14.1 ALARM RECOVERY
Probe alarms P1”, “P2”, “P3” and “P4” start some seconds after the fault in the related probe; they
automatically stop some seconds after the probe restarts normal operation. Check connections
before replacing the probe.
Temperature alarms “HA”, “LA” “HA2” and “LA2” automatically stop as soon as the temperature
returns to normal values.
Alarms “EA” and “CA” (with i1F=bAL)recover as soon as the digital input is disabled.
Alarm “CA” (with i1F=PAL) recovers only by switching off and on the instrument.
14.2 OTHER MESSAGES
Pon
Keyboard unlocked.
PoF
Keyboard locked
noP
In programming mode: none parameter is present in Pr1
On the display or in dP2, dP3, dP4: the selected probe is nor enabled
15. TECHNICAL DATA
Housing: self extinguishing ABS.
Case: XR70CX frontal 32x74 mm; depth 60mm;
Mounting: XR70CX panel mounting in a 71x29mm panel cut-out
Protection: IP20; Frontal protection: XR70CX IP65
Connections: Screw terminal block
d 2,5 mm
2
wiring.
Power supply: according to the model: 12Vac/dc, ±10%; 24Vac/dc, ±10%; 230Vac
r10%,
50/60Hz, 110Vac
r10%, 50/60Hz
Power absorption: 3VA max
Display: 3 digits, red LED, 14,2 mm high; Inputs: Up to 4 NTC or PTC probes.
Digital input: free voltage contact
Relay outputs: compressor SPST 8(3) A, 250Vac; SPST 16(6)A 250Vac
defrost: SPDT 8(3) A, 250Vac or SPST 16(6)A 250Vac
fan: SPST 5A, 250Vac or SPST 16(6)A 250Vac
aux: SPDT 8(3) A, 250Vac or SPST 16(6)A 250Vac
Data storing: on the non-volatile memory (EEPROM).
Kind of action: 1B; Pollution grade: 2;Software class: A.;
Rated impulsive voltage: 2500V; Overvoltage Category: II
Operating temperature: 0÷60 °C;Storage temperature: -30÷85 °C.
Relative humidity: 20
y85% (no condensing)
Measuring and regulation range: NTC probe: -40÷110°C (-40÷230°F);
PTC probe: -50÷150°C (-58÷302°F)
Resolution: 0,1 °C or 1°C or 1 °F (selectable); Accuracy (ambient temp. 25°C): ±0,7 °C ±1 digit
16. CONNECTIONS
The X-REP output excludes the TTL output.. It’s present in the following codes:
XR70CX- xx2xx, XR70CX –xx3xx;
16.1 XR70CX – 8A OR 16A COMP. RELAY - 230VAC OR 120VAC
NOTE: The
compressor relay is
8(3)A or 16(6)A
according to the
model.
24Vac supply:
connect to the
terminals 5 and 6.
16.2 XR70CX –4 X 16A - 12VAC/DC
17. DEFAULT SETTING VALUES
Labe
Name
Range
°C/°F
Level
Set Set point
LS÷US
-5.0
- - -
Hy Differential
0,1
y25.5°C/ 1y 255°F
2.0
Pr1
LS Minimum set point
-50°C
ySET/-58°FySET
-50.0
Pr2
US Maximum set point
SET
y110°C/ SET y 230°F
110
Pr2
Ot Thermostat probe calibration
-12
y12°C /-120y120°F
0.0
Pr1
P2P Evaporator probe presence
n=not present; Y=pres.
Y
Pr1
OE Evaporator probe calibration
-12
y12°C /-120y120°F
0.0
Pr2
P3P Third probe presence
n=not present; Y=pres.
n
Pr2
O3 Third probe calibration
-12
y12°C /-120y120°F
0
Pr2
P4P Fourth probe presence
n=not present; Y=pres.
n
Pr2
O4 Fourth probe calibration
-12
y12°C /-120y120°F
0
Pr2
Labe
Name
Range
°C/°F
Level
OdS Outputs delay at start up
0÷255 min
0
Pr2
AC Anti-short cycle delay
0
y 50 min
1
Pr1
rtr P1-P2 percentage for regulation
0 ÷ 100 (100=P1 , 0=P2)
100
Pr2
CCt Continuos cycle duration
0.0÷24.0h
0.0
Pr2
CCS Set point for continuous cycle
(-55.0÷150,0°C) (-67÷302°F)
-5
Pr2
COn Compressor ON time with faulty probe
0
y 255 min
15
Pr2
COF Compressor OFF time with faulty probe 0
y 255 min
30
Pr2
CF Temperature measurement unit
°C
y °F
°C
Pr2
rES Resolution
in=integer; dE= dec.point
dE
Pr1
Lod Probe displayed
P1;P2
P1
Pr2
rEd
2
X-REP display
P1 - P2 - P3 - P4 - SEt - dtr
P1
Pr2
dLy Display temperature delay
0 ÷ 20.0 min (10 sec.)
0
Pr2
dtr P1-P2 percentage for disply
1 ÷ 99
50
Pr2
tdF Defrost type
EL=el. heater; in= hot gas
EL
Pr1
dFP Probe selection for defrost termination
nP; P1; P2; P3; P4
P2
Pr2
dtE Defrost termination temperature
-50
y 50 °C
8
Pr1
IdF Interval between defrost cycles
1
y 120 ore
6
Pr1
MdF (Maximum) length for defrost
0
y 255 min
30
Pr1
dSd Start defrost delay
0÷99min
0
Pr2
dFd Displaying during defrost
rt, it, SEt, DEF
it
Pr2
dAd MAX display delay after defrost
0 ÷ 255 min
30
Pr2
Fdt Draining time
0÷120 min
0
Pr2
dPo
First defrost after startup
n=after IdF; y=immed.
n
Pr2
dAF Defrost delay after fast freezing
0 ÷ 23h e 50’
0.0
Pr2
Fnc Fan operating mode
C-n, o-n, C-y, o-Y
o-n
Pr1
Fnd Fan delay after defrost
0÷255min
10
Pr1
Fct Differential of temperature for forced
activation of fans
0÷50°C
10
Pr2
FSt Fan stop temperature
-50÷50°C/-58÷122°F
2
Pr1
Fon Fan on time with compressor off
0÷15 (min.)
0
Pr2
FoF Fan off time with compressor off
0÷15 (min.)
0
Pr2
FAP Probe selection for fan management
nP; P1; P2; P3; P4
P2
Pr2
ALc Temperat. alarms configuration
rE= related to set;
Ab = absolute
Ab
Pr2
ALU MAXIMUM temperature alarm
Set
y110.0°C; Set÷230°F
110
Pr1
ALL Minimum temperature alarm
-50.0°C
ySet/ -58°FySet
-50.0
Pr1
AFH Differential for temperat. alarm recovery
(0,1°C÷25,5°C) (1°F÷45°F)
1
Pr2
ALd Temperature alarm delay
0
y 255 min
15
Pr2
dAO Delay of temperature alarm at start up
0
y 23h e 50’
1.3
Pr2
AP2 Probe for temperat. alarm of condenser
nP; P1; P2; P3; P4
P4
Pr2
AL2 Condenser for low temperat. alarm
(-55 ÷ 150°C) (-67÷ 302°F)
-40
Pr2
AU2 Condenser for high temperat. alarm
(-55 ÷ 150°C) (-67÷ 302°F)
110
Pr2
AH2 Differ. for condenser temp. alar. recovery [0,1°C ÷ 25,5°C] [1°F ÷ 45°F]
5
Pr2
Ad2 Condenser temperature alarm delay
0 ÷ 254 (min.) , 255=nU
15
Pr2
dA2 Delay of cond. temper. alarm at start up
0.0 ÷ 23h 50’
1,3
Pr2
bLL
Compr.
off
for
condenser
low
temperature alarm
n(0) - Y(1)
n
Pr2
AC2
Compr.
off
for
condenser
high
temperature alarm
n(0) - Y(1)
n
Pr2
tbA Alarm relay disabling
n=no; y=yes
y
Pr2
oA3 Fourth relay configuration
ALr = alarm; dEF = do not select
it; Lig =Light; AUS =AUX;
onF=always on; Fan= do not
select it; db = do not select it;
dF2 = do not select it
ALr
Pr2
AoP Alarm relay polarity (oA3=ALr)
oP; cL
cL
Pr2
i1P Digital input polarity
oP=opening;CL=closing
cL
Pr1
i1F Digital input configuration
EAL, bAL, PAL, dor; dEF; Htr, AUS
dor
Pr1
did Digital input alarm delay
0÷255min
15
Pr1
Nps Number of activation of pressure switch
0 ÷15
15
Pr2
odc Compress and fan status when open
door
no; Fan; CPr; F_C
F-c
Pr2
rrd Regulation restart with door open alarm
n – Y
y
Pr2
HES Differential for Energy Saving
(-30°C÷30°C) (-54°F÷54°F)
0
Pr2
PbC Kind of probe
Ptc; ntc
1
Pr2
Adr Serrial address
1÷247
1
Pr2
onF on/off key enabling
nu, oFF; ES
ntc
Pr1
dP1 Room probe display
--
nu
Pr2
dP2 Evaporator probe display
--
--
Pr1
dP3 Third probe display
--
--
Pr1
dP4 Fourth probe display
--
--
Pr1
rSE Valore set operativo
actual set
--
Pr2
rEL Software release
--
--
Pr2
Ptb Map code
--
--
Pr2
2
Only for models XR70CX–xx2xx, XR70CX–xx3xx; XR70CX–xx6xx; XR70CX–xx7xx
Dixell S.p.A. Z.I. Via dell’Industria, 27
32010 Pieve d’Alpago (BL) ITALY
tel. +39 - 0437 - 98 33 - fax +39 - 0437 - 98 93 13
E-mail: dixell@dixell.com - http://www.dixell.com