Bacharach MGD-100 Installation And Operation Manual

Manual is about: Gas Detector and Controllers

Summary of MGD-100

  • Page 1

    Gas detector and controllers installation and operation manual instruction 6109-9000 revision 4 – june 2014 product leadership • training • service • reliability.

  • Page 2

    Mgd-100 manual 2 6109-9000 rev 4 warranty policy bacharach, inc. Warrants this instrument, excluding sensors, to be free from defects in materials and workmanship for a period of one year from the date of purchase by the original owner. The sensors have a warranty period of one year from the date of...

  • Page 3

    Mgd-100 manual 6109-9000 rev 4 3 performing all needed repairs to restore the instrument to full operating condition. Prior to shipping equipment to bacharach, contact our office for an rma # (returned merchandise authorization). All returned goods must be accompanied with an rma number. Pack the eq...

  • Page 4: Table Of Contents

    Mgd-100 manual 4 6109-9000 rev 4 table of contents section 1. Overview ................................................................................ 5 1.1. General information ................................................................................ 5 1.2. Technical specifications ...........

  • Page 5: Section 1.  Overview

    Mgd-100 manual 6109-9000 rev 4 5 section 1. Overview 1.1. General information the mgd-100 is the ideal gas detection solution for installations requiring a quality and affordable stand-alone gas detector. It consists of 1 to 6 remote gas sensors connected to and powered by a controller. The controll...

  • Page 6: (Single Level Alarm)

    Mgd-100 manual 6 6109-9000 rev 4 figure 1. Mgd-100 1- and 2-channel controller pcb (single level alarm) figure 2. Mgd-100 1- and 2-channel controller pcb (dual level alarm).

  • Page 7: (Single Level Alarm)

    Mgd-100 manual 6109-9000 rev 4 7 figure 3. Mgd-100 4- and 6-channel controller pcb (single level alarm).

  • Page 8: (Dual Level Alarm)

    Mgd-100 manual 8 6109-9000 rev 4 figure 4. Mgd-100 4- and 6-channel controller pcb (dual level alarm).

  • Page 9

    Mgd-100 manual 6109-9000 rev 4 9 figure 5. Examples mgd-100 pcbs.

  • Page 10

    Mgd-100 manual 10 6109-9000 rev 4 1.2. Technical specifications specification description power supply 100 - 230 vac 50 - 60 hz, or 12 vdc (specified at time of order) alarm silence key switch alarm delay preset: 25 sec (low), 30 sec (high) power monitoring led green alarm relay(s) 10 a, 120v/230v w...

  • Page 11

    Mgd-100 manual 6109-9000 rev 4 11 specification description 1- and 2-chan systems 4- and 6-chan systems std. Enclosure ratings mgd: ip41 controller: ip51 mgd: ip41 controller: ip51 dimensions and weight: controller 8.4” x 4.1” x 3.15” 214 x 105 x 80 mm 2.2 lbs / 1.0 kg 10.3” x 10.4” x 303” 262 x 265...

  • Page 12

    Mgd-100 manual 12 6109-9000 rev 4 supported cfm and duct sizes for the duct mount housing units duct size inches 12 x 12 12 x 24 18 x 18 24 x 24 24 round feet 1 x 1 1 x 2 1.5 x 1.5 2 x 2 pi x 1 x 1 area (ft 2 ) 1 2 2.25 4 3.14 cfm ft/min (based on cfm and duct size) 2800 2800 n/a n/a n/a n/a 3000 30...

  • Page 13: 2.1.  Installation Warnings

    Mgd-100 manual 6109-9000 rev 4 13 section 2. Placing sensors 2.1. Installation warnings note: this instrument can be equipped with a semiconductor sensor for the detection of refrigerant, combustible and voc gases. Semiconductor sensors are not gas specific and respond to a variety of other gases in...

  • Page 14

    Mgd-100 manual 14 6109-9000 rev 4 avoid routing sensor cabling outside of premises, or between buildings via overhead cables. Also, sensor wiring should be kept to a minimum of 20 in (500mm) from the main power supply and telephone cables. When connecting the main power supply and/or sensor cables e...

  • Page 15: 2.3.  Machinery Rooms

    Mgd-100 manual 6109-9000 rev 4 15 2.3. Machinery rooms there is no absolute rule in determining the number of sensors and their locations. However, a number of simple guidelines will help to make a decision. Sensors monitor a point as opposed to an area. If the gas leak does not reach the sensor the...

  • Page 16: 2.4.  Refrigerated Spaces

    Mgd-100 manual 16 6109-9000 rev 4 otherwise, a gas leak might pass by in a high-speed jet and not be detected by the sensor. • make sure that pits, stairwells and trenches are monitored since they may fill with stagnant pockets of gas. • if a pressure relief vent (prv) pipe is fitted to the system, ...

  • Page 17

    Mgd-100 manual 6109-9000 rev 4 17 • with air-cooled chillers or air-cooled condensers with non- enclosed condenser sections it is difficult to effectively monitor leaks in the coil sections. With some designs it will be possible using an airflow sensor to monitor airflow to the start–up fans in the ...

  • Page 18

    Mgd-100 manual 18 6109-9000 rev 4 section 3. Housing dimensions figure 6. Mgd-100 standard housing.

  • Page 19

    Mgd-100 manual 6109-9000 rev 4 19 figure 7. Mgd-100 exd housing figure 8. Mgd-100 ip66 housing (with splash guard).

  • Page 20: Mount

    Mgd-100 manual 20 6109-9000 rev 4 figure 9. Mgd-100 ip66 housing with remote sensor figure 10. Mgs-100 ip66 housing with airflow duct mount see figure 8 for mounting locations. Cut out in duct for pitot 22mm.

  • Page 21

    Mgd-100 manual 6109-9000 rev 4 21 figure 11. 4- & 6-sensor controller housing.

  • Page 22

    Mgd-100 manual 22 6109-9000 rev 4 figure 12. 1- to 2-sensor controller housing.

  • Page 23: 4.1.  Wiring Mgd-100S

    Mgd-100 manual 6109-9000 rev 4 23 section 4. Wiring instructions 4.1. Wiring mgd-100s step wiring mgd-100s 1 connect a 4-conductor cable (18 awg recommended) to a terminal block on the mgd-100 controller (cn1, cn2, etc). 2 route the cable to an mgd-100. 3 for standard (ip41) mgd-100 housings, remove...

  • Page 24: 4.3.  Dc Output

    Mgd-100 manual 24 6109-9000 rev 4 note: you may use different cables and longer distances provided the corresponding resistance shown above is not exceeded. 4.2. External audible alarm note: this section applies to the external audible alarm (4-6 channel systems only). Step wiring the external audib...

  • Page 25: 4.4.  Relays

    Mgd-100 manual 6109-9000 rev 4 25 4.4. Relays all relay outputs are labeled high, low and fault on the silkscreen. Connect leads to terminal block for common (com) and n/o and/or n/c connections as required. Note that relays are rated as 10a @ 120/230 vac. Note: n/o (normally open) and n/c (normally...

  • Page 26: Diagram

    Mgd-100 manual 26 6109-9000 rev 4 figure 13. 1- & 2-sensor, one-alarm installation diagram.

  • Page 27: Diagram

    Mgd-100 manual 6109-9000 rev 4 27 figure 14. 1- & 2-sensor, two-alarm installation diagram.

  • Page 28

    Mgd-100 manual 28 6109-9000 rev 4 figure 15. 4- & 6-sensor, one-alarm installation.

  • Page 29

    Mgd-100 manual 6109-9000 rev 4 29 figure 16. 4- & 6-sensor, two-alarm installation.

  • Page 30

    Mgd-100 manual 30 6109-9000 rev 4 section 5. Operation and stabilization when power to the unit is switched on, the green led is illuminated, and then there is a 3-minute delay before the system activates. This allows the sensors to warm up to the correct temperature for gas detection. When a unit h...

  • Page 31

    Mgd-100 manual 6109-9000 rev 4 31 operation state description idle only the green light on the panel is on. No gas is present. Power interrupted if the green light is off, power to the unit has been interrupted. Refer to section 7. Alarm conditions one-alarm units: one or more red lights on the pane...

  • Page 32: 6.1.  Introduction

    Mgd-100 manual 32 6109-9000 rev 4 section 6. Functional tests and calibration 6.1. Introduction to comply with the requirements of en378 and the european f-gas regulation, sensors must be tested annually. However, local regulations may specify the nature and frequency of this test. Caution: check lo...

  • Page 33

    Mgd-100 manual 6109-9000 rev 4 33 important: before testing the sensors on-site, the mgd- 100 must have been powered up and allowed to stabilize for at least 24 hours. See section 5. Important: failure to test or calibrate the unit in accordance with applicable instructions and with industry guideli...

  • Page 34: 6.2.  Electrical Reset

    Mgd-100 manual 34 6109-9000 rev 4 caution: before you carry out the bump test or calibration: • advise occupants, plant operators, and supervisors. • check if the mgd-100 is connected to external systems such as sprinkler systems, plant shut down, external sirens and beacons, ventilation, etc. And d...

  • Page 35: 6.3.  Bump Testing

    Mgd-100 manual 6109-9000 rev 4 35 6.3. Bump testing after installation the units should be bump tested. Expose the sensors to test gas ampoules (nh 3 , co 2 , etc.) or test cylinder (appropriate to the installation). The gas is heavier than air and should fall into the sensor, putting the system int...

  • Page 36

    Mgd-100 manual 36 6109-9000 rev 4 figure 17. Gas cylinder and test hardware note: if the bump test is unsuccessful, perform a calibration as described later in this manual. Important: after a semiconductor sensor is exposed to a substantial gas leak, the sensor should be checked and replaced if nece...

  • Page 37

    Mgd-100 manual 6109-9000 rev 4 37 figure 18. Gas ampoules for bump testing step bump testing using gas ampoules 1 make sure that both the ampoules and the calibration beaker are clean and dry. 2 unscrew the beaker wing nut and place the ampoule so that it sits in the base of the beaker (see figure 1...

  • Page 38: 6.4.  Calibration Overview

    Mgd-100 manual 38 6109-9000 rev 4 6.4. Calibration overview to comply with the requirements of en378 and the european f-gas regulation, sensors must be tested annually. However, local regulations may specify the nature and frequency of this test. Caution: check local regulations on calibration or te...

  • Page 39

    Mgd-100 manual 6109-9000 rev 4 39 step sensor board exchange 4 fit the new pre-calibrated sensor and reconnect the cable in the correct color sequence at positions 1,2,3 and 4. 5 power on the unit and allow to stabilize for 15 minutes (minimum). 6 check voltage readings on positions 1,2,3 and 4 (see...

  • Page 40

    Mgd-100 manual 40 6109-9000 rev 4 step adjusting the low alarm threshold voltage (atv) 2 monitor the voltage between tp5 (0v) & tp4 (+ve)/0v and vs on ir units. 3 apply the low concentration calibration gas to the sensor and wait until the sensor output signal stabilizes. Record this voltage. 4 adju...

  • Page 41

    Mgd-100 manual 6109-9000 rev 4 41 section 7. Troubleshooting symptom possible cause(s) no lights displayed on panel • power failure (check supply) • tripped circuit breaker or blown fuse on electrical supply • blown fuse at the electrical supply on the controller pcb board red light is on, but no al...

  • Page 42

    Mgd-100 manual 42 6109-9000 rev 4 • connect voltmeter and monitor voltage between tp5 (0v) and tp4 (+ve). For ir, monitor between 0v and vs. Table 1. Connections correct values position number at the sensor controller 1 12v power supply +10v 2 sensor output, these are approximate, typical internal r...

  • Page 43: Eclaration

    Mgd-100 manual 6109-9000 rev 4 43 d eclaration of c onformity the manufacturer of the products covered by this declaration: bacharach, inc. 621 hunt valley circle new kensington, pa 15068 year(s) conformity is declared: 2014 (iec/en61010), 2011 (en61326/en55011) product(s): mgd model(s): mgd-100 the...

  • Page 44

    Mgd-100 manual 44 6109-9000 rev 4 world headquarters 621 hunt valley circle, new kensington, pennsylvania 15068 phone: 724-334-5000 • toll free: 1-800-736-4666 • fax: 724-334-5001 website: www.Mybacharach.Com • e-mail: help@mybacharach.Com.