AirPac COOLIT 1000 Operation manual

Manual is about: Portable 7500 BTU

Summary of COOLIT 1000

  • Page 1

    Airpac, incorporated airpac technology park 888 shenandoah shores road front royal, virginia 22630 u.S.A. Toll free 888-324-7722 web: airpacinc.Com email: coolit@airpacinc.Com © 1999 airpac, incorporated printed in u.S.A. Manual cit119..Instr instructions for installation, operation & maintenance op...

  • Page 3

    Airpac warrants to its authorized distributor, each new coolit 1000 to be free from defects in material and workmanship for a period of one (1) year from date of purchase. Limitations: this warranty shall not apply to nor include any of the following: 1. Any repair or replacement required as a resul...

  • Page 4

    Forward thank you for purchasing the airpac coolit 1000 portable air conditioner. This manual describes the unit features and explains how to set-up and operate the coolit 1000 . Preventative maintenance procedures are outlined and a trouble-shooting guide is provi ded for your reference. Please rea...

  • Page 5

    28 trouble shooting guide problem cause solution unit does not work unit not plugged in. Plug in power cord. Main power off. Check fuse or circuit breaker. Water tank full. Empty water tank. Poor cooling performance wrong function mode selected. Set in correct function mode. Condenser air exhaust or...

  • Page 6

    The versatility of the coolit 1000 makes it adaptable for cooling various applications. The coolit 1000 is designed to automatically adjust room temperature, reduce moisture and filter room air. The coolit 1000 is manufactured with quality materials and is designed to give you many years of reliable...

  • Page 7

    Parts diagram 19 26 the first step in preparing the coolit 1000 for installation is to run through this check list to ensure you have all the pieces necessary for your installation. Your shipment consists of two boxes: 1. Coolit 1000 unit box contains: coolit 1000 (item 1) 2. Coolit 1000 accessory b...

  • Page 8

    All coolit 1000 units are shipped in sturdy packaging reinforced with foam panels and covered with cardboard cartons. The accessory items for the standard exhaust kit are shipped in a separate box at the same time the unit is shipped. Both boxes should arrive together but there is a possibility that...

  • Page 9

    Coolit 1000 cooling a small lan and telecommunications closet. 24 cooling capacity 7,500 btu/h power source 115 v 60 hz rated current 8.5 amps power input 950 watts compressor type rotary air flow 100 low / 180 hi cfm dehumidifier value .26 gal/hour sound level 52 db physical dimensions 14”w x 14.5”...

  • Page 10

    Your new coolit 1000 unit has passed a double quality assurance program; once before leaving the factory and again before leaving the regional warehouse. If you find shipping damage please contact the point of purchase immediately. Do not operate the unit. Important: after unpacking your unit and in...

  • Page 11

    6. Read instructions packed with the pump for piping the discharge line. 7. The pump supplied with your coolit 1000 unit may have two wires coming from the top of the pump. These wires are low volt- age safety switch leads and are not used for normal operation of your coolit 1000 . If you would like...

  • Page 12

    Coolit 1000 will shut off after the unit has been operating for the designated number of hours on the timer. To set the timer press the timer/thermometer button twice until the timer indicator light is flashing green. Press the up and down arrow buttons to select the desired number of hours (from 1—...

  • Page 13

    Condensate removal during cooling and dehumidifying operations the condensate will flow into the water tank. The condensate can be removed from the tank by manually emptying the tank, gravity drain or with a condensate pump. Manual tank draining 1. Th e tank full indicator will flash and you will he...

  • Page 14

    10—12 inches. Put the ceiling adapter into the ceiling tile grid. Make sure the ceiling adapter is positioned properly in the ceiling grid and cannot fall out. There should be at least 12— 15” of open space above the ceiling adapter outlet so ex- haust air is not blocked. For permanent installation ...

  • Page 15

    Power requirements the coolit 1000 has a nema 5-15 plug and operates on 115 volts, 60 cycle electrical outlet. Do not bend the metal prongs on the plug. If your cord or outlet becomes warm or hot and/or the fuse blows or the breaker switch trips, this may be an indication of an overload on the elect...

  • Page 16

    16 control panel functions power on/off button press once to turn on and press again to turn off. Mode function button three function mode selection: cooling (top), dehumidifying (middle) and fan (bottom). To operate the air conditioner, press the function button and the cooling indicator light (top...