Daewoo DSB-181LH Service Manual - Indoor Fan Motor Starting
13
3 min. Time Delay of Compressor
In normal operation, there is a time delay of three minutes between turn off and turning back on including initial
power up.
When indoor fan motor is on, it always starts at normal speed and then it operates desired speed.
Indoor Fan Motor Starting
Frost Prevention of Indoor Unit
When the unit operates at low ambient temperature, frost may appear on the Evaporator. When the indoor coil
temperature is lower than 0°C at the end of 10 minutes of continuous compressor operation from the start, the
microcomputer of the unit stops the compressor to protect the unit from the frost. The control procedure for
indoor coil freeze protection.
1) The compressor and outdoor fan turn off.
2) Indoor fan operates according to user set speed.
3) The normal operation returns when the indoor coil temperature is higher than 7°C or equal to 7°C.
0
°
C
7
°
C
Compressor and
Outdoor Fan
OFF
OFF
ON
Set Speed
Indoor Fan
(Indoor coil temperature)