Zehnder Rittling ComfoAir 550 Luxe Installer Manual - page 13
9 - EN
Therefore a condensation drain is not necessary
with an enthalpy exchanger.
Ensure that the condensation drain is sealed.
This prevents the ComfoAir from sucking in
any leakage air.
The condensation drain can be sealed with a stan-
dard screw-cap.
2.7 Commissioning the ComfoAir
After installation, the ComfoAir must be commis-
sioned.
This can be done via the P menus on the digital op-
erating device. These P menus can be used to enter
various settings (ventilation programmes, in partic-
ular) for the ComfoAir. An overview of the available
P menus is given below:
Menu
options
P1
Reading statuses (from menu P2)
P2
Setting time delays
P3
Setting and reading the ventilation levels
P4
Setting and reading the temperatures
P5
Setting additional programmes
P6
Setting additional programmes
P7
Reading and resetting malfunctions (and
system information)
P8
Setting the RF input and analogue inputs
(0-10V)
P9
Reading statuses (from menu P5 and P6)
P menus P1, P2 and P9 can be accessed by the
user, mainly to read statuses and set time delays.
The remaining P menus P3 to P8 are intended
sole-
ly
for the installer.
The ComfoAir's bypass valve will not work
for the first 4 minutes after a power cut un
-
less the programme mode is activated.
2.7.1 CC Ease panel
The ComfoAir Luxe can be operated and commis-
sioned by means of a CC Ease panel, which can
be ordered separately. The CC (Comfort Control)
Ease panel is a digital operating device which can
be mounted on the wall in the living room and from
there communicates with the ComfoAir.
Accessing the P menus
1. Press and hold "
" and "
" for 2 sec-
onds, simultaneously.
- Wait until "P 2" appears on the display.
P menus P1, P2 and P9 can now be ac
-
cessed
.
2. Press
and hold "
" and "
" for 2 sec-
onds, simultaneously.
- Wait until P menu ”P3" appears on the
display.
P menus P3 to P8 can now be accessed
.
3. Select the desired P menu, e.g. " 5 ", using "
" or "
".
4. Press "
".
5. Select the desired P sub-menu, e.g. " 51 ", us-
ing "
" or "
".
6. Press "
".