ABB i-bus KNX SUG/U 1.1 Product Manual - page 20
ABB i-bus
®
KNX
Commissioning
18 2CDC508171D0201 | SUG/U 1.1
Enable group object
"In operation", 1 bit
Options:
No
Yes
•
Yes
: Enables the 1-bit group object
In operation
.
Dependent parameters:
Sending
Options:
Value 0
Value 1
Sending cycle time
Options:
1…60…65,535 s
The time interval at which the
In operation
group object cyclically sends a telegram is set here.
Note
After bus voltage recovery, the group object sends its value after the set sending and switching
delay time.
Enable group object
"Request status values" 1 bit
Options:
No
Yes
All status messages can be requested via this group object, provided they have been parametrized with
the option
After a change or request
.
•
Yes
: Enables the 1-bit group object
Request status values
.
Dependent parameter:
Request with object value
Options:
0
1
0 or 1
•
0
: Sending status messages is requested with the value 0.
•
1
:
Sending status messages is requested with the value 1.
•
0 or 1:
Sending status messages is requested with the values 0 or 1.