D-Link DES-7206 Quick Installation Manual - page 6
DES-7200 Series Quick Installation Guide
Correctly Moving the DES-7210 and DES-7206
Warning
Do not move the equipment by grasping the panel, power supply handle,
ventilation holes of the chassis, as they are not designed to bear the
weight of the entire equipment. Failing to do so may cause damage or
even injure yourself.
Preparation Before Installation
Temperature and Humidity Requirements
To ensure the normal working and a prolonged useful life of the DES-7210/7206, appropriate
temperature and humidity must be maintained in the equipment room.
If the equipment room has temperature and humidity that do not meet the requirements for a
long time, the equipment may be damaged.
Temperature and Humidity Requirements of the DES-7210/7206
Temperature
Relative Humidity
Long-term condition
Short-term condition
Long-term condition
Short-term condition
0ºC-45ºC
0ºC-45ºC
40%-65% 10%-90%
Note
1. The ambient temperature and humidity are measured at the point that is
1.5m above the floor and 0.4m before the equipment when there is no
protective plate in front or back of the equipment rack.
2. The short-term working condition applies where the continuous working
period does not exceed 48 hours and the accumulative total period within
a year does not exceed 15 days.
Static Discharge Damage Prevention
To prevent damage from static electricity, you must pay attention to the following:
1. Proper grounding of the equipment and floor
2. Dust prevention measures are taken in the room.
4