1) Press ▲ key and theflashingfigurewillchange,presskey
again until obtaining 3. Press ◄toconfirmtheflashing3 that
becomesfixed.Itisnowpossibletoeditthefigurefurtherto
theleftthatbeginstoflash.Press▲ key in order to change
thefigurenowflashingto3andthen◄inordertoconfirmthis
valueandmovetothefigurefurthertotheleft.Thisoperation
must be repeated until obtaining the number 3 four times =
3333. Press ►key to confirm the PASSword. We are now
in a position to configure or reconfigure the controller.
For one electric preheater you need to set n° 1045.
For two or more preheaters you need to set n° 1046.
2) At this point go through the procedure illustrated in point 1 to
set n° 1045 or n° 1046.
3) We can now set parameters (control values) as detailed in the
previous table.
4) Press F key, repeatedly if necessary, until the wording SP
appears. Press ►keyandthefigurefurthesttotherightwill
starttoflash.Nextproceedasperpoint1inordertoenterthe
requiredvalue(130°C).Havingsetthedesiredtemperature,
press ►toconfirmandthetemperaturesettingwillappearat
the bottom of the display.
5) It is now necessary to set value SP.2. Press F key repeatedly
until wording Par appears. Press ►keytoconfirmandthe
wording SP.2 will appear. Proceed as per point 1 in order to
set value given in the table for SP.2 = 110 °C.
6) Press F key and the wording Pb will appear. Proceed as per
point1inordertosettablevalue=6.Press►toconfirm
this value and the wording t.i will appear.
7) Proceedaspreviouslydescribedinordertosetvaluet.i=4as
pertable.Press►toconfirmthisvalueandmovetot.d.
8) Proceedaspreviouslydescribedinordertosetvaluet.d.=0.8
aspertable.Press►toconfirmthisvalueandmovetot.c.
9) Proceedaspreviouslydescribedinordertosetvaluet.c.=10
aspertable.Press►toconfirmthisvalueandmovetoYh.
10) ProceedaspreviouslydescribedinordertosetvalueYh=100
aspertable.Confirmthisvaluebypressing►andthedisplay
will return to Pb.
11) Press F key in order to move to Hy2. Proceed as per point 1
andsetvalueHy2=1.Press►keytoconfirmandremainat
Hy2.
12) Press F key in order to move to SPL 1. Proceed as before and
setSPL1=100°C.Press►toconfirmandmovetoSPLh.
SetSPLh=250°Cintheusualmanner.Press►toconfirm
and move to SLOP.
13) ProceedasbeforeinordertosetSLOP=0andconfirmwith
► key.Thecontrollerisnowconfiguredandcapableoffun-
ctioning using set values. Should it be necessary to modify
any temperature setting, proceed as previously described at
specificpoints4forSPand5forSP2.
!
The controller is supplied with the instructions given by the ma-
nufacturerASCONthatcontaintherespective“flowdiagram”.
14) Proceedasfollowsifwishingtocheckthedefaultconfiguration
setbyus(1045or1046):
Press F key repeatedly until the wording ConF appears.
Press►keyonceandtheconfigurationsetwillappear(1045
or 1046 - Conf.). From this position, if wishing to alter the
configurationpress►onceandthewording9999-PASS
willappear(9furthesttotherightflashing).Itisnecessary
toenterthePASSword(=3333)asdescribedatpoint1.
Itisnowpossibletochangetheconfigurationifdesiredby
following the instructions of point 1.