C&K Systems S802 Installation Manual

Manual is about: SECURIT 802 CONTROL PANEL

Summary of S802

  • Page 1

    Installation manual securit 802 control panel s802.

  • Page 2: Contents

    1 contents warnings 2 standards 2 warranty statement 2 product description 2 available parts 2 intended use 2 specifications 3 processor version 3 power supply 3 keypads 3 general 3 factory defaults 3 installation 4 mounting 4 wiring 4 battery 4 detector circuits 4 l as latch line 4 l as id- 5 inter...

  • Page 3: Warnings

    2 warnings prolonged short circuit of any supply can cause damage to the unit. Take the necessary precautions in not allowing liquids to spill on or into the unit. Standards this unit conforms to ecd 89/336/eec & lvd 73/23/eec. This unit has been tested and has proven to meet all current emission an...

  • Page 4: Specifications

    3 specifications there now follows the specifications of the panel. These include power consumption, panel dimensions etc. Specification for software revision number v1.0 the software revision number is located on the top of the main processor specification power supply mains supply voltage 230 v ac...

  • Page 5: Installation

    4 installation when fitting the panel, make sure to site it somewhere that is not visible from an outside location ( window or door ) and also make sure that the panel is going to be accessible. An ideal location would be a cupboard in a hall or under stairs located close to the main entrance. Ensur...

  • Page 6

    5 detector reset (l+ when programmed for id) some detectors require the removal of power to reset (e.G. Viper plus ® or smoke detectors). The l+ terminal can be programmed to be used as an 'id' output using option 7-4. The l+ terminal should then be used as the negative supply for these devices. The...

  • Page 7: Powering Up

    6 mounting a remote keypad 1) locate the position for your keypad then mark the holes for mounting. 2) make sure the cable is run through the backbox. 3) screw the backbox in the agreed position making sure it is not twisted. Wiring a remote keypad 1) all remote keypads require 6 core cable for thei...

  • Page 8: Programming

    7 if programming is not required simply close any lids that are open and press the # key. This will exit engineering mode. Now refer to the users manual for customer options. If at any time you wish to exit engineering mode, confirm any options you have selected with the * (star) key, then close all...

  • Page 9

    8 sounder duration (sounder ring time) 3-2 (range 3-20 minutes) enter 3-2. This has been preset to a factory default of 15 minutes. A new time may be programmed by entering one key from the following table. Press * to confirm the selection. The accept tone will sound. Enter 1 3 minutes. Led 1 on. En...

  • Page 10

    9 circuit programming 4 (range 2-7) circuits 2 - 7 can be reprogrammed to suit your requirements. Circuit 1 is fixed as a final exit circuit. Circuit 8 has limited options. Enter program zone enter program zone 4 - 2 2 4 - 6 6 4 - 3 3 4 - 7 7 4 - 4 4 4 - 8 8 4 - 5 5 select the circuit you wish to al...

  • Page 11

    10 by pressing the keys 1-8 on the keypad you will select which zones you want isolated during home set. As a key is pressed, its relevant led on the display will toggle on or off. Any led’s that are on will be isolated during home set and any that are off will remain active. Engineer access code 1-...

  • Page 12: Glossary of Terms

    11 factory programming defaults 9-9 factory defaults have been split into two sections, programming and codes. To return to factory programming defaults first enter engineering mode then proceed as follows:- 1) enter 9-9 any extension sounders will give a rapid pipping sound. The internal keypad sou...

  • Page 13

    12 night set entry this means when the panel is night set the zone, when activated, will start the entry timer but if the panel is full set then this zone will simply act as an alarm zone entry circuit this will start the entry timer when activated providing the panel is set. Fire (for use with smok...

  • Page 14

    13 zone zone use / location resistance keys entered 1 Ω Ω 2 Ω Ω 3 Ω Ω 4 Ω Ω 5 Ω Ω 6 Ω Ω 7 Ω Ω 8 Ω Ω timer value keys entered full seconds night seconds ext sounder minutes tick box 1 2 3 4 5 6 7 8 checked extended options battery voltage v aux. Voltage v installed by this information should be kept ...

  • Page 15

    14 fault finding a selection of common known problems and solutions are listed below. Problem cause answer programmed 7-5 but zone 1 wont isolate in night set. Have not manually isolated zone when setting panel. When night setting enter code * 0 * 1. Zone 1 is permanently lit memory default link is ...

  • Page 16: 5-051-519-01

    15 c&k systems ltd. Unit 23-24 walkers road north moons moat industrial estate redditch worcs. B98 9he tel: 01527 68111 fax: 01527 68222 tech support:0345 660533 9am-5pm weekdays (uk only) email to: info@cksys.Co.Uk website: http://users.Powernet.Co.Uk/cksys 5-051-519-01 approved bs en iso no.9002:1...