    Overview the ebdhs-knx pir (passive infrared) presence detector provides automatic control of lighting loads with optional manual control. The ebdhs-knx is a high sensitivity pir detector suitable for high bay applications, such as warehouses and factories, and where high detection sensitivity is ne...

  • Page 2: Detection Diagrams

    2 detection diagrams range detection pattern walk across maximum mounting height 20m walk towards height range diameter 15m 30m 10m 20m 6m 12m 3m 8m height range diameter 15m 40m 10m 26m 6m 16m 3m 9m alignment marks the sensor head has 4 alignment marks. These correspond to the 4 outer passive infra...

  • Page 3: Applications

    3 masking the ebdhs-dd includes two clip-on masking shields to allow for precise masking of the detection shape. The masks can be easily shaped to produce detection patterns suitable for applications such as aisles and corners and for narrowing the detection diameter. Radial tear pattern for narrowi...

  • Page 4: Installation

    4 the ebdhs-dd is designed to be mounted using either:  flush fixing, or  surface fixing, using the optional surface mounting box (part no. Dbb). Both methods are illustrated below. Use the supplied gasket to ensure ip rating (not compatible with surface mounting box part no. Dbb). Assembly remove...

  • Page 5: Ir Operation

    5  uhs5 programming ir handset. See below for programmable functions.  uhs7 user ir handset. This handset can be used for selecting scenes, on, off, raise and lower. See user guide for full programming details. For most basic programming operations the uhs5 handset can be used and the following pr...

  • Page 6

    6 knx function and configuration introduction a presence detector monitors the detection zone for occupancy, and causes one or more actions to be executed when a person enters the detection area. In their simplest form, presence detectors could be used to turn on a light when a person enters a room,...

  • Page 7

    7 knx function and configuration configuration configuration of the presence detector and associated logic functions is via the ets tool, available from the knx association. Start the process by downloading the device catalogue from the www.Cpelectronics.Co.Uk and importing it into ets. Once importe...

  • Page 8: Basic Movement Detection

    8 setting options description sensor walk test led disable enable enable or disable the sensor walk test led, triggered when movement is detected. This is useful for commissioning, (or if the detector is to be used in bedrooms). Note that the walk test function can also be turned on and off via infr...

  • Page 9: Switch Inputs

    9 switch inputs the switch inputs parameters are used to define the behaviour when the two volt-free switch inputs are connected. The inputs can be used to send dimming commands, recall scenes or send simple switch (on/off) telegrams. It should be noted that these switch inputs can be used as part o...

  • Page 10: Infra-Red Scene Control

    10 infra-red scene control the infra-red scene control parameters are used to configure the scene recall behaviour when the sensor is used with the uhs7 remote control handset. This handset provides eight scene recall buttons, dim up/down buttons and on/off buttons. As knx defines a maximum of 64 sc...

  • Page 11

    11 logic controller 1 / 2 (switch/scene) group object data type description switch state output 1.1 dpt_switch the main output from the channel's logic expression. Scene recall output 17.1 dpt_scenenumber configured scene number is sent via this group object if required. Enable input 1.1 dpt_switch ...

  • Page 12

    12 logic controller 3 (brightness) the brightness logic controller aims to maintain a uniform brightness in the sensor area at all times. Two brightness targets can be defined, subject to a successful calibration (as detailed earlier). In similar fashion to the movement controllers, a logic expressi...

  • Page 13

    13 this page intentionally left blank.

  • Page 14: Technical Data

    14 due to our policy of continual product improvement cp electronics reserves the right to alter the specification of this product without prior notice. Dimensions see diagrams opposite weight 0.20kg supply voltage 30v dc via knx bus power consumption on (peak) 5.5ma off (idle) 5.4ma terminal capaci...