ABB RIO600 Product Manual

Other manuals for RIO600: Configuration Manual
Manual is about: Remote I/O

Summary of RIO600

  • Page 1

    Remote i/o rio600 product guide.

  • Page 2

    Contents 1. Description.....................................................................3 2. Design............................................................................3 3. Configuration examples..................................................4 4. Self-supervision..........................

  • Page 3

    1. Description rio600 is designed to expand the digital i/o of abb’s relion® series ieds and to provide i/o for the station automation device com600 using the iec 61850 communication. Rio600 allows maximum i/o flexibility and provides a seamless iec 61850 connectivity between the substation binary i...

  • Page 4

    Rio600 has modular architecture with specific functionality like inputs and outputs that are built on the modules. Rio600modules can be stacked on standard din rail to achieve the desired configuration. Rio600 consists of four module types. • psm_h - power supply module • lecm - communication module...

  • Page 5

    Psm_h ready rio600 lecm ready irf rx/tx 10m/100m dom ready irf do1 do2 do3 do4 dom ready irf do1 do2 do3 do4 dom ready irf do1 do2 do3 do4 dom ready irf do1 do2 do3 do4 dom ready irf do1 do2 do3 do4 dom ready irf do1 do2 do3 do4 dom ready irf do1 do2 do3 do4 dom ready irf do1 do2 do3 do4 dom ready i...

  • Page 6

    7. Technical data table 1. Dimensions of the power supply module (psm_h) description value width 51.0 mm height 145.5 mm depth 99.0 mm weight 235.0 g table 2. Dimensions of the communication module (lecm) description value width 32.5 mm height 145.5 mm depth 81.0 mm weight 123.0 g table 3. Dimension...

  • Page 7

    Table 6. Power supply description value u aux nominal 100, 110, 120, 220, 240 v ac, 50 and 60 hz 110, 125, 220, 250 v dc u aux variation 85...264 v ac 88...300 v dc ripple in the dc auxiliary voltage max 15% of the dc value (at frequency of 100 hz) maximum interruption time in the auxiliary dc witho...

  • Page 8

    Table 8. Signal outputs (digital output module dom) description value rated voltage 250v ac/dc continuous contact carry 5a make and carry for 3.0 s 10a make and carry for 0.5 s 15a breaking capacity when the control-circuit time constant l/ r 1a / 0.25a / 0.15a table 9. Communication interface (comm...

  • Page 9

    Table 13. Electromagnetic compatibility and immunity tests description type test value reference electrostatic discharge iec 61000-4-2, level 3 and iec 60255-22-2 • contact discharge 6 kv • air discharge 8 kv radio-frequency electromagnetic field (amplitude modulated) 10 v/m (rms) f= 80 - 1000 mhz i...

  • Page 10

    Table 13. Electromagnetic compatibility and immunity tests, continued description type test value reference voltage dips, short interruptions and voltage variation immunity tests (ac 50 hz and 60 hz) 30 % reduction for 1 period 60% reduction for 50 periods 100% reduction for 5 periods 100% reduction...

  • Page 11

    Table 15. Mechanical tests description reference requirement vibration tests (sinusoidal) iec 60255-21-1 class 2 vibration response test: - f = 10…150 hz - ± 0.075 mm/1.0 g - 1 sweep cycle in each axis vibration endurance test:- f = 10…150 hz - 2.0 g - 20 sweep cycles in each axis shock and bump tes...

  • Page 12

    8. Connection and terminal diagram uaux x1 1 ( pe ) 2 ( nc ) 3 ( n/- ) 4 ( l/+ ) 5 ( nc ) 5 ( pe ) psm_h dim8_h di 1 di 2 di 3 di 4 1 ( 0v + ) 2 ( di1 ) 3 ( di2 ) 4 ( di3 ) 5 ( di4 ) 6 ( 0v + ) x1 di 5 di 6 di 7 di 8 1 ( 0v + ) 2 ( di5 ) 3 ( di6 ) 4 ( di7 ) 5 ( di8 ) 6 ( 0v + ) x2 x1 do 1 do 2 do 3 ...

  • Page 13

    9. Dimensions and mounting a b d e f c guid-907d3c00-52c3-464f-b37e-044c89d1c344 v1 en figure 4. Dimension and mounting details of rio600 power supply module psm_h a 46 mm b 4.5 mm c 51mm d 99 mm e 81 mm f 145.5 mm remote i/o 1mrs757487 a rio600 product version: 1.0 abb 13.

  • Page 14

    Guid-b5c4052e-7782-4e23-9a45-0706b1ef3e51 v1 en figure 5. Dimension and mounting details of rio600 digital input module dim8_h a 46 mm b 4.5 mm c 51 mm d 99 mm e 81 mm f 145.5 mm remote i/o 1mrs757487 a rio600 product version: 1.0 14 abb.

  • Page 15

    A b d f e c guid-3c54dc2f-92f6-4b6c-a457-2f1f0403d871 v1 en figure 6. Dimension and mounting details of rio600 digital output module dom a 27.5 mm b 4.5 mm c 32.5 mm d 99 mm e 81 mm f 145.5 mm remote i/o 1mrs757487 a rio600 product version: 1.0 abb 15.

  • Page 16

    B a d e c guid-7770857a-8b26-4b64-95e4-5addb579d4c8 v1 en figure 7. Dimension and mounting details of rio600 communication module lecm a 27.5 mm b 4.5 mm c 32.5 mm d 81 mm e 145.5 mm remote i/o 1mrs757487 a rio600 product version: 1.0 16 abb.

  • Page 17

    10. Assembly diagram 2 3 4 5 6 7 1 1 2 guid-57402def-96c5-4555-9254-bd644c9d5b40 v1 en figure 8. Assembly drawings of rio600 modules 1 rubber cap 2 end clamp 3 psm module 4 lecm module 5 digital input module 6 digital ouptput module 7 din rail the total length of the assembly can be calculated by ad...

  • Page 18

    The protection and control ied manager pcm600 is available in three different variants, that is pcm600, pcm600 engineering and pcm600 engineering pro. Pcm600 engineering pro with the rio600 connectivity package is used for configuring rio600 in offline or online mode to connect to the other ieds in ...

  • Page 19

    13. Document revision history document revision/date product version history a/2011-12-23 1.0 first release remote i/o 1mrs757487 a rio600 product version: 1.0 abb 19.

  • Page 20

    20

  • Page 24

    Contact us abb oy distribution automation p.O. Box 699 fi-65101 vaasa, finland phone +358 10 22 11 fax +358 10 22 41094 www.Abb.Com/substationautomation 1mrs757487 a © copyright 2011 abb. All rights reserved..