    Abloy oy an assa abloy group company abloy ® da460 swing door operator – installation and commissioning manual.

  • Page 2

    2 ------------------- this manual contains important safety instructions ------------------- warning - it is important for safety of persons to follow these instructions. -------------------------------------------- save these instructions -------------------------------------------- warning! Warnin...

  • Page 3

    3 contents approvals......................................................................................... 2 revision.........................................................................................4 content of delivery.........................................................................

  • Page 4

    4 revision following pages has been revised: page revision 12, 13 the lenght of sliding arm has increased. Pictures has been updated. As at 29.02.2008..

  • Page 5

    5 da460 swing door operator - screws 4 pcs m8x22 da103 mounting plate - screws 6 pcs 5,5x32 da147 standard arm - screws 2 pcs 5,5x32 and 1 pcs m8x30 da148 extended arm - screws 2 pcs 5,5x32 and 1 pcs m8x30 da149 sliding arm - screws 2 pcs 5,5x50 and 1 pcs m8x30 da150 extension piece - 10 mm + m8x35 ...

  • Page 6

    6 general information technical data measures 595 (l) x 85 (h) x 107 (w) mm weight 6,5 kg • supply voltage 90-264 vac, 47-63 hz rated output 70 w enclosure class ip20 temperature range storage -30...+85 °c (in dry premises) operation: -15...+50 °c (in dry premises) the automatic swing door operator ...

  • Page 7

    7 operation abloy ® da460 is an electromechanical swing door operator for heavy use. The door operator includes new free swing function: when using the door manually it operates lightly without motor’s resistance and the door can be left in open position when required. It can be used on both single ...

  • Page 8

    8 standard arm 50 60 70 80 90 100 110 120 130 140 150 160 170 180 60 70 80 90 100 110 120 130 140 150 door weight [kg] door width [cm] sliding arm door width [cm] 50 60 70 80 90 100 110 120 130 140 150 160 170 180 60 70 80 90 100 110 120 130 140 150 door weight [kg] door weight.

  • Page 9

    9 installation tools required drill set of ball ended allen wrenches # 2 phillips head screwdriver flat blade screwdrivers, 2 pcs steps of installation - preparing installation - installing the mounting plate - mounting the operator and the arm - connecting the operator to mains - commissioning - te...

  • Page 10

    10 installing the mounting plate operator is to be installed on the transom, with the main switch located towards the hinge. Use the mounting plate da103 with the door operator ensuring the installation base is level and securely fixed to a flat surface. Installation measurements for standard arm an...

  • Page 11

    11 assembly of the operator and the standard arm to the closing side - after installation, ensure that the arm and door are properly adjusted. - mount a door stop to the door open position so that wind will not drive the door against the wall, resulting in damage. - tighten the holding screw. Frame ...

  • Page 12

    12 assembly of the operator and the sliding arm da149 to the closing side - after installation, ensure that the arm and door are properly adjusted. - mount a door stop to the door open position so that wind will not drive the door against the wall, resulting in damage. - tighten the holding screw. F...

  • Page 13

    13 assembly of the operator and the sliding arm da149 to the opening side - after installation, ensure that the arm and door are properly adjusted. - mount a door stop to the door open position so that wind will not drive the door against the wall, resulting in damage. - tighten the holding screw. F...

  • Page 14

    14 internal connections - electrical connections should be made by a qualified electrician. - the power plug must have an easy access. - if a permanent connection is made unit must be equipped with an external switch providing all pole disconnection. - keep the mains disconnected during installation...

  • Page 15

    15 commissioning 1 check the free movement of the door. 2 turn mode switch to man. The mode switch is located in the head panel. 3 plug in the mains and turn main switch on. The main switch is located in the head panel. 4 choose the type of the arm the jumpers are located on the control board. Jumpe...

  • Page 16

    16 7 teach door open and closed position 6 check the option option sing le ma ster co rri dor fire n.C free swing option sing le ma ster co rri dor fire n.C free swing option sing le ma ster co rri dor fire n.C free swing select "single" for a stand alone door. "master" and "corridor", not yet avail...

  • Page 17

    17 commissioning 9 test the operation - turn mode switch to auto. - test the operation. - if the function is not desired, repeat steps 4 to 9. Door weight (kg) door width (mm) time (sec) 60 80 100 120 800 2,7 3,2 3,5 3,9 1000 3,4 4,0 4,4 4,8 1200 4,1 4,7 5,3 5,8 1300 4,5 5,1 5,8 6,3 adjust the openi...

  • Page 18

    18 a safe door the safety of the door operator is controlled by basic adjustments; operator force, speeds, and hold open times. - the operator force is an important adjustment. A high value affects to the safety feature and also to its sensitivity. - high speeds increases the energy transferred in t...

  • Page 19

    19 12 +24 vdc, 500 ma output 11 +12 vdc, 1,0 a output 10 ground 7, 8, 9 potential free relay output for lock drive 6 normal impulse 5 delayed impulse. Door will open after 1,0 seconds delay. 4 safety sensor ground to stop the door movement during operation 3 locking circuit inhibits the opening if t...

  • Page 20

    20 impulse inputs the closing contact drive (no) must be potential free. The impulse device, like a push button or motion sensor, must be installed within direct sight of the door. Maximum length of the impulse device cable is 30 meters. The total resistance of the control switch and its wiring must...

  • Page 21

    21 connection examples safety sensors da001 and da002 on the opening side on the closing side connect the 1000 ohm resistor from connectors 1 and 4 to safety sensor connectors 4 and 6. The resistor connection controls the condition of cable. If cable is cut or short circuit, the door will stop. When...

  • Page 22

    22 connection examples da061 and da062 microwave motion sensor da063 microwave motion sensor 1 2 3 4 5 6 7 8 9 10 11 12 +24 out normal safety locking gnd circuit sensor impulse fire detector +12v out delayed impulse gnd yellow white green pink blue brown 1 2 3 4 5 6 7 8 9 10 11 12 +24 out normal saf...

  • Page 23

    23 connection examples da033 elbow switch da039 and da049 rotary switch 1 2 3 4 5 6 7 8 9 10 11 12 +24 out normal safety locking gnd circuit sensor impulse fire detector +12v out delayed impulse gnd com n.O n.C red black blue x2 x5 manual = no connection auto = 2...1 open = 2...3 1 3 2.

  • Page 24

    24 connection examples electric locks el412, el414, el512 black blue red green 1 2 3 4 5 6 7 8 9 10 11 12 +24 out normal safety locking gnd circuit sensor impulse fire detector +12v out delayed impulse gnd motor locks el490, el590 1 2 3 4 5 6 7 8 9 10 11 12 +24 out normal safety locking gnd circuit ...

  • Page 25

    25 connection examples motorlocks el420, el520 el520 consumes max. 600ma current. Electric lock el410 black blue red green 1 2 3 4 5 6 7 8 9 10 11 12 +24 out normal safety locking gnd circuit sensor impulse fire detector +12v out delayed impulse gnd 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 ac /dc ...

  • Page 26

    26 connection examples rebated doors 1 2 3 4 5 6 7 8 9 10 11 12 +24 out normal safety locking gnd circuit sensor impulse fire detector +12v out delayed impulse gnd 1 2 3 4 5 6 7 8 9 10 11 12 +24 out normal safety locking gnd circuit sensor impulse fire detector +12v out delayed impulse gnd impulse d...

  • Page 27

    27 fire door system connection examples operation: when detector reacts, it’s relay switches on. Then the gnd (-) is disconnected from the operator’s control unit (connector 2). The operator doesn’t open the door from impulse but it have to be opened manually. The operator closes the door after manu...

  • Page 28

    28 self diagnostics the means of diagnostic features is to - detect malfunctions - try to take care of safety during malfunction - get the operator to recover from the defected state. In case the result of the diagnostics shows unrecoverable malfunctions, the door operator is considered as unsafe, a...

  • Page 29

    29 maintenance requirements for trouble-free use of the operator installation, commissioning and maintenance is made by trained and qualified technician. Door leaf is moving sensitively and locking works well. Regular annual services are made : - under 100 openings per day; service once a year - 100...

  • Page 30

    30 compatible unit 809854 control unit 809877 head panel 810174 rear damper 809820 side damper 803520 transformer 810057 mode switch 809928 main switch 807437 position sensor 809863 da147 da148 da149 cover aluminium 410358 cover white 410357 da460 spare parts.

  • Page 31

    31.

  • Page 32

    An assa abloy group company abloy oy is one of the leading manufacturers of locks, locking systems and architectural hardware and the world’s leading developer of products in the field of electromechanical locking technology. The assa abloy group is the world’s leading manufacturer and supplier of l...