Aircalo CASSETTE BALI Installation And Maintenance Manual - page 13
12
6. ELECTRIC CONNECTIONS
The electrical installation of a device must comply with the installation rules in force and carried out by
qualified personnel according to the diagrams attached end of document.
The supply voltage is 230 V single-phase + earth (operation mini 198 V ; Max: 264 V).
Make the connection of earth before any other connection.
Check that the power supply is done through a switch that disconnects all poles, keeping a distance of at
least 3 mm between the contacts.
Caution : Electrical regulation requires that any installation of rotating equipment should have an effective
protection from all points of view. In this context, the guarantees issued by the Union of Electrical Construction
does not apply to motors whose winding is "burnt".
The warranty is void in case of changes in wiring and factory settings.
All electrical connections should be made on the terminal block on the same side as easements of the
unit.
An electrical box must control each device. In the case of multiple devices controlled by a single
thermostat, it is necessary to provide an electrical relay system.
We recommend the use of electric supply cable from the unit HO7 RN-F type. The section of the wire
connections must be defined in terms of power absorbed (below) and cable lengths to put depending of
the geometry of the premises.
Motor power
Electric power auxiliary heating resistors
Power
BALI 60
BALI 90
2000 W
4.40 (A)
-
4000 W
-
8.80 (A)
Note : A reset safety thermostat is integrated into the control box.
Caution :
Post-ventilation: It is necessary to provide a delay of forced operation of the fan motor after stopping the
electric coil to ensure dissipation of residual energy on resistance. Post-ventilation time 45 seconds.
Non-observance of this control can result in damage to the unit or the environment.
During operation of the electric coil, a power cut can cause tripping of the safety thermostat.
The operation of electrical heaters is prohibited when the main battery is supplied with hot water.
If the airflow is not sufficient, the electrical coil will not start. The minimum speed for continuous
operation of the electrical resistances is 300 RPM.
BALI 60
BALI 90
Input power (W)
80
362
Intensity (A)
0.35
1.57