ABB REJ603 Product Manual - page 15
Self-powered feeder protection
1MDB07217-YN
REJ603
Product version: 3.0
Issued: 2017-11-21
Revision: E
15
ABB
Table 26.High- set earth-fault protection, stage I0>> / 50N
Parameter
Value (Range)
Setting range of pick-up current ‘I0 >>’
External earth measurement (through CBCT or residual connection) :
0.01...12.5 x In in steps 0.001, infinite
Internal earth measurement : 0.1...12.5 x In in steps 0.001, infinite
Operation accuracy
1)
External earth measurement : ± 3.0% x In for value
x I for value ≥ 1.2 In
Internal earth measurement : ± 9.0% x In for value
I for value ≥ 1.2 In
Operation mode
Definite time, Instantaneous
Operate time delay (DMT) ‘t0 >>’
0.04...64 s in steps of 0.01
Operation time accuracy
1)
External earth measurement : ± 2.0% of set value or ± 30 ms
Internal earth measurement : ± 10.0% of set value or ± 30 ms
Reset ratio
0.98
1)
Operation time accuracy for protection functions when relay is in energised condition.
Table 27.Transformer inrush detection, 3I2f> / 68
Parameter
Value (Range)
Inrush threshold value
0.2...32 x In, in steps of 0.01
Ratio Setting
10%...50%, in steps of 1%
Table 28.Thermal overload protection, 3Ith> / 49
Parameter
Value (Range)
Initial thermal level of apparatus 0
0.0…100%, in steps of 1%
Reference current leading to thermal
calculation “Ib”
0.1 … 1.5 x In, in steps of 0.1
Heating time constant of object ‘𝜏′
1.0…300 min, in steps of 1.0
Cooling time constant of object ‘𝜏
↓𝑠
‘
1.0…300 min, in steps of 1.0
Alarm value, alm
50…200%, in steps of 1%
Operate value, trip
50…200%, in steps of 1%
Options for calculating thermal value
during power interruption, powerOFF
1…4
1)
Operation time accuracy
3% of 5 time constant or ± 30s
Reset ratio
0.98
1)
Options for calculating thermal image during power interruption shall be as below
1 = On restoration of power, new value of current after power on will be considered to calculate new value of thermal image for
interruption period Δt.
2 = On restoration of power, new value of thermal image is calculated for interruption period Δt considering that current has
remained constant value during power interruption.
3 = Power interruption of the relay assumes no change of thermal image during interruption period.
4 = Power interruption of the relay resets the thermal image to the set value defined by setting 0.