AAON Mini Controller User Manual - page 18
18
FAN - COOL MIN SPEED
Minimum cooling speed of a variable speed
fan. Default is 30%, range is 30-80% and
value must be less than the maximum
cooling speed.
FAN - HEAT MAX SPEED
Maximum heating speed of a variable speed
fan. Default is 100%, range is 50-100% and
value must be greater than the minimum
heating speed.
FAN - HEAT MIN SPEED
Minimum heating speed of a variable speed
fan. Default is 50% for non-heat pump units,
75% for heat pump units, range is 50-100%
and value must be less than the maximum
heating speed.
FAN - DEHUM SPEED
Dehumidification speed of a variable speed
fan. Default is 50% and range is 25-75%
FAN - UNOCC
Unoccupied fan mode options are Auto or
On. Auto activates the fan only during
unoccupied heating and cooling operation.
On activates the fan for the duration of the
unoccupied mode of operation. Default
value is Auto.
FAN - OCC
Occupied fan mode options are Auto or On.
Auto activates the fan only during occupied
heating and cooling operation. On activates
the fan for the duration of the occupied
mode of operation. Default value is On.
HUMIDITY - DEHUMIDIFICATION -
DEHUM
Options available are None or Dehum.
Enables modulating hot gas reheat humidity
control.
HUMIDITY - DEHUMIDIFICATION -
DEHUM PRIORITY
Options available are False or True. False
activates
dehumidification
only
when
heating and cooling setpoints are satisfied.
True activates dehumidification anytime
space humidity is outside dehumidification
setpoints. Default is False.
HUMIDITY - DEHUMIDIFICATION -
DEHUM SETPT
Default setpoint is 50% RH and range is 20-
85% RH.
HUMIDITY - DEHUMIDIFICATION -
DEHUM DEADBAND
Default value is 5% RH and range is 5-15%
RH.
SENSOR SETUP - OAT SENSOR (AI4)
Available outside air temperature sensor
options are Yes or No. Outside air
temperature sensor is required for all air-
cooled application and default value is Yes.
SENSOR - SAT SENSOR (AI3)
Available supply air temperature options are
Yes or No. Supply air temperature sensor is
required for single zone VAV, modulating
hot gas reheat and economizer applications
and default value is No.
SENSOR - AI2
Additional controller input options. Default
value is Not Used.
Not Used - No analog input 2 is connected.
Fan Status - Airflow sensor is connected for
fan status option.
Remote CO
2
Sensor - CO
2
sensor is
connected for CO
2
economizer override
option.
Suction Line PSI - Suction pressure sensor is
connected for modulating hot gas reheat
humidity control option.
Remote Space Avg - Space temperature
sensor is connected for remote averaging
space temperature option.
Remote Space Only - Space temperature
sensor is connected for remote space
temperature option.
OA Humidity - Outside air humidity sensor
is
connected for enthalpy
controlled
economizer option.