    Auber instruments www.Auberins.Com 2016.05 p1/8 syl-2342 pid temperature controller instruction manual version 5.3 (may 2016) caution this controller is intended to control equipment under normal operating conditions. If failure or malfunction of the controller may lead to abnormal operating conditi...

  • Page 2

    Auber instruments www.Auberins.Com 2016.05 p2/8 3.3 control output connection the relay output of the controller syl-2342 can be used to turn on a contactor or a solenoid valve. It can drive a small heater directly if the heater draws less than 10a when connected to 120v ac power source. For applica...

  • Page 3

    Auber instruments www.Auberins.Com 2016.05 p3/8 set pv sv 2s set set set set set set set alm1 process high alarm hy-1 9 9 9 9 hy-1 deviation high alarm hy-2 9 9 9 9 hy-2 deviation low alarm hy 0 . 3 hy hysteresis band at 3 at control mode i 1 0 0 0 i integral time p 5 0 0 p proportional constant set...

  • Page 4

    Auber instruments www.Auberins.Com 2016.05 p4/8 the things you should know about alarms 1) absolute alarm and deviation alarm high (or low) limit absolute alarm is set by the specific temperatures that the alarm will be on. Deviation high (or low) alarm is set by how many degrees above (or below) th...

  • Page 5

    Auber instruments www.Auberins.Com 2016.05 p5/8 pv sv sv-hy 100 97 relay on when heating, at=0 if pv (sv-hy), relay on if pv (sv+hy), relay off (sv=100, hy=3) figure 5. On/off control mode. Sv+hy 103 4.5.3. Manual mode manual mode allows the user to control the output as a percentage of the total he...

  • Page 6

    Auber instruments www.Auberins.Com 2016.05 p6/8 alarm, and not show the alarm type in the lower display window, set a = 1, b = 0, c = 0, d = 0, and e = 1. Parameter “al-p” should be configured to: al-p = 1x1 + 0x2 + 0x4 + 0x8 + 1x16 = 17 (this is the factory default setting) note: unlike controllers...

  • Page 7

    Auber instruments www.Auberins.Com 2016.05 p7/8 5.3 controlling a 24v valve tc n 1 13 14 6 2 3 4 5 7 8 9 10 l 120vac fuse syl-2342 + - s 24vac solenoid valve figure 8. Syl-2342 or syl-2342p with thermocouple input. This is a typical wiring set up for a 24v gas valve, hot water valve, or a contactor ...

  • Page 8

    Auber instruments www.Auberins.Com 2016.05 p8/8 quick guide for syl-2342, 2352 1. Wiring 1) power to the controller. Connect the 85-260v ac power to terminals 9 and 10. 2) control output connection. Connect terminals 7 and 8 for output. 3) sensor connection. For thermocouples, connect the positive w...