Airpax Dimensions ADI-36/3200D Owner's Manual - page 5
ment and that the fan is not blocked.
5.03 Call Airpax Dimensions, Inc. for technical
assistance and/or a return authorization number
if the above steps are completed and the inverter
will still not operate satisfactorily.
5. TROUBLESHOOTING
5.01 Airpax Dimensions offers free phone
consultation concerning installation or trouble-
shooting. Call the Customer Service Department
at:
1-651-653-7000 or 1-800-553-6418
Fax: 1-651-653-7600
e-mail: inverterinfo@Airpax.net
NOTE: Since the inverter has a quasi-sine
waveform, a TRUE RMS volt meter is required for
an accurate reading. Other volt meters that use
averaging circuitry will give false readings.
5.02 If the inverter fails to operate, use the
following troubleshooting procedure.
5.02.1 Connect a 100 watt light bulb to the
inverter output.
5.02.2 Make sure that the inverter is
turned “On”, and the circuit breakers are reset.
5.02.3 Check the connection to the remote
switch, if used. The remote switch wire leads in
the wiring compartment should be connected
together if not used.
5.02.4 Observe the fault indicating lights
on the front of the inverter.
a) The Low input voltage light indicates a low
battery condition. Switch the inverter “Off” for 5
seconds, then “On” again. The light coming on
again indicates a fault in the battery wiring,
battery capacity and voltage or the line fuse.
b) The Overload light indicates an output wiring
short circuit or a load that is too large for the
power rating of the inverter. Switch the inverter
“Off”, remove the short circuit or excessive load
from the output, then switch the inverter back
“On”.
c) The High temperature light indicates the
inverter has overheated. The unit will automati-
cally turn back on when it has cooled to 40
0
C.
Verify that the inverter is not in a closed compart-
Page 5