Switch inputs
The switch inputs parameters are used to define the behaviour when the two volt-free switch inputs are connected. The
inputs can be used to send dimming commands, recall scenes or send simple switch (on/off) telegrams. It should be
noted that these switch inputs can be used as part of logic functions if required.
Setting
Options
Description
Switch input 1 close action
Send 'dim up' command
Send 'dim down' command
Recall scene number
Send 'on' command
Send 'off' command
Send 'on' command cyclically
Send 'off' command cyclically
Do nothing
Defines what type of command should be sent when
switch input 1 is closed.
Switch input 1 close scene number
1 – 64
Scene number to recall when switch input 1 is closed
Switch input 1 open action
Send 'dim up' command
Send 'dim down' command
Recall scene number
Send 'on' command
Send 'off' command
Send 'on' command cyclically
Send 'off' command cyclically
Do nothing
Defines what type of command should be sent when
switch input 1 is opened.
Switch input 1 open scene number
1 – 64
Scene number to recall when switch input 1 is
opened.
Switch input 2 close action
Send 'dim up' command
Send 'dim down' command
Recall scene number
Send 'on' command
Send 'off' command
Send 'on' command cyclically
Send 'off' command cyclically
Do nothing
Defines what type of command should be sent when
switch input 2 is closed.
Switch input 2 close scene number
1 – 64
Scene number to recall when switch input 2 is closed.
Switch input 2 open action
Send 'dim up' command
Send 'dim down' command
Recall scene number
Send 'on' command
Send 'off' command
Send 'on' command cyclically
Send 'off' command cyclically
Do nothing
Defines what type of command should be sent when
switch input 2 is opened.
Switch input 2 open scene number
1 – 64
Scene number to recall when switch input 2 is
opened.
Dim up/dim down step percentage
100%
50%
25%
12.5%
6.25%
3.125%
1.5625%
The percentage to add or subtract from the current
dimmer value when the relevant button is pressed.
Smaller percentages offer finer-grained control, but
require the user to press the button more times to
change the light level.
Send switch 1 cyclical telegrams every
0 – 65,535s
Defines how often to send switch state telegrams if
cyclical sending has been chosen.
Send switch 2 cyclical telegrams every
0 – 65,535s
Defines how often to send switch state telegrams if
cyclical sending has been chosen.
Group Object
Data Type
Description
Switch 1 scene recall output
17.1 DPT_SceneNumber
Scene number transmitted when switch 1 changes
state if in scene recall mode.
Switch 2 scene recall output
17.1 DPT_SceneNumber
Scene number transmitted when switch 2 changes
state if in scene recall mode.
Switch 1 state output
1.1 DPT_Switch
On/off switch state telegram if configured.
Switch 2 state output
1.1 DPT_Switch
On/off switch state telegram if configured.
Dimming control output
3.7 DPT_Control_Dimming
Dimming control output if switches are configured for
dim up/dim down operation.