Bard WG3S2-A Installation Instructions Manual

Manual is about: WG Series

Summary of WG3S2-A

  • Page 1

    Manual 2100-587b page 1 of 59 wg - series combination gas/electric wall-mount models: wg3s2-a wg3s2-b wg3s2-c wg4s2-a wg4s2-b wg4s2-c wg5s2-a wg5s2-b wg5s2-c manual no.: 2100-587b supersedes: 2100-587a file: volume iii, tab 20 date: 09-20-13 bard manufacturing company, inc. Bryan, ohio 43506 since 1...

  • Page 2: Contents

    Manual 2100-587b page 2 of 59 contents getting other information and publications .............. 4 wg series model nomenclature ............................... 5 ventilation options .................................................... 5 air conditioning module options ..................................

  • Page 3: Contents

    Manual 2100-587b page 3 of 59 contents figures figure 1 unit dimensions ..................................... 8 figure 2a mounting instructions – wg3s2 ........... 11 figure 2b mounting instructions–wg4s2 & wg5s2 .... 12 figure 3 combustible clearance ........................ 13 figure 4 wall mounti...

  • Page 4

    Manual 2100-587b page 4 of 59 getting other information and publications for more information, contact these publishers: acca air conditioning contractors of america 1712 new hampshire avenue, nw washington, dc 20009 telephone: (202) 483-9370 ansi american national standards institute 11 west street...

  • Page 5

    Manual 2100-587b page 5 of 59 wg 4 s 2 – a x c x x x x x x wall mount gas/electric general model number nomenclature 1 low ambient control is required with economizer for low temperature compressor operation. Ventilation options s l e d o m s 5 g w , s 4 g w , s 3 g w n o i t p i r c s e d d e l l a...

  • Page 6: Caution

    Manual 2100-587b page 6 of 59 air conditioning module options std = standard equipment. 1 ccm compressor control module has adjustable 30 second to 5 minute delay-on-break timer. On initial power up, or any time the power is interrupted, the delay-on-make will be 2 minutes plus 10% of the delay-on-b...

  • Page 7

    Manual 2100-587b page 7 of 59 * 75 degree c copper wire size ** maximum time delay fuse or hacr type circuit breaker table 1 specifications sl e d o ma - 2 s 3 g wb - 2 s 3 g wc - 2 s 3 g wa - 2 s 4 g wb - 2 s 4 g wc - 2 s 4 g wa - 2 s 5 g wb - 2 s 5 g wc - 2 s 5 g w z h 0 6 - g nit a r l a ci rt c ...

  • Page 8

    Manual 2100-587b page 8 of 59 m g n p d a ff gg hh y z t c k j bb dd r w s s s s cc f b aa x u i v s b ee o e l ii q h fi lt e r ser v ic e d oor g a s pa n el v e n t opt ion c ir c u it br ea ker / fron t r e t u r n open in g c o nde ns e r ba c k su pply open in g di s c o nne c t a c c e s s ri...

  • Page 9: Warning

    Manual 2100-587b page 9 of 59 a one-inch clearance to combustible material for the first three feet of duct attached to the outlet air frame is required. See wall mounting instructions and figures 2, 2a, 3 and 3a for further details. Ducts through the walls must be insulated and all joints taped or ...

  • Page 10: Caution

    Manual 2100-587b page 10 of 59 5. Transportation damage all units are packed securely in shipping container. All units should be carefully inspected upon arrival for damage. In the event of damage, the consignee should: 1. Note on delivery receipt of any damage to container. 2. Notify carrier prompt...

  • Page 11

    Manual 2100-587b page 11 of 59 figure 2a mounting instructions for wg3s2.

  • Page 12

    Manual 2100-587b page 12 of 59 figure 2b mounting instructions for wg4s2 and wg5s2.

  • Page 13: Warning

    Manual 2100-587b page 13 of 59 figure 3 combustible clearance warning a minimum of one (1) inch clearance must be maintained between the supply air duct and combustible materials. This is required for the first three (3) feet of ducting. It is important to insure that the one (1) inch minimum spacin...

  • Page 14

    Manual 2100-587b page 14 of 59 figure 4 wall mounting instructions figure 5 wall mounting instructions.

  • Page 15

    Manual 2100-587b page 15 of 59 figure 6 common wall mounting installations.

  • Page 16: Warning

    Manual 2100-587b page 16 of 59 9. Clearances minimum clearances, as specified in table 2, must be maintained from adjacent structures to provide adequate fire protection, adequate combustion air, and room for service personnel. While minimum clearances are acceptable for safety reasons, they may not...

  • Page 17: Caution

    Manual 2100-587b page 17 of 59 10. Vent terminal and combustion air inlet hood the vent terminal is shipped in the burner compartment. See figure 7. Remove the two shipping screws and separate the two-piece assembly. Install the vent terminal by using the four screws provided. Make sure gasket is in...

  • Page 18

    Manual 2100-587b page 18 of 59 12. Vent resizing instructions when an existing furnace is removed from a venting system servicing other appliances, the venting system is likely to be too large to properly vent the remaining attached appliances. The following steps shall be followed with each of the ...

  • Page 19: Warning

    Manual 2100-587b page 19 of 59 electrical grounding when installed, the furnace must be electrically grounded in accordance with local codes or in the absence of local codes, with the national electrical code, ansi/nfpa 70, or canadian electrical code, csa22.1, latest edition. Use a copper wire from...

  • Page 20

    Manual 2100-587b page 20 of 59 note: the voltage should be measured at the field power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition). P a t e g n a r 0 4 2 6 0 2 – 3 5 2 8 0 2 7 8 1 – 0 2 2 17. Thermostats 16. Wiring – low voltage wi...

  • Page 21: Unit Control Panel

    Manual 2100-587b page 21 of 59 g part #8403-058 thermostat low voltage wiring - no ventilation package 1 o/b y thermostat r unit control panel block w2 r c w1 w2 e y2 y1 2 3 r c w y2 rc w2 y g l y1 d/yo y2 a w1/e c g terminal part #8403-060 thermostat subbase factory installed jumper unit 24v mis-23...

  • Page 22: Thermostat Subbase

    Manual 2100-587b page 22 of 59 red must install jumper for 8403-058 or other thermostat that does not black y (must be configured low voltage wiring - multi-position commercial room ventilator 1 purple orange for heat/cool) brown install if you require ventilation anytime blower is on. Block r c w1 ...

  • Page 23: Unit Control Panel

    Manual 2100-587b page 23 of 59 w2 orange thermostat thermistor from low voltage wiring - eifm economizer 1 wgseifm-5 red o/b g red unit control panel block r c w1 w2 e y2 y1 2 3 r c w y2 rc w2 y g l y1 d/yo y2 a plug y unit 24v terminal part #8403-058 w1/e c r thermostat thermostat subbase g factory...

  • Page 24

    Manual 2100-587b page 24 of 59 mis-2434 c wgserv-*5 r have occupancy output. Thermostat panel y control install if you require ventilation anytime blower is on. Block r c w1 a w2 e y2 y1 2 3 r c w y2 rc w2 y g l y1 d/yo low voltage wiring - wgserv-*5 energy recovery ventilator 1 g unit control y2 a ...

  • Page 25

    Manual 2100-587b page 25 of 59 figure 11 gas pipe connection.

  • Page 26

    Manual 2100-587b page 26 of 59 18. Gas supply and piping general recommendations 1. Be sure the gas line complies with the local codes and ordinances, or in their absence with the national fuel gas code, ansi z223.1, or natural gas installation code, can/cga b149.1, or propane installation code b149...

  • Page 27: Warning

    Manual 2100-587b page 27 of 59 19. Manifold pressure adjustment you will need a 0 to 15 inch water manometer with 0.1 inch resolution and a 1/8" npt manual shut off valve to measure actual manifold pressure. Depending on your local gas heating value and elevation, you may need to adjust manifold pre...

  • Page 28: Warning

    Manual 2100-587b page 28 of 59 natural gas input rate natural gas heating value (btu/cu. Ft.) can vary significantly. Before starting natural gas input check, obtain gas heating value at your location from local supplier. You will need a stopwatch to measure actual gas input. 1. Gas supply pressure ...

  • Page 29

    Manual 2100-587b page 29 of 59 21. Standard orifice sizing and high altitude derate this furnace is shipped with fixed gas orifices for use with natural gas and sized for 1000 btu/cubic foot gas. Make sure actual gas input does not exceed rating plate input. You may need to change orifices to get co...

  • Page 30

    Manual 2100-587b page 30 of 59 all other orifice sizes shown are available as individual items. See orifice tables below for part numbers and number required. Table 8 natural gas orifice tables for models wg3s, wg4s and wg5s y r o t c a f d r a d n a t s t u p n i * t a e h s a g e u l a v . T f . U...

  • Page 31: Warning

    Manual 2100-587b page 31 of 59 23. Measuring air temperature rise air temperature rise (supply air temperature minus return air temperature) must be within allowable air temperature rise range specified on furnace rating plate and in table 1. You will need 2 thermometers with 1 degree resolution cap...

  • Page 32

    Manual 2100-587b page 32 of 59 24. Filters a 2" thick throwaway filter is supplied with each unit. This filter is installed by removing the filter access panel. (see figure 13.) replacement filters are available through your dealer. 25. Compressor control module the compressor control module is stan...

  • Page 33

    Manual 2100-587b page 33 of 59 alarm output alarm terminal is output connection for applications where alarm signal is desired. This terminal is powered whenever compressor is locked out due to hpc or lpc sequences as described. Note: both high and low pressure switch controls are inherently automat...

  • Page 34

    Manual 2100-587b page 34 of 59 26. Lighting and shutdown instructions figure 14 instruction label.

  • Page 35: Caution

    Manual 2100-587b page 35 of 59 27. Service agency procedures main burner observe the main burners in operation. The flame should be mostly “blue” with possibly a little orange (not yellow) at the tips of the flame. The flames should be in the center of the heat exchanger tubes and not impinging on t...

  • Page 36: Warning

    Manual 2100-587b page 36 of 59 routine maintenance 1. Air filters – check the condition at least monthly when the unit is in use, and replace as necessary. 2. Lubrication requirements – the indoor circulating air blower motor and outdoor circulating air fan motor are permanently lubricated and requi...

  • Page 37

    Manual 2100-587b page 37 of 59 30. Sequence of operation – heating on a call for heat from the thermostat, the induced draft blower is energized. Once sufficient draft is established, the pressure switch contacts close and the ignition system is energized. The direct spark ignitor will be energized ...

  • Page 38

    Manual 2100-587b page 38 of 59 32. Indoor blower operation the indoor blower motor is a constant cfm variable speed direct drive motor. The motor is programmed to respond to individual thermostatic inputs that will determine the speed/airflow at which the motor operates. The motor software maintains...

  • Page 39

    Manual 2100-587b page 39 of 59 table 10 integrated furnace and blower control operation l o r t n o c e c n e u q e s n o i t i n g i e c r u o s n o i t i n g i i s d c a v 4 2 g n i s n e s e m a l f e t o m e r s g n i m i t - - - - - - - - - - - - - - e g r u p e r p e g r u p t s o p e g r u p ...

  • Page 40: Start Up

    Manual 2100-587b page 40 of 59 start up these units require r-410a refrigerant & polyol ester oil. Application: 1. Use separate service and manufacturing equipment to avoid cross contamination of oil and refrigerants. 2. Use recovery equipment rated for r-410a refrigerant. 3. Use manifold gauges rat...

  • Page 41

    Manual 2100-587b page 41 of 59 three phase scroll compressor start up information scroll compressors, like several other types of compressors, will only compress in one rotational direction. Direction of rotation is not an issue with single phase compressors since they will always start and run in t...

  • Page 42: Troubleshooting

    Manual 2100-587b page 42 of 59 compressor solenoid (see sequence of operation on page 37 for function.) a nominal 24-volt direct current coil activates the internal compressor solenoid. The input control circuit voltage must be 18 to 28 volt ac. The coil power requirement is 20 va. The external elec...

  • Page 43: Troubleshooting  Ecm

    Manual 2100-587b page 43 of 59 troubleshooting ecm ™ motors caution: disconnect power from unit before removing or replacing connectors, or servicing motor. To avoid electric shock from the motor’s capacitors, disconnect power and wait at least 5 minutes before opening motor. Symptom cause/procedure...

  • Page 44: Troubleshooting  Ecm

    Manual 2100-587b page 44 of 59 troubleshooting ecm ™ motors cont’d. Replacing ecm control module to replace the control module for the ge variable-speed indoor blower motor you need to take the following steps: 1. You must have the correct replacement module. The controls are factory programmed for ...

  • Page 45

    Manual 2100-587b page 45 of 59 33. Pressure service ports high and low pressure service ports are installed on all units so that the system operating pressures can be observed. Table 12 outlines expected pressures at various indoor and outdoor temperatures. Low side pressure ± 4 psig high side press...

  • Page 46: * *

    Manual 2100-587b page 46 of 59 35. Low-nox burner assembly “n” suffix models only – u.S. Installations only natural gas models only model numbers designated with an “n” are designed for low nox emissions which comply with all california air quality management district regulations for nitrogen oxide ...

  • Page 47

    Manual 2100-587b page 47 of 59 index wiring diagrams and ladder diagrams . O n l e d o m t u p n i g n i t a e h r e w o p t u p n i m a r g a i d g n i r i w m a r g a i d r e d d a l 2 s 3 g w 0 0 0 , 0 5 1 / 0 6 / 0 3 2 / 8 0 2 a 4 5 1 - 5 8 0 4 5 5 1 - 5 8 0 4 0 0 0 , 5 7 a 6 5 1 - 5 8 0 4 7 5 1...

  • Page 48

    Manual 2100-587b page 48 of 59 wg3s2-a, wg4s2-a, wg5s2-a 208/230/60/1 t2 nc c l2 l3 au x. L1 t1 t3 lp c cc hp c y al r c lp c m in u tes 4 2 3 5 r 1 switch pressure high compressor compressor high speed motor crankcase 16 replaced, it must be replaced with wiring material having a temperature rating...

  • Page 49

    Manual 2100-587b page 49 of 59 wg3s2-a, wg4s2-a, wg5s2-a 208/230/60/1 if option not a wires connect used bard mfg. Co. Bryan, ohio 4085-155 indoor blower motor 14 12 10 6 2 13 3 1 16 pin plug for 15 w1 c heat unused g high voltage optional low voltage factory com contactor 7 line 2 compressor blower...

  • Page 50

    Manual 2100-587b page 50 of 59 wg3s2-a, wg4s2-a, wg5s2-a 208/230/60/1 t2 nc c l2 l3 au x. L1 t1 t3 4 m in u tes lp c c r 5 3 2 compressor compressor high speed motor not used crankcase 16 replaced, it must be replaced with wiring material having a temperature rating of at least 105° c except the ign...

  • Page 51

    Manual 2100-587b page 51 of 59 wg3s2-a, wg4s2-a, wg5s2-a 208/230/60/1 if option not a wires connect used bard mfg. Co. Bryan, ohio 4085-157 indoor blower motor 14 12 10 6 2 13 3 1 16 pin plug for 15 w1 c heat unused g high voltage optional low voltage factory a induced draft terminal y2 contactor co...

  • Page 52

    Manual 2100-587b page 52 of 59 wg3s2-b, wg4s2-b, wg5s2-b 208/230/60/3 bryan, ohio 4085-254 a bard mfg. Co. T2 nc c l2 l3 au x. L1 t1 t3 brown if option not used motor indoor blower 16 pin plug for black blower motor for indoor pin plug black speed 150 135 120 fuse 13 2 6 10 1 3 15 12 14 bl ac k/ w h...

  • Page 53

    Manual 2100-587b page 53 of 59 wg3s2-b, wg4s2-b, wg5s2-b 208/230/60/3 if option not a wires connect used bard mfg. Co. Bryan, ohio 4085-269 indoor blower motor 14 12 10 6 2 13 3 1 16 pin plug for 15 w1 c heat unused g high voltage optional low voltage factory 6 y ladder diagram low vol tage ter m . ...

  • Page 54

    Manual 2100-587b page 54 of 59 wg3s2-b, wg4s2-b, wg5s2-b 208/230/60/3 bryan, ohio 4085-255 a bard mfg. Co. T2 nc c l2 l3 au x. L1 t1 t3 r 5 3 lp c motor lp c 2 4 m inut e s which is 250°c high voltage cable temperature rating of at least 105° c except the ignition cable outdoor fan integrated furnac...

  • Page 55

    Manual 2100-587b page 55 of 59 wg3s2-b, wg4s2-b, wg5s2-b 208/230/60/3 if option not a wires connect used bard mfg. Co. Bryan, ohio 4085-270 indoor blower motor 14 12 10 6 2 13 3 1 16 pin plug for 15 w1 c heat unused g high voltage optional low voltage factory d1 9 l1 c compressor y ladder diagram lo...

  • Page 56

    Manual 2100-587b page 56 of 59 wg3s2-c, wg4s2-c, wg5s2-c 460/60/3 t2 nc c l2 l3 au x. L1 t1 t3 lp c cc hp c y al r c lp c m inut e s 4 2 3 5 r 1 460v 230v fuse step down black motor indoor blower 16 pin plug for blower motor for indoor pin plug bl ac k bl ac k transformer speed 150 135 120 (opt.) 13...

  • Page 57

    Manual 2100-587b page 57 of 59 wg3s2-c, wg4s2-c, wg5s2-c 460/60/3 if option not a wires connect used bard mfg. Co. Bryan, ohio 4085-392 indoor blower motor 14 12 10 6 2 13 3 1 16 pin plug for 15 w1 c heat unused g high voltage optional low voltage factory 2 yo y ladder diagram low vol tage ter m . B...

  • Page 58

    Manual 2100-587b page 58 of 59 wg3s2-c, wg4s2-c, wg5s2-c 460/60/3 t2 nc c l2 l3 au x. L1 t1 t3 lp c cc hp c y al r c lp c m in u tes 4 2 3 5 r 1 6 1 3 2 4 460v 230v switch pressure high compressor compressor high speed motor control 16 replaced, it must be replaced with wiring material having a temp...

  • Page 59

    Manual 2100-587b page 59 of 59 wg3s2-c, wg4s2-c, wg5s2-c 460/60/3 if option not a wires connect used bard mfg. Co. Bryan, ohio 4085-393 indoor blower motor 14 12 10 6 2 13 3 1 16 pin plug for 15 w1 c heat unused g high voltage optional low voltage factory y l1 induced draft ladder diagram low vol ta...