Eaton 5PX 1500i RT2U Installation And User Manual - 5. Maintenance
Page 20
614-07977-00_EN
5. Maintenance
Mounting the new battery module
Carry out the above instructions in reverse order.
To ensure safety and high performance, use only batteries supplied by EATON.
p
Take care to firmly press together the two parts of the connector during remounting.
p
5.3 Maintenance on a UPS equipped with the HotSwap MBP module
The HotSwap MBP module makes it
possible to service or even replace
the UPS without affecting the connected
loads (HotSwap function).
Maintenance
1. Set switch (55) to Bypass position.
The red LED on the HotSwap MBP
module goes ON, indicating that the
load is supplied directly with AC input
source power.
2. Stop the UPS by pressing the
button on the UPS control panel.
LED (53) "UPS ON - OK to switch"
goes OFF, the UPS can now be
disconnected and replaced.
Return to normal operation
1. Check that the UPS is correctly
connected to the HotSwap MBP
module.
2. Start the UPS by pressing the
button on the UPS control panel.
LED (53) "UPS ON - OK to switch" on
the HotSwap MBP module goes ON
(otherwise, there is a connection error
between the HotSwap MBP module
and the UPS).
3. Set switch (55) to Normal position.
The red LED on the HotSwap MBP
module goes OFF.
5PX
HotSwap MBP
46
51
52
55
54
53
56
57
58