Xinje XMP2-32 series Operating Manual

Manual is about: Integral industrial controller

Summary of XMP2-32 series

  • Page 1

    Xinje xmp2-32 series integral industrial controller operating manual xinje electronic co.,ltd.

  • Page 2

    C at a l og 1. Xmp2-32 introduction ..................................................................................................................4 1-1 performance and characteristic ...........................................................................................4 1-2 specs .............

  • Page 4

    0b 1. Xmp2-32 introduction 1-1 performance and characteristic xmp2-32r-e ( relay output type ) and xmp2-32t-e ( transistor output type ) are integrated with hmi ( mp series ) and plc ( xc2 series ) perfectly. They can totally instead of hmi and plc in control system with the premiss of meeting the c...

  • Page 5

    Anti-jamming voltage noise: 1000vp-p air condition no causticity gas protect construction according to ip20 1-2-2 hmi specs 1-2-3 plc specs specs item xmp2-32 program executing format loop scan format, time scan format program format instruction, c language and ladder chart processing speed 0.5us po...

  • Page 6

    High speed processing function high speed count、pulse output、external interrupt setting of time scan space 0~99ms password protection 6 bits ascii self diagnose function power on self-diagnose、monitor timer、grammar check 1-2-4 product type xmp-32 series relay output transistor output xmp2-32r-e xmp2...

  • Page 7

    1-3 part name display and touch area number key function key power point product label input point output point com port download port usb、cj45 port.

  • Page 8

    1-3-1 led display pwr: power supply run: program running stop: program stop 1-3-2 download port n the port is rs-232 standard and double function designed, is able to download plc program and hmi program. Pin2 rxd pin3 txd pin5 gnd pin7 rts n used as rs-485 com port: for hmi connecting with slave de...

  • Page 9

    1-3-3 com port the port is rs-232 standard, is used to connect pc and hmi. Pin2 rxd pin3 txd pin5 gnd 1-3-4 port a and b the port is rs-485 standard, is used to connect meter, inverter, extension model, etc. Attention: a, b port and rs-232 com port are the same port, can not be used at the same time...

  • Page 10

    Installate dimension ( mm ): 1 b 2. In-out specs and exterior layout 2-1 input specs and layout input specs: input connection figure: input signal voltage dc24v±10% input signal current 7ma/dc24v input on current above 4.5ma input off current below 1.5ma input response time about 10ms input signal f...

  • Page 11

    2 4 v + 24 v - r 3 r 4 r 2 r 1 x 1 1 x 0 0 c o m + 5 v r 5 r 6 l e d i = 7m a se n s o r d c p o w e r s u p p l y input point arrangement: 2-2 output specs and layout relay output: interior power below ac250v、dc30v circuit insulation machine insulation action indication led light resistor load 3a i...

  • Page 12

    Output connection figure: u relay output: + 2 4 v c ir c ui t d ri v e r el ay y * 3 y * 2 y * 1 y * 0 m 5 a ~10 a l o ad ~ ac p ow e r c 2 5 0v r e l a y o u t p u t to av o i d b ur n i ng p lc b a si c c i rc u i t s et a fu s e e v e ry 4 p o i nt s su p pl y u transistor output connection use s...

  • Page 13

    3b 3. Plc function and using 3-1 plc instruction xmp2-32 series product used xc2 series plc, the plc instructions are the same as xc2-32. It contains sfc instructions, applied instructions and special function instructions. Please refer to xc series plc manual: paragraph 4, 5,6. Here listed in-out p...

  • Page 14

    3. Interrupt function pointer tag channel input rising interruption falling interruption disable interruption instruction chl1 x2 i0000 i0001 m8050 chl2 x5 i0100 i0101 m8051 chl3 x10 i0200 i0201 m8052 4. Frequency measurement the point is x1, x6, x7. 5. Pulse width modulation (pwm) the point is y0, ...

  • Page 15

    C300~c599:32 bits forth/back counter 【c600~c619】:one phase high speed counter 【c620~c629】:pulse + direction high speed counter 【c630~c639】:ab phase high speed counter d0~d999 【d4000~d4999】 2000 d data register for special using d8000~d8511 d8630~d8729 612 fd0~fd127 128 fd flash rom register for spec...

  • Page 16

    3-3 build a project xmp2-32 series products are integrated with xc series plc and hmi. When editing plc program, please use xcp pro software which is the same as xc series plc. 1. Select the product type open xcppro, click “file---change plc model”: select “xmp2-32”: 2. Edit the plc program after se...

  • Page 17

    3. Download program after editing and saving the program, users need to download them to xmp. Before downloading, ensure the xmp has connected with computer successfully. (please refer to chapter 1-3-2 for cable connection ). Click to open software serial port configuration choose the correct serial...

  • Page 18

    After downloading, click to run the plc program. 2 upload the program if you want to check the plc program in xmp2-32, click to upload the program to the pc. Then click to save the program. 3-4 communication function xmp2-32 series support modbus and free format communication protocol. The instructi...

  • Page 19

    0:300bps 1:600bps 2:1200 bps 3:2400 bps 4:4800 bps 5:9600 bps 6:19.2k bps 7:38.4k bps 8:57.6k bps 9:115.2k bps 0:8bits data 1:7bits data 0:2 stop bits 2:1stop bit 0:no check 1:odd check 2: even check station 1, baud rate 19200bps, 8 data bits, 1 stop bit, even check station no. Modbus station no. : ...

  • Page 20

    0:8 bits communication 1:16 bits communication 0: without start symbol 1: with start symbol 0:without end symbol 1:with end symbol reserved fd8226: 3-4-3 communication mode xmp series product support master and slave mode of modbus communication protocol. Master format: when plc is set to be master ...

  • Page 21

    Word component address modbus address ( decimal k ) modbus address ( hex h ) d0~d7999 0~7999 0~1f3f td0~td618 12288~12906 3000~326a cd0~cd634 14336~14970 3800~3a7a d8000~d8511 16384~16895 4000~41ff fd0~fd5000 18432~23432 4800~5b88 fd8000~fd8511 26624~27135 6800~69ff free format communication transfe...

  • Page 22

    Turn the screen to the next page inquiry, jump to the user appointed screen to write the modified value in the register and continue modifying next register. After the last register in the screen has been modified, it will quit the setting. Alarming list key. After setting the function of alarming l...

  • Page 23

    4-2 build a project please use touchwin software. Open the software, click “file---new” or click to build a new project. Choose “mp760-t(xmp-32)” in the panel window: click “next”, choose “xinje xc series” for plc port device:.

  • Page 24

    Click “next”, choose “unuse download port” for download port device: click “next” to complete the building. The editing interface is as below: the software using details please refer to tp touch screen operating manual..

  • Page 25

    After completing the project editing and saving, connect the download port of xmp and computer serial port with downloading cable, make sure the xmp power is on. Click or “file---download” to start downloading data, the download window is as below: if it appears the item “connection overtime, check ...

  • Page 26

    0 1 4 5 2 3 8 9 6 7 al m f 6 f5 f 4 f 3 f2 f 1 aaa a aa aa a a a a a aaa aa a a aa aa a a aaa a aa aa a a a a a a a a a s to p p wr inverter rs485 modbus protocol meter hmi ma module 5-2. Extend ma model xmp2-32 series product can extend ma model via rs-485 com port (a and b point) in order to contr...

  • Page 27

    Type description ma-8x8yr 8 channels digital input,8 channels digital relay output ma-16x 16 channels digital input ma-16yr 16 channels digital relay output ma-16yt 16 channels digital transistor output ma-4da item voltage output current output dc0~5v、0~10v dc0~20ma、4~20ma analog output range ( exte...

  • Page 28

    Analog input range 0~5v,0~10v 0~20ma,4~20ma maximum input range dc±18v 0~40ma digital output range 12 bits binary value (0~4095) resolution 1/4095(12bit) pid output range 0~k4095 integrated precision 0.8% converting speed 20ms per channel power for analog dc24v±10%,100ma installation fix up the modu...

  • Page 29

    Ma-6pt-p xmp2-32 product can connect with ma model via rs-485 com port ( a and b point ). It can extend 16 ma models via setting dip switch of ma model. Please see the connection figure: the details and using method please refer to ma model manual. Ao g n d g nd vo 2 vo 1 ai 4 g nd 0 v 2 4v ai 3 vi ...