th...

  • Page 73

    Inverter troubleshooting 975-0240-01-01 4–7 in a grid-interactive mode, the unit is experiencing excessive anti-islanding faults. The utility grid is not dropping out, yet the unit is disconnecting from the grid. The unit has two sets of ac limits: adjustable ac qualification limits (as set on the a...

  • Page 74

    Troubleshooting 4–8 975-0240-01-01 battery charger troubleshooting to determine the cause of an charger error condition, refer to the troubleshooting solutions below to resolve the situation. Problem possible cause solution ac1/ac2 led is on, but will not start charging (allow 40 seconds to synchron...

  • Page 75

    Battery charger troubleshooting 975-0240-01-01 4–9 charger amperage drops off before full charging has finished (no fault led). Ac frequency at the ac input terminal may be out-of-tolerance (too high or low) or the ac voltage may be outside the hi ac volt or lo ac volt settings. The charge settings ...

  • Page 76: Faults and Warnings

    Troubleshooting 4–10 975-0240-01-01 faults and warnings when a fault or warning message appears on the system control panel, you can acknowledge the message to clear the screen. To acknowledge a fault or warning message, press the enter button. This action does not clear the fault or warning conditi...

  • Page 77

    Faults and warnings 975-0240-01-01 4–11 warning types there are two types of warnings: automatic and manual. When the xw inverter/ charger detects a warning condition, it displays a warning message on the system control panel. Table 4-1 describes how they differ in their behavior and in how you can ...

  • Page 78

    Troubleshooting 4–12 975-0240-01-01 w11 ac2 input l1 over voltage automatic ac over voltage warning (ac2 line 1 input is at or above the ac2 hi volt setting, minus 2 v) check ac input voltage. Check or adjust high ac input voltage setting (ac2 hi volt). W12 ac2 input l1 under voltage automatic ac un...

  • Page 79

    Faults and warnings 975-0240-01-01 4–13 w57 fet1 over temperature automatic internal temperature is over 85 °c. Ac input voltage may be too high while charging. Operating too large of a load for too long while inverting. Ambient temperature may be high. Inverter cooling fan may have failed. Inverter...

  • Page 80

    Troubleshooting 4–14 975-0240-01-01 w96 cannot equalize manual the selected battery type should not be equalized. Change battery type if your batteries should be equalized. Gel or agm batteries should not be equalized. W97 battery temp sensor failure. Automatic battery temperature sensor shorted rep...

  • Page 81

    Faults and warnings 975-0240-01-01 4–15 fault messages when the xw inverter/charger detects a fault condition, the fault is displayed on the system control panel. The xw inverter/charger also illuminates the fault light on the system control panel and inverter information panel. A fault affects the ...

  • Page 82

    Troubleshooting 4–16 975-0240-01-01 fault types there are three types of fault messages: automatic faults, manual faults, and escalating automatic faults. Table 4-3 describes how they differ in their behavior and how you can respond to them when they appear on the xw system control panel. Inverter o...

  • Page 83

    Faults and warnings 975-0240-01-01 4–17 f17 to f22: relay welded inverting unit stops inverting and waits for user to clear fault. F23 to f40: anti- islanding grid support (peak load shaving or selling) moves to ac bypass and waits for nominal grid conditions to return for a minimum of five minutes....

  • Page 84

    Troubleshooting 4–18 975-0240-01-01 table 4-5 provides descriptions of the fault messages and solutions. If you are unable to resolve the problem after referring to this table, contact your dealer or customer service. Table 4-5 fault messages fault number message fault type cause solution f1 ac outp...

  • Page 85

    Faults and warnings 975-0240-01-01 4–19 f8 ac1 input l2 over voltage automatic ac1 over-voltage shutdown at the ac1 hi volt setting. Fault clears when voltage falls below the ac1 hi volt setting. If fault persists, check ac input voltage. Check and adjust ac input high voltage setting. F9 ac1 input ...

  • Page 86

    Troubleshooting 4–20 975-0240-01-01 f16 ac2 input l1 under frequency automatic ac2 under-frequency shutdown (ac line 1 input) at the ac2 lo freq setting. Fault clears when frequency rises above the ac2 lo freq setting. Check ac input frequency. Check and adjust ac input low frequency setting. F17 re...

  • Page 87

    Faults and warnings 975-0240-01-01 4–21 f24 ai under frequency automatic under-frequency anti- islanding, caught by the ac qualification limit. See f23. F25 ai over frequency automatic over-frequency anti- islanding, 60.4 hz see f23. F26 ai under frequency automatic under-frequency anti- islanding, ...

  • Page 88

    Troubleshooting 4–22 975-0240-01-01 f38 ai l2 under voltage automatic see f37. See f23. F39 ai l1l2 under voltage automatic under-voltage anti- islanding fault, caught by the qualification limit, voltage difference between l1 and l2. See f23. F40 ai l1l2 under voltage automatic under-voltage anti- i...

  • Page 89

    Faults and warnings 975-0240-01-01 4–23 f47 dc under voltage automatic dc under-voltage shutdown (immediate) occurs if dc voltage is below 16 vdc (24 v) or 32 vdc (48 v) the fault clears and the inverter restarts when dc voltage reaches 23 vdc (24 v) or 46 vdc (48 v). Check for the correct battery v...

  • Page 90

    Troubleshooting 4–24 975-0240-01-01 f57 fet1 over temperature shutdown automatic internal temperature is over 105 °c. Ac input voltage may be too high while charging. Operating too large of a load for too long while inverting. Ambient temperature may be high. Inverter cooling fan may have failed. In...

  • Page 91

    Faults and warnings 975-0240-01-01 4–25 f65 ac overload l2 escalating auto fault. Must occur 3 times in 5 minutes before becoming a manual fault. Excessive load on the ac output. See f63. F66 system configuration fault automatic multi-unit configuration settings are incorrect. Ensure only one unit i...

  • Page 92

    4–26.

  • Page 93: Specifications

    A specifications appendix a, “specifications” provides the electrical and environmental specifications for the xw inverter/charger..

  • Page 94: Electrical Specifications

    Specifications a–2 975-0240-01-01 electrical specifications table a-1 xw series inverter/charger electrical specifications model xw6048-120/240-60 xw4548-120/240-60 xw4024-120/240-60 continuous output power 6,000 w 4,500 w 4,000 w surge rating (10 seconds) 12,000 w 9,000 w 8,000 w surge current l-n:...

  • Page 95

    Electrical specifications 975-0240-01-01 a–3 xw inverter/charger overload capability loads presented to the inverter are seldom constant. Typically, large loads are operated for only short periods of time. In order to provide the maximum utility, xantrex inverters are allowed to operate at power lev...

  • Page 96

    Specifications a–4 975-0240-01-01 output power versus ambient temperature when the internal temperature of the xw inverter/charger exceeds its rated range, the unit reduces it energy output to ensure maximum component ratings are not exceeded. Xw inverter/charger efficiency inverting efficiency (typ...

  • Page 97: Mechanical Specifications

    Mechanical specifications 975-0240-01-01 a–5 charging efficiency (typical) sell mode efficiency (typical) mechanical specifications table a-2 xw series inverter/charger mechanical specifications model xw6048-120/240-60 xw4548-120/240-60 xw4024-120/240-60 supported battery types flooded (default), ge...

  • Page 98: Accessories

    Specifications a–6 975-0240-01-01 accessories system network xanbus (publish-subscribe network, no need for hubs or special cards) emissions fcc class b regulatory approvals ul 1741 1st edition: 2005 version, csa 107.1-01 enclosure type nema type 1—indoor rated temperature range (meets all specifica...

  • Page 99: Default Settings

    B default settings appendix b contains the default configuration settings and ranges for the xw inverter/charger. Configuration settings can be viewed and changed using the xw system control panel..

  • Page 100: Default Settings and Ranges

    Default settings b–2 975-0240-01-01 default settings and ranges figure b-1 shows the xw inverter/charger configuration menus as they appear on the xw system control panel. Figure b-1 configuration menu map (advanced) xw6048 00:ac xw6048 00:inv xw6048 00: multi xw6048 00:gen xw6048 00: aux xw6048 00:...

  • Page 101

    Default settings and ranges 975-0240-01-01 b–3 inverter menu charger menu item default setting range step size 24 v nominal 48 v nominal 24 v nominal 48 v nominal low batt cut out 22v 44v 20–24v 40–48v 1v lbco delay 10s 0–600s 1s high batt cut out 32.0v 70.0 v 29.0–36.0v 58.0–70.0v 0.1v search watts...

  • Page 102

    Default settings b–4 975-0240-01-01 custom battery menu ac menu item default setting a a.Custom battery default settings are based on the flooded battery default settings. The gel and agm default settings are provided here for reference only. Range step size 24 v 48 v 24 v 48 v eqlz support enabled ...

  • Page 103

    Default settings and ranges 975-0240-01-01 b–5 grid support menu gen support menu item default range step size 24 v 48 v 24 v 48 v grid supp volts 27.0v 54.0v 23.0–29.0v 46.0–58.0v 0.1v max sell amps 27a 0–60a a a.This setting is restricted to the selected ac1 breaker size. 1a load shave amps 48a 0–...

  • Page 104

    Default settings b–6 975-0240-01-01 aux menu connections menu item default range step size 24 v 48 v 24 v 48 v manual aux manualoff manualon, manualoff, automatic n/a active lvl activehigh activehigh, activelow n/a trigger src a a.The trigger src setting (and the settings below trigger src) appear o...

  • Page 105: Warranty

    975-0240-01-01 wa–1 warranty and return information warranty what does this warranty cover? This limited warranty is provided by xantrex technology inc. (“xantrex”) and covers defects in workmanship and materials in your xw series inverter/charger. This warranty period lasts for five years from the ...

  • Page 106: Disclaimer

    Warranty and return wa–2 975-0240-01-01 what does this warranty not cover? This limited warranty does not cover normal wear and tear of the product or costs related to the removal, installation, or troubleshooting of the customer's electrical systems. This warranty does not apply to and xantrex will...

  • Page 107: Return Procedure

    Warranty and return 975-0240-01-01 wa–3 return material authorization policy before returning a product directly to xantrex you must obtain a return material authorization (rma) number and the correct factory "ship to" address. Products must also be shipped prepaid. Product shipments will be refused...

  • Page 108

    Warranty and return wa–4 975-0240-01-01 information about your system as soon as you open your xw series inverter/charger package, record the following information and be sure to keep your proof of purchase. If you need to contact customer service, please record the following details before calling....

  • Page 109: Index

    975-0240-01-01 ix-1 numerics 2-stage charge mode 3–12 3-stage charge mode 3–11 a absorption charging stage 3–12 ac settings menu default settings b–4 description 3–16 advanced menu 3–4 automatic faults 4–16 automatic generator start 3–8 auxiliary output menu default settings b–6 description 3–21 b b...

  • Page 110

    Index ix–2 975-0240-01-01 purchase date wa–4 serial number wa–4 inverter information panel 1–6, 2–2 inverter settings menu default settings b–3 description 3–7 inverter status led 2–3 islanding protection 1–5 k keypress for system standby mode 2–8 l load shave 2–13, 3–17, 3–19 m manual faults 4–16 m...

  • Page 112

    Xantrex technology inc. 1 800 670 0707 tel toll free na 1 360 925 5097 tel direct 1 800 994 7828 fax toll free na 1 360 925 5143 fax direct customerservice@xantrex.Com www.Xantrex.Com 975-0240-01-01 printed in china.