A.O. Smith 110 Troubleshooting Manual - page 18
Troubleshooting Guide
18|
Page
ERROR CODE 721 [510 (T‐D2)], SIX FLASHES/72 [110 (T‐KJR2), 310 (T‐K4)]
FALSE FLAME DETECTION
1) First and foremost, shut off all gas and power to the unit. The problem could be the flame sensor,
but if it isn’t, this is a very dangerous situation.
2) Contact the Technical Service Department for further assistance.
ERROR CODE 741 [510 (T‐D2)], 74 [110 (T‐KJR2), 310 (T‐K4)]
MAIN REMOTE CONTROL PROBLEM
This error code only occurs when there is a miscommunication between the temperature remote
controller and the water heater.
1) Check that all wiring is properly connected to the remote.
2) Verify the correct model of remote is being used for the corresponding tankless model.
3) Verify that only a remote is installed. Multiple remotes will result in this error code.
4) If you disconnect the remote from the heater with the power supply on, this error code will result.
Turn off power before disconnecting the remote from the heater.
5) Check for any signs of power surges.
ERROR CODE 761 [510 (T‐D2)]
COMMUNICATION FAILURE
1) This error code only occurs in a multiple heater setup, where there is a miscommunication between
master and slave units for Easy‐Link systems.
2) This error code will only be displayed on the master heater.
3) This error indicates that the master unit has lost communication with the indicated heater.
4) Verify that there is power to the unit that has lost communication.
5) See the Installation Manual for proper communication cable setup.
6) Check for signs of power surges.
ERROR CODE 991 [510 (T‐D2)], FIVE FLASHES/99 [110 (T‐KJR2), 310 (T‐K4)]
ABNORMAL COMBUSTION
1) Refer to error code 101.
2) Contact the Technical Service Department for further assistance if nothing has worked so far. The
manifold gas pressure may need adjustment.
3) If you are sure that the problem has been solved, reset the computer (p. 23).