ABB REF 610 Operator's Manual

Manual is about: Feeder Protection Relay

Summary of REF 610

  • Page 1

    Ref 610 feeder protection relay operator’s manual - ansi version.

  • Page 3

    3 ref 610 issued: january 30, 2005 version: a feeder protection relay operator’s manual - ansi version contents 1. Introduction ............................................................................... 5 1.1. About this manual ......................................................................

  • Page 4

    4 1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 3.3.1. Target leds ..................................................................... 29 3.3.1.1. Green target led ................................................ 29 3.3.1.2. Yellow target led ...........................

  • Page 5: Introduction

    1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 5 1. Introduction 1.1. About this manual this manual provides basic information on the protection relay ref 610 and presents detailed instructions on how to use the human-machine interface (hmi) of the relay, also known as ...

  • Page 6

    6 1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 • three normally open trip contacts • two change-over (form c) non-trip contacts and three additional change-over (form c) non-trip contacts on the optional i/o module • output contact functions freely configurable for de...

  • Page 7

    1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 7 • battery charge supervision • continuous self-supervision of electronics and software. • detachable plug-in unit 1.4. Warranty please inquire about the terms of warranty of your nearest abb representative. 1.5. Revision ...

  • Page 8: Safety Information

    8 1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 2. Safety information dangerous voltages can occur on the connectors, even though the auxiliary voltage has been disconnected. National and local electrical safety regulations must always be followed. The device contains ...

  • Page 9: Instructions

    1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 9 3. Instructions 3.1. Hmi features 3.1.1. Front panel the front panel of the protection relay includes: • an alphanumeric 2 x 16 characters’ lcd with backlight and automatic contrast control • three target leds (green, yel...

  • Page 10

    10 1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 3. The display will be returned to the idle mode and the backlight turned off if no operation target message is displayed. However, if the non-volatile function is active, a message shown on the display before the auxili...

  • Page 11

    1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 11 fig. 3.1.2.4.-1 adjusting the display contrast after power pickup of the relay, the factory default value of the display contrast will automatically be restored. 3.1.3. How to use the push buttons the hmi includes push b...

  • Page 12

    12 1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 3.1.4. Main menu the main menu contains six main groups: • measurements • recorded data • operation • settings • configuration • info fig. 3.1.4.-1 the display showing the first main menu group • to navigate between the ...

  • Page 13

    1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 13 as soon as you have replaced the default hmi password, the new password will be required for altering parameter values. Once you have given the valid password, the display will remain in the setting mode until returned t...

  • Page 14

    14 1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 3.1.7. Spa password (from cap 501 password to download) the password for spa bus communication is required for altering parameter values via the spa bus. The default password is 001. You can change the spa password eithe...

  • Page 15

    1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 15 3. Press to enter the setting mode and give the password if required. The second line will start to flash indicating that you are allowed to set the language. 4. Use or to move the cursor to the desired language. 5. Pres...

  • Page 16

    16 1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 fig. 3.1.9.-1 setting the real-time clock 3.1.10. How to reset the trip lockout function the trip lockout function is used to prevent accidental closing of the circuit breaker after a trip. The trip lockout function must...

  • Page 17

    1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 17 3.1.11. How to switch between front and rear connection there are two means of serial communication available for the relay: the front connection for spa bus communication and optional rear communication modules for comm...

  • Page 18

    18 1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 3.1.11.1. Target led for front communication • target off: rear communication is currently selected • lit target: front communication port is currently selected • blinking target: front communication port is currently se...

  • Page 19

    1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 19 3.2. Hmi operation levels the hmi menu consists of a user level and a technical level. The user level is used for measuring and monitoring whereas the technical level is used for advanced protection relay setting and can...

  • Page 20

    20 1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 fig. 3.2.1.2.-1 measurements to access the primary current values by activating the monitoring state: 1. Press and simultaneously to view the primary line currents on phases i a , i b and i c and the ground-fault current...

  • Page 21

    1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 21 5. To return the display to the idle mode, press . Fig. 3.2.1.3.-1 recorded data 3.2.1.4. Info the main menu group info contains information you may need when ordering repair service. 1. Press an arrow button to access t...

  • Page 22

    22 1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 fig. 3.2.1.4.-1 info 3.2.2. Technical level 3.2.2.1. Menu system of parameters press an arrow button to activate the main menu. If the default password is in use, no password will be required to change the parameters. If...

  • Page 23

    1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 23 • with a digital input signal, provided that sgb1 ... 5 / 4 has been set to 1 in both setting groups ( grp1 and grp2 ). • with parameter v150 via the spa bus. When a large number of settings are to be altered, e.G. Durin...

  • Page 24

    24 1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 fig. 3.2.2.2.-2 settings switchgroups the relay includes the following switchgroups: to set functions via switchgroups: 1. Press an arrow button to access the main menu. 2. Use the arrow buttons to select the main menu g...

  • Page 25

    1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 25 3. Use or to select the desired switchgroup (e.G. Sgf2 for display settings) and press . 4. Use or to select setting group 1 or 2 ( grp1 or grp2 ). The active setting group is indicated by an asterisk “ * ”. 5. Press to ...

  • Page 26

    26 1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 3.2.2.3. Configuration in general, the parameters found under configuration are set only once by the customer, i.E. Prior to commissioning of the relay. To alter a parameter: 1. Press an arrow button to access the main m...

  • Page 27

    1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 27 fig. 3.2.2.3.-1 configuration, part 1 measurements recorded data operation settings configuration info main menu group menu parameter menu configuration function test/on communication language memory settings frequency p...

  • Page 28

    28 1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 fig. 3.2.2.3.-2 configuration, part 2 3.2.2.4. How to acknowledge and reset targets, output contacts and memorized values • to clear the leds and the display, press . The leds and the display will be cleared only if the ...

  • Page 29

    1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 29 3.3.1. Target leds when a protection element pickups or generates an alarm, the yellow target led will be lit. When a protection element trips, the yellow target led will remain lit and the red target led will be lit. Wh...

  • Page 30

    30 1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 the yellow target led will continue blinking for as long as a protection element remains blocked. The blocking target will disappear with the digital input signal or when the protection element is no longer picked up. If...

  • Page 31

    1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 31 3.3.2.1. Operation target messages when a protection element picks up, the text pickup will appear on the display along with the name of the function. Additionally, in case of a latching pickup target, the name of the en...

  • Page 32

    32 1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 fig. 3.3.2.1.-4 definite trip-alarm target latching and non-latching targets a latching operation target message will remain on the display until manually cleared or until replaced by a message of higher priority. Howeve...

  • Page 33

    1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 33 (ready) is blinking, the fault target cannot be cleared. In case an internal fault disappears, the green target led will stop blinking and the relay will be returned to the normal service state, but the fault target mess...

  • Page 34

    34 1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 1) may be corrected by formatting to the factory setting. 2) the user-defined values will be set to zero during the internal fault state. Warning in case of a less severe fault (warning), the relay will continue to opera...

  • Page 35

    1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 35 1) the external fault warning can be routed to so2 with sgf1/8. 3.4. Detachable plug-in unit 3.4.1. Identifying the product the order number is found on a label under the lower handle of the relay. Table 3.3.2.3-2 warnin...

  • Page 36

    36 1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 fig. 3.4.1.-1 checking the order number of the relay 3.4.2. Detaching and installing the plug-in unit prior to detaching the plug-in unit from the case, the auxiliary voltage must be disconnected. To detach the plug-in u...

  • Page 37

    1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 37 however, it is highly recomended that all characters in the order number of the substitute plug-in unit, exept for those for indicating a spare part, should match the ones of the case. Otherwise, it may result in loss of...

  • Page 38

    38 1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 fig. 3.4.3.-1 inserting and changing the battery battery_a battery holder note! Polarity battery.

  • Page 39

    1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 39 4. Commissioning and maintenance the relay should be subject to regular tests and maintenance in accordance with national regulations and instructions. Prior to commissioning, the functionality of the application-specifi...

  • Page 40

    40 1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 relay commissioning includes: 1. Verifying that the correct application-specific settings have been entered into the relay. This is done by reading the relay settings either via the hmi or serial communication and compar...

  • Page 41

    1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 41 4.2.2. Preventive parts replacement when being used for real-time clock and recorded data functions, the battery should be changed every five years; refer to section inserting and changing the battery. 4.3. Measurements ...

  • Page 42

    42 1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 7. Press again to return the display to the idle mode. The table below shows the activation order and the corresponding digit flashing when a signal is being tested. Table 4.4.-1 function test it is also possible to test...

  • Page 43

    1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 43 1. Select the programmable led to target detection of light from the arc detection by setting switch 21 to 1 in the sgl for the chosen led. It is also possible to route the detected light signal to an output relay, that ...

  • Page 44

    44 1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 4.7.2. Testing of the ground-fault protection when calculating the current to be injected into the ground-fault current energizing input, the calculation should be done on the basis of the following: the rated current, 0...

  • Page 45: Spare Parts

    1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 45 5. Spare parts 5.1. Plug-in unit the relay’s construction allows a spare part in form of a plug-in unit. The outage time can therefore be reduced to a minimum in case the relay should fail. In case of malfunction, please...

  • Page 46: Repair

    46 1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 6. Repair if the relay fails in operation or if the operating values differ remarkably from the specified values, the relay is to be given a proper overhaul. All major measures involving overhaul of electronics are to be...

  • Page 47: Ordering Information

    1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 47 7. Ordering information refer to the technical reference manual..

  • Page 48: References

    48 1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 8. References other available manuals: • technical reference manual, 1mrs 755535 • installation manual, 1mrs 752265-mum.

  • Page 49: Abbreviations

    1mrs 755539 feeder protection relay operator’s manual - ansi version ref 610 49 9. Abbreviations ansi american national standards institute ascii american standard code for information interchange cbfp circuit-breaker failure protection cpu central processing unit ct current transformer di digital i...

  • Page 50

    Abb oy distribution automation p.O. Box 699 fin-65101 vaasa finland tel. +358 10 22 11 fax. +358 10 224 1094 www.Abb.Com/substationautomation 1 m r s 7555 39 e n 10.2 004 abb inc distribution automation 7036 snowdrift rd allentown, pa. 18106 phone: (610) 395-7333 toll free: (800) 634-6005 fax: (610)...