AAON AA-EBUS-DRS-TGD-01K Technical Manual - page 11
E-BUS Digital Room Sensor Technical Guide
APPENDIX
11
LCD Backlight Test Screens
To select the third option—
BACKLT—touch
while at the Sensor Confi guration
& Test Screen (Figure 12, page
10). This option allows you to
control when the LCD backlight
turns on and off. You can con-
fi gure the backlight to stay on at
all times, remain off at all times,
or to come on when any button
is touched on the sensor.
To exit this screen, touch
play> . Sensor Confi guration and Test Screens Thermistor Averaging Screen To select the fourth and fi nal op- tion—THRM AVG—, while at the Sensor Confi guration & Test Screen (Figure 12, page 10), touch simultaneously below the and buttons. (See Figure 11, page 10 which shows where to touch to access this option.) This option allows you to set the rate—from 1-15 seconds—at which the sensor takes a new temperature reading. Touch <> to increase the number of seconds and touch <> to decrease the number of seconds. To exit this screen, touch play> . NOTE: The sensor takes the average of the last 10 readings based on the number that is entered in this screen. For example, if you want a 3-second sample, the sensor will take the average of the last 10 readings every 3 seconds over a 30-second span. Therefore, if you have your sensor next to an outside doorway, you would want to enter a higher number for your sample to give a more accurate read- ing for the room temperature in case the outside door is opened often. Figure 15: Backlight Test & Confi guration Screen Figure 16: Temperature Averaging Screen Address Screen To access the Address Screen, while at the Thermistor Averag- ing Screen, (Figure 16), touch the button. This option allows you to set the address—from 1-10. Touch <> to increase the number and touch <> to decrease the number. The default is 1. To exit this screen, touch . Figure 17: Address Screen SENSOR 1 COMM ADDRESS