Z-Wave T100R Installation Manual

Summary of T100R

  • Page 1

    Dcn: 140-01773-01 page 1 installation guide model t100r z-wave thermostat this thermostat is compatible with most hvac systems, including the following: 24vac systems note: requires both the 24r and 24c (common) wires standard gas/oil/electric heating systems o 1 stage heating and cooling o 2 stage ...

  • Page 2

    Dcn: 140-01773-01 page 2 installation hvac system setup the thermostat requires that you setup the type and configuration of your hvac system for proper operation. This is done in the thermostat info screen setup button or the installer settings screen on the thermostat. The installer settings is a ...

  • Page 3

    Dcn: 140-01773-01 page 3 thermostat connects to help determine this. If the original system had an orange wire connected to an “o” terminal, then you have a “changeover with cool” system. If you have a brown wire connected to the “b” terminal, then you have a “change over with heat” system. Installe...

  • Page 4

    Dcn: 140-01773-01 page 4 delta settings : the delta t setting is the delta, or difference between, the setpoint and current temp for determining when a heat or cool call comes on. The “delta” is the number of degrees away from setpoint. H/c delta range: 3 - 15 degrees. Default: 3f (1c) sets the mini...

  • Page 5

    Dcn: 140-01773-01 page 5 sets the minimum off time before another heating/cooling cycle can begin. Provides compressor short cycle protection. Temp response range: 1-6 default: 2 adjust the temperature sensor sensitivity. Sets how fast the sensor responds to change. Fan cycler the fan cycler functio...

  • Page 6

    Dcn: 140-01773-01 page 6 installer settings summary setting range default display lock y or n n locks out front buttons service mode submenu test mode y or n n reduces delays for testing system settings submenu mechanical settings submenu sys type std or hp std fan type gas or elec gas c/o type w/he...

  • Page 7

    Dcn: 140-01773-01 page 7 standard hvac system g fan w1 heat stage 1 y1 compressor stage 1 r 24vac return c 24vac common thermostat connection y2 compressor stage 2 w2 heat stage 2 optional 24r connection for single transformer hvac systems rc and rh are jumpered together on thermostat board. Cut rc/...

  • Page 8: Heat Pump Hvac System Wiring

    Dcn: 140-01773-01 page 8 heat pump hvac system thermostat connection g fan w1 aux heat y1 compressor stage 1 r 24vac return c 24vac common y2 compressor stage 2 o change over valve for heat pump systems, connect the 24r connection to either the 24rc or 24rh y1 g y2 rs2 rs2 rsc hc heat pump hvac syst...