ABB VD4 Series Instruction Manual - page 7
VD4 Vacuum Circuit-breaker | Technical data 7
Equipment
Shunt release OFF
Shunt release ON
Blocking magnet
Undervoltage release
undelayed
delayed
Indirect overcurrent release
with intermediate current transformer
two-phase
three-phase
Y2
3)
, Y9
3)
Y2
4)
, Y9
4)
Y3
3)
Y3
4)
Y1
3)
4)
Y4
Y7
Power consumption
1)
AC
VA
250
310
250
310
10
11
10
3.5
2)
/15
2.0
2)
/15
DC
W
250
310
250
310
10
10
-
-
-
1)
Approximate values
2)
With short-circuited intermediate current transformer
3)
Auxiliary voltages AC: 110 and 220 V, DC: 24, 48, 60, 110 and 220 V.
4)
Auxiliary voltages AC: 240 V, DC: 125 and 240 V.
2.3 Technical data
Motor-operated mechanisms
Auxiliary
voltage
V
AC
110
220
240
DC
24
30
48
60
110
125
220
240
consumption
1)
Power
VA/W
200
200
200
180
180
180
180
190
190
190
190
Charging time
(maximum)
2)
s
15
15
15
15
15
15
15
15
15
15
15
1)
Approximate values
2)
At the rated auxiliary voltage
2.2 Technical data
Releases and blocking magnet