4. START UP / OPERATION
4.01The battery charger will operate anytime
that there is external AC power and the battery is
not 100% charged. The status lights will indicate
that there is external power and the battery’s
condition.
4.02 There are two switches on the right side
that should be set.
4.03 The switch labeled "Battery Type" should
be set to the correct setting based on the compo-
sition of the batteries attached to the inverter.
Use the following table to determine the correct
setting.
BATTERY TYPE SELECTION
SETTING
BATTERY TYPE
A Vented Nickel-Cadium 10 cells
B Vented Lead-Acid (Antimony)
Flooded Electrolyte
C Sealed Lead-Acid Absorbed or
Vented Nickel-Cadium 9 cell
D
Sealed Lead-Acid Gelled
NOTE: Used batteries should be put through 5
charge cycles with the switch set one position
lower (to the right) than desired. Example: Start
a used vented-lead acid battery on the "C"
setting.
4.04 The switch labeled "Battery Size"
should be set to the correct setting based on the
total amp hour capacity of the batteries attached
to the inverter. Use the following table to
determine correct setting.
BATTERY CAPACITY SELECTOR
SETTING AMP HOUR CAPACITY
A
Over 600
B
600 - 400
C
400 - 200
D
Less than 200
4.05 To operate the U.P.S., turn the On/
Off switch to “ON”. Assure that the output breakers
are reset. If a remote switch is used, the inverter is
turned “On” or “Off” by the remote switch.
BATTERY CHARGER RATING
U.P.S. Input Current Output Current
Model @ 120VAC, 60Hz @ 24VDC
24/2400N Up to 20 Amp AC 40 Amp DC
24/4800N Up to 40 Amp AC 105 Amp DC
5. CUSTOMER SERVICE
TROUBLESHOOTING
5.01 Dimensions offers free phone consulta-
tion concerning installation or troubleshooting. Call
the Customer Service Department at:
1-800-553-6418 or 651-653-7000
fax: 1-651-653-7600
e-mail: inverterinfo@Airpax.net
5.02 If the U.P.S. fails to operate, use the
following troubleshooting procedure.
5.02.1 Connect a 100 watt light bulb to the
inverter output.
5.02.2 Make sure that the U.P.S. is turned
“On”, and the circuit breakers are reset.
5.02.3 Check the connection to the remote
switch, if used. +24VDC must be present at the
violet wire for the unit to operate. If not, check any
fuses in the remote switch circuit.
5.02.4 Observe the fault indicating lights on
the front of the inverter.