1MRS755347
SPA-ZC 400
63
Ethernet Adapter
Installation and Commissioning Manual
Data set
S12
GetDataSetValues
TP
O
M
Supported
S13
SetDataSetValues
TP
O
O
Not Supported
S14
CreateDataSet
TP
O
O
Not Supported
S15
DeleteDataSet
TP
O
O
Not Supported
S16
GetDataSetDirectory
TP
O
O
Supported
Substitution
S17
SetDataValues
TP
M
M
Supported
Setting gropu control
S18
SelectActiveSG
TP
O
O
Not Supported
S19
SelectEditSG
TP
O
O
Not Supported
S20
SetSGValues
TP
O
O
Not Supported
S21
ConfirmEditSGValues
TP
O
O
Not Supported
S22
GetSGValues
TP
O
O
Not Supported
S23
GetSGCBValues
TP
O
O
Not Supported
Reporting
Buffered report control block (BRCB)
S24
Report
TP
a
a
Supported
S24-1
data-change (dchg)
S24-2
qchg-change (qchg)
S24-3
data-update (dupd)
S25
GetBRCBValues
TP
a
a
Supported
S26
SetBRCBValues
TP
a
a
Supported
Unbuffered report control block (URCB)
S27
Report
TP
a
a
Supported
S27-1
data-change (dchg)
S27-2
qchg-change (qchg)
S27-3
data-update (dupd)
S28
GetURCBValues
TP
a
a
Supported
Table 7.2.3-1
ACSI service conformance statement (Continued)
Services
AA:
TP/MC
Client
(C)
Server
(S)
SPA-ZC 400/
Comments
Summary of SPA-ZC 400
Page 1
Spa-zc 400 ethernet adapter installation and commissioning manual.
Page 3
Ethernet adapter installation and commissioning manual © copyright 2004 abb oy, distribution automation, vaasa, finland 3 spa-zc 400 1mrs755347 issued: 06.10.2004 version: a/06.10.2004 1. About this manual .....................................................................7 1.1. Copyrights ..........
Page 4
4 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 4.8.1. Spa communication parameters .................................... 45 4.9. Using dataset editor ................................................................... 47 4.10.Configuring report control blocks ............
Page 5
1mrs755347 spa-zc 400 5 ethernet adapter installation and commissioning manual 7.3.3.9. Complex measured value (cmv) .......................77 7.3.3.10.Sampled value (sav) .........................................78 7.3.3.11.Wye ...................................................................79 7...
Page 7: About This Manual
1mrs755347 spa-zc 400 7 ethernet adapter installation and commissioning manual 1. About this manual 1.1. Copyrights the information in this document is subject to change without notice and should not be construed as a commitment by abb oy. Abb oy assumes no responsibility for any errors that may app...
Page 8
8 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 this manual is divided into following sections: chapter 2. Introduction this section gives an overview of spa-zc 400, its components and functionality and the engineering tool, and introduces the iec 61850 data modeling p...
Page 9
1mrs755347 spa-zc 400 9 ethernet adapter installation and commissioning manual 1.5. Document conventions the following conventions are used for the presentation of material: • the words in names of screen elements (for example, the title in the title bar of a dialog, the label for a field of a dialo...
Page 10
10 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 1.6. Terminology the following is a list of terms associated with spa-zc 400 that you should be familiar with. The list contains terms that are unique to abb or have a usage or definition that is different from standard ...
Page 11
1mrs755347 spa-zc 400 11 ethernet adapter installation and commissioning manual 1.7. Abbreviations 1.8. Related documents abbreviation description cet communication engineering tool cid configured ied description (a type of scl file) do data object ds data set icd ied configuration description templ...
Page 12
12 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 1.9. Document revisions 1.10. Safety information version date history a 06.10.2004 document created dangerous voltages can occur on the connectors, even though the auxiliary voltage has been disconnected. National and lo...
Page 13: 2. Introduction
1mrs755347 spa-zc 400 13 ethernet adapter installation and commissioning manual 2. Introduction 2.1. Spa-zc 400 product overview spa-zc 400 is used to connect one re_54_ device to the iec 61850-8-1 station bus. The iec 61850 standard defines the iec 61850 communication and engineering specifications...
Page 14
14 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 2.2. Introduction to iec 61850 standard the iec 61850 standard defines the communication between ieds in substations. Ieds support the following functions: - protection and control - integration of innovative sensor and ...
Page 15
1mrs755347 spa-zc 400 15 ethernet adapter installation and commissioning manual in the loop topology, the interface receives the message from the fibre-optic interface and passes it both to the fibre-optic transmitter and to the rs-485 interface. In the star topology, the interface receives the mess...
Page 16
16 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 module parts fig. 2.4.-1 parts of spa-zc 400 2.5. Ordering information 2.5.1. Spa-zc 400 product package spa-zc 400 • spa-zc 400 module • spa-zc 400 installation and commissioning manual spa-zc 400-mm • spa-zc 400 module...
Page 17
1mrs755347 spa-zc 400 17 ethernet adapter installation and commissioning manual spa-zc 400-bb • spa-zc 400 module with simultaneous dual port communication • snap-in connectors for plastic fibre • spa-zc 400 installation and commissioning manual spa-zc 400 configuration cd • engineering tool, commun...
Page 19: 3. Installation
1mrs755347 spa-zc 400 19 ethernet adapter installation and commissioning manual 3. Installation this chapter describes the installation of the spa-zc 400 module and the communication engineering tool (cet). For additional information, such as technical data, maintenance and service, refer to chapter...
Page 20
20 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 4. Then the cet installation program opens. In this dialog click next, see fig. 3.2.2.-2. With the back button you can return to the previous dialog, and with the cancel button exit the installation wizard. This applies ...
Page 21
1mrs755347 spa-zc 400 21 ethernet adapter installation and commissioning manual 5. Read the license agreement, then check the option i accept the license agreement and click next to continue the installation, see fig. 3.2.2.-3. If you check the option i do not accept the license agreement, the next ...
Page 22
22 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 6. Select the folder in which the application is to be installed, see fig. 3.2.2.-4. • to select the default folder shown at the bottom of the dialog, click next. • to select another folder, click browse, choose the fold...
Page 23
1mrs755347 spa-zc 400 23 ethernet adapter installation and commissioning manual 7. Both manuals are installed by default in your local hard drive, see fig. 3.2.2.-5. By clicking next you can continue the installation. • to install a manual, click the respective manual and select will be installed on...
Page 24
24 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 8. On this stage installation can begin, see fig. 3.2.2.-6. Click next to begin the installation. A040009 fig. 3.2.2.-6 ready to install.
Page 25
1mrs755347 spa-zc 400 25 ethernet adapter installation and commissioning manual 9. You can follow the progress of the installation in a dialog that also shows the directory path where the files are copied, see fig. 3.2.2.-7. At this point, you can still cancel the installation by clicking cancel. A0...
Page 26
26 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 10.Then a dialog opens to show that the gateway has been successfully installed, see fig. 3.2.2.-8. Close the dialog and finish the installation by clicking finish. A040011 fig. 3.2.2.-8 installation complete 11.When cli...
Page 27
1mrs755347 spa-zc 400 27 ethernet adapter installation and commissioning manual 3.2.3. Uninstalling cet 1. Open the add or remove programs dialog by selecting start > settings > control panel > add or remove programs in the windows task bar. 2. Select cet and click remove, see fig. 3.2.3.-1. A040012...
Page 28
28 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 4. Then the connectivity package installation program opens. In this dialog click next, see fig. 3.3.-1. With the back button you can return to the previous dialog, and with the cancel button exit the installation wizard...
Page 29
1mrs755347 spa-zc 400 29 ethernet adapter installation and commissioning manual 5. Read the license agreement, then check the option i accept the license agreement and click next to continue the installation, see fig. 3.3.-2. If you check the option i do not accept the license agreement, the next bu...
Page 30
30 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 6. Select the folder in which the application is to be installed, see fig. 3.3.-3. • to select the default folder shown at the bottom of the dialog, click next. • to select another folder, click browse, choose the folder...
Page 31
1mrs755347 spa-zc 400 31 ethernet adapter installation and commissioning manual 7. On this stage installation can begin, see fig. 3.3.-4. Click next to begin the installation. A040019 fig. 3.3.-4 ready to install.
Page 32
32 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 8. You can follow the progress of the installation in a dialog, which also shows the directory path where the files are copied to, see fig. 3.3.-5. At this point, you can still cancel the installation by clicking cancel....
Page 33
1mrs755347 spa-zc 400 33 ethernet adapter installation and commissioning manual 9. Then a dialog opens to show that the connectivity package has been successfully installed, see fig. 3.3.-6. Close the dialog and finish the installation by clicking finish. A040021 fig. 3.3.-6 installation complete 3....
Page 35: 4. Engineering
1mrs755347 spa-zc 400 35 ethernet adapter installation and commissioning manual 4. Engineering 4.1. About this section this section guides you in the engineering tasks required before using spa-zc 400. For more information on the iec 61850 data modeling, refer to the iec 61850 standards listed in se...
Page 36
36 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 4.3. Creating project you need to start the spa-zc 400 communication engineering tool (cet) to open and name a project, see fig. 4.3.-1 and fig. 4.3.-2. A040014 fig. 4.3.-1 creating a new cet project a040013 fig. 4.3.-2 ...
Page 37
1mrs755347 spa-zc 400 37 ethernet adapter installation and commissioning manual 4.5. Building object tree after installing the connectivity package you need to build and configure an object tree in the spa-zc 400 communication engineering tool (cet) to define the communication structure. The fig. 4....
Page 38
38 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 add the objects in the following order: 1. Iec 61850 device object (spa-zc 40x) 2. Logical device objects 3. Logical node objects 4. Data objects 4.5.1. Adding iec 61850 device object to start building the object tree, a...
Page 39
1mrs755347 spa-zc 400 39 ethernet adapter installation and commissioning manual 2. Add a new logical device object (ref 541/3/5), see fig. 4.5.2.-1.This is possible only after you have installed connectivity packages to your computer. The ied’s data model behind spa-zc 400 is described in the logica...
Page 40
40 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 when the actual iec 61850 data model is created the logical device name has two parts: • device object name • logical device name for example spazc40xld0. 4.5.3. Importing iec 61850 data object model of ied 1. Right-clic...
Page 41
1mrs755347 spa-zc 400 41 ethernet adapter installation and commissioning manual a040026 fig. 4.5.3.-1 project explorer dialog in the communication engineering tool window 4.6. Configuring spa-zc 400 using imported cid file if you have to configure several spa-zc 400 with the similar iec 61850 data o...
Page 42
42 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 4.7. Configuring spa-zc 400 using iec 61850 data model components you can configure the ied model from the beginning. You have to be familiar with the ied, spa model and how the ied model can be converted to the iec 6185...
Page 43
1mrs755347 spa-zc 400 43 ethernet adapter installation and commissioning manual a040132 fig. 4.7.-2 do wizard to get the data from the spa model to the iec 61850 model, you have to give spa point data for selected data object in doi editor. To open data object instance (doi) editor, first you have t...
Page 44
44 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 4.8. Configuring communication parameters spa-zc 400 communication parameters are located in the device properties. Spa-zc 400 uses static ip addresses, which have to be defined in the planned network structure, see fig....
Page 45
1mrs755347 spa-zc 400 45 ethernet adapter installation and commissioning manual a040022 fig. 4.8.-1 communication parameters 4.8.1. Spa communication parameters spa-zc 400 needs also ied spa address to access the spa data. Every logical device has spa communication parameters object properties expec...
Page 46
46 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 • enabled this is the default operation mode. When the operation is selected, you can synchronize spa-zc 400 with sntp as it is defined in the iec 61850-8-1 standard and spa-zc 400 is also synchronizing ied over spa. • d...
Page 47
1mrs755347 spa-zc 400 47 ethernet adapter installation and commissioning manual 4.9. Using dataset editor dataset groups selected data, so that client can access to it easily with a single read operation. Dataset is also the basic part of event reporting; data is linked to spontaneous event sending ...
Page 48
48 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 following rcb’s default type is defined for data set: • buffered reporting iec 61850-8-1 buffers events also during the communication break. • buffer time default value for buffered reporting is 100 milliseconds (ms). Wi...
Page 49
1mrs755347 spa-zc 400 49 ethernet adapter installation and commissioning manual a040134 fig. 4.10.-1 report control block buffered reporting needs mandatory report client definitions. Report client definitions links certain rcb to certain client. Client can import the cid file to check what rcb inst...
Page 50
50 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 4.11. Downloading configuration and exporting cid file after you have built the iec 61850 data model and done the spa mapping, it is possible to download the configuration to spa-zc 400. Select the iec 61850 device objec...
Page 51
1mrs755347 spa-zc 400 51 ethernet adapter installation and commissioning manual 4.12. Commissioning spa-zc 400 the downloaded cid file is taken into use when restarting spa-zc 400. Normally, the reset happens automatically after the configuration is downloaded with communication engineering tool. Yo...
Page 52
52 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 4.12.2. Obtaining diagnostic data through ftp the following session gets the diagnostic counters through ftp. C:\>ftp x.X.X.X user: abb password: abb ftp> cd d: ftp> get diagnostic.Txt ftp> quit the q attribute quality b...
Page 53: 5. Technical
1mrs755347 spa-zc 400 53 ethernet adapter installation and commissioning manual 5. Technical data 5.1. Interfaces spa-zc 400 - ied interface - fixed mechanics and fixed connectors for ref 541/3/5, rem 543/5 and ret 541/3/5 protection relays • d-type subminiature connector for iec 61850 traffic • d-t...
Page 54
54 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 lon/spa/iec 60870-5-103 diagnostic led - rx dimensions and weight a040130 fig. 5.1.-1 dimensions of the spa-zc 400 module table 5.1.-1 dimensions and weight type dimensions [mm] weight [g] spa-zc 400 195 x 50 x 26 130 sp...
Page 55
1mrs755347 spa-zc 400 55 ethernet adapter installation and commissioning manual 5.2. Test and conditions table 5.2.-1 environmental test and conditions recommended service temperature range (continuous) -10...+55°c transport and storage temperature range -40...+70°c according to the iec 60068-2-48 d...
Page 56
56 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 electromagnetic emission tests according to the en 55011 • conducted, rf-emission (mains terminal) en 55011, class a, iec 60255-25 radiated rf-emission en 55011, class a, iec 60255-25 ce approval complies with the emc di...
Page 57: Maintenance and Service
1mrs755347 spa-zc 400 57 ethernet adapter installation and commissioning manual 6. Maintenance and service 6.1. General about service if the spa-zc 400 module or a part of it is found to be faulty, the normal service operation is to replace the entire module. For more details, refer to the ordering ...
Page 58
58 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 • spa command timeout spa command timeout should be • spa baud rate and spa slave number baud rate and slave number have to be according to the spa-zc 400 configuration. Table 6.3.-1 protocol selection for re_54_ connect...
Page 59: 7. Technical
1mrs755347 spa-zc 400 59 ethernet adapter installation and commissioning manual 7. Technical reference 7.1. About this section this chapter defines the compliance to iec 61850 in terms of service, modeling, engineering interfaces and also exceptions and local adaptations. The information gives you a...
Page 60
60 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 7.2. Acsi conformance statement 7.2.1. Asci basic conformance statement 7.2.2. Acsi models conformance statement table 7.2.1-1 asci basic conformance statement client/ subscriber server/ publisher spa-zc 400/ comments cl...
Page 61
1mrs755347 spa-zc 400 61 ethernet adapter installation and commissioning manual reporting m7 buffered report control o o supported m7-1 sequence-number m7-2 report-time-stamp m7-3 reason-for-inclusion m7-4 data-set-name m7-5 data-reference m7-6 buffer-overflow m7-7 entryid m7-8 buftim m7-9 intgpd m7...
Page 62
62 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 7.2.3. Acsi service conformance statement the table below defines the acsi service conformance statement depending on the statement defined in table 7.2.1-1. If svc (41/42) is supported m14 multicast svc o o not supporte...
Page 63
1mrs755347 spa-zc 400 63 ethernet adapter installation and commissioning manual data set s12 getdatasetvalues tp o m supported s13 setdatasetvalues tp o o not supported s14 createdataset tp o o not supported s15 deletedataset tp o o not supported s16 getdatasetdirectory tp o o supported substitution...
Page 64
64 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 s29 seturcbvalues tp a a supported logging log control block s30 getlcbvalues tp m m not supported s31 setlcbvalues tp o m not supported log s32 querylogbytime tp b m not supported s33 querylogbyentry tp b m not supporte...
Page 65
1mrs755347 spa-zc 400 65 ethernet adapter installation and commissioning manual s49 getuscvcbvalues tp o o not supported s50 setusvcbvalues tp o o not supported control s51 select m m supported s52 selectwithvalue tp m m supported s53 cancel tp o m supported s54 operate tp m m supported s55 command-...
Page 66
66 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 7.3. Model conformance statement in this chapter the model implementation conformance statement (mics) is defined detailing the standard data object model elements supported by spa- zc 400. It is also possible to export ...
Page 67
1mrs755347 spa-zc 400 67 ethernet adapter installation and commissioning manual 7.3.1.2. Analogue value 7.3.1.3. Configuration of analogue value 7.3.1.4. Range configuration table 7.3.1.2-1 analogue value analoguevalue type definition attribute name attributetype value/ value range m/o/c spa-zc 400/...
Page 68
68 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 7.3.1.5. Step position with transient indication 7.3.2. Originator table 7.3.1.5-1 step position with transient indication valwithtrans type definition attribute name attributetype value/ value range m/o/c spa-zc 400/ co...
Page 69
1mrs755347 spa-zc 400 69 ethernet adapter installation and commissioning manual 7.3.2.1. Unit definition 7.3.2.1. Vector definition 7.3.3. Common data classes 7.3.3.1. Single point status (sps) the table below defines the common data class of single point status. Table 7.3.2-3 unit unit type definit...
Page 70
70 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 7.3.3.2. Double point status (dps) the table below defines the common data class of double point status. Subq quality sv pics_subst not supported subid visible string64 sv pics_subst not supported configuration, descript...
Page 71
1mrs755347 spa-zc 400 71 ethernet adapter installation and commissioning manual 7.3.3.3. Integer status (ins) the table below defines the common data class of integer status. Cdcname visible string255 ex ac_dlnda_m not supported datans visible string255 ex ac_dlnda_m not supported table 7.3.3.2-1 do...
Page 72
72 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 7.3.3.4. Protection activation information (act) the table below defines the common data class of protection activation information. Table 7.3.3.4-1 protection activation information (act) act class attribute name attrib...
Page 73
1mrs755347 spa-zc 400 73 ethernet adapter installation and commissioning manual 7.3.3.5. Directional protection activation information (acd) the table below defines the common data class of directional protection activation information. Table 7.3.3.5-1 directional protection activation information (...
Page 74
74 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 7.3.3.6. Security violation counting (sec) the table below defines the common data class of security violation counting. 7.3.3.7. Binary counter reading (bcr) the table below defines the common data class of binary count...
Page 75
1mrs755347 spa-zc 400 75 ethernet adapter installation and commissioning manual 7.3.3.8. Measured value (mv) the table below defines the common data class of measured value. Q quality st qchg m supported t timestamp st m supported configuration, description and extension units unit cf see annex a o ...
Page 76
76 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 substitution subena boolean sv pics_subst not supported subval analoguevalue sv pics_subst not supported subq quality sv pics_subst not supported subid visible string64 sv pics_subst not supported configuration, descript...
Page 77
1mrs755347 spa-zc 400 77 ethernet adapter installation and commissioning manual 7.3.3.9. Complex measured value (cmv) the table below defines the common data class of measured value. Table 7.3.3.9-1 complex measured value (cmv) cmv class attribute name attribute type fc trgop value/ value range m/o/...
Page 78
78 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 7.3.3.10. Sampled value (sav) the table below defines the common data class of sampled value. Different variants of the type exist based on the connectivity package short address information (saddr). Underlined informati...
Page 79
1mrs755347 spa-zc 400 79 ethernet adapter installation and commissioning manual 7.3.3.11. Wye the table below defines the common data class of wye. Table 7.3.3.11-1 wye sav class attribute name attribute type fc trgop value/ value range m/o/c spa-zc 400/ comments dataname inherited from data class (...
Page 80
80 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 7.3.3.12. Delta (del) the table below defines the common data class of delta. Table 7.3.3.12-1 delta (del) sav class attribute name attribute type fc trgop value/ value range m/o/c spa-zc 400/ comments dataname inherited...
Page 81
1mrs755347 spa-zc 400 81 ethernet adapter installation and commissioning manual 7.3.3.13. Sequence (seq) the table below defines the common data class of sequence. 7.3.3.14. Harmonic value (hmv) the table below defines the common data class of harmonic value. Table 7.3.3.13-1 sequence (seq) sav clas...
Page 82
82 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 t timestamp mx m not supported harmonics and interharmonics har array[0..Numhar] of vector m mx dchg, dupd m not supported configuration, description and extension numhar int16u cf >1 m not supported numcycl int16u cf >0...
Page 83
1mrs755347 spa-zc 400 83 ethernet adapter installation and commissioning manual 7.3.3.15. Harmonic value for wye (hwye) the table below defines the common data class of harmonic value for wye. Table 7.3.3.15-1 harmonic value for wye (hwye) hwye class attribute name attribute type fc trgop value/ val...
Page 84
84 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 7.3.3.16. Harmonic value for del (hdel) the table below defines the common data class of harmonic value for del. Rmstim int32u cf ac_rms_m not supported d visible string255 dc text o not supported cdcns visible string255...
Page 87
1mrs755347 spa-zc 400 87 ethernet adapter installation and commissioning manual 7.3.3.18. Controllable double point (dpc) the table below defines the common data class of controllable double point. Table 7.3.3.18-1 controllable double point (dpc) spc class attribute name attribute type fc trgop valu...
Page 88
88 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 7.3.3.19. Controllable integer status (inc) the table below defines the common data class of controllable integer status. D visible string255 dc text o supported cdcns visible string255 ex ac_dlnda_m not supported cdcnam...
Page 90
90 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 7.3.3.20. Binary controlled step position information (bsc) the table below defines the common data class of binary controlled step position information. Table 7.3.3.20-1 binary controlled step position information (bsc)...
Page 91
1mrs755347 spa-zc 400 91 ethernet adapter installation and commissioning manual 7.3.3.21. Integer controlled step position information (isc) the table below defines the common data class of integer controlled step position information. Minval int8 cf o not supported maxval int8 cf o not supported st...
Page 92
92 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 substitution subena boolean sv pics_subst not supported subval valwithtrans sv pics_subst not supported subq quality sv pics_subst not supported subid visible string 64 sv pics_subst not supported configuration, descript...
Page 93
1mrs755347 spa-zc 400 93 ethernet adapter installation and commissioning manual 7.3.3.22. Controllable analogue set point information (apc) the table below defines the common data class of controllable analogue set point information. Table 7.3.3.22-1 analogue set point (apc) apc class attribute name...
Page 94
94 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 7.3.3.23. Single point setting (spg) the table below defines the common data class of single point setting. 7.3.3.24. Integer status setting (ing) the table below defines the common data class of integer status setting. ...
Page 95
1mrs755347 spa-zc 400 95 ethernet adapter installation and commissioning manual 7.3.3.25. Analogue setting (asg) the table below defines the common data class of analogue setting. Stepsize int32 cf 1 … (maxval - minval) o not supported d visible string255 dc text o not supported cdcns visible string...
Page 96
96 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 7.3.3.26. Setting curve (curve) the table below defines the common data class of setting curve. Table 7.3.3.26-1 setting curve (curve) asg class attribute name attribute type fc trgop value/ value range m/o/c spa-zc 400/...
Page 97
1mrs755347 spa-zc 400 97 ethernet adapter installation and commissioning manual 7.3.3.27. Device name plate (dpl) the table below defines the common data class of device name plate. 7.3.3.28. Logical node name plate (lpl) the table below defines the common data class of logical node name plate. Tabl...
Page 98
98 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 7.3.3.29. Curve shape description (csd) the table below defines the common data class of curve shape description. Lnns visible string255 ex ac_dld_m supported cdcns visible string255 ex ac_dlnda_m not supported cdcname v...
Page 99
1mrs755347 spa-zc 400 99 ethernet adapter installation and commissioning manual 7.4. Scl conformance statement the table below defines the support of substation configuration language. Implementations claiming conformance to scl.2 or scl.3 may support the acsi services defined in the table below. Ta...
Page 100
100 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 the additional mms services, defined table below, must be supported if support for scl.2 or scl.3 is declared. 7.5. Scl control block the scl control block must have a functional constraint of sc. This control block mus...
Page 101
1mrs755347 spa-zc 400 101 ethernet adapter installation and commissioning manual 7.6. Protocol implementation conformance statement in the tables below basic protocol conformance statements (pics) are defined. 7.6.1. Profile conformance 7.6.1.1. Mms conformance all needed services supporting the acs...
Page 102
102 1mrs755347 ethernet adapter installation and commissioning manual spa-zc 400 7.6.1.2. Goose services table below defines the conformance of the goose service. Table 7.6.1.2-1 goose conformance subscriber publisher spa-zc 400/comments goose services a a not supported sendgoosemessage m m not supp...
Page 104
Abb oy distribution automation p.O. Box 699 fi-65101 vaasa finland tel. +358 10 22 11 fax. +358 10 224 1094 www.Abb.Com/substationautomation 1m r s 75 53 47 e n 10 .20 0 4.