AAON Mini Controller User Manual - page 14
14
When System Enable is set to Auto, the
controller will maintain both the space
heating and cooling setpoints with operation
depending on the space temperature. When
System Enable is set to Heating, the
controller will maintain only the space
heating setpoint. When System Enable is set
to Cooling, the controller will maintain only
the space cooling setpoint. For heat pump
units, when System Enable is set to
Emergency Heating, the controller will
maintain only the space heating setpoint
using only the emergency heating. When
System Enable is set to Off, the controller
operation will be turned off.
When the controller is in the heating mode
of operation HEAT and an animated icon
will be displayed. When the controller is in
the cooling mode of operation COOL and an
animated icon will be displayed. When OFF
is displayed the mode of operation display is
off.
Occupancy Override (OCC:)
The Occupancy Override options available
are On and Off. Override is automatically
turned on if the space temperature setpoint
has been temporarily changed from the
home screen. The occupancy override will
hold for the duration of the occupancy
override amount of time (adjustable under
Main Menu: System) or until the occupancy
override has been turned off manually from
the Home Screen.
When in the occupied mode of operation a
sun icon is displayed. When in the
unoccupied mode of operation a quarter
moon icon is displayed. OVR is displayed
when the space temperature setpoint has
been temporarily changed from the home
screen or occupancy override has been
turned on manually.
Fan Mode (Fan:)
The Fan Mode options available for both the
unoccupied
and
occupied
modes
of
operation are Auto and On.
Auto activates the fan only during heating
and cooling operation. On activates the fan
for the duration of the occupied or
unoccupied mode of operation.
When the supply fan has been commanded
to run an animated fan icon is displayed.
When the supply fan command stops the fan
icon is motionless.
Main Menu Configuration
About
About menu displays information about the
controller, including:
FW: Firmware
VERSION: Firmware version
BUILT: Date and time of firmware build
ASV: Application software version
MODEL: Controller model number
APP: Application configuration
OPT: Heating and cooling staging
INSTANCE: BACnet instance number
MAC ADDRESS: BACnet Mac Address
S/N: Serial Number
BOARD REV: Hardware revision
Alarm
A flashing SERVICE message on the Home
Screen, below the space temperature,
indicates an alarm. Within the Alarm menu,
press Enter while an alarm is highlighted to
view details. Press Enter on the alarm details
to delete the alarm or Left to go back.