Manual is about: 9E 6-20kVA

Summary of 9E10Ki

  • Page 1

    Powerquality.Eaton.Com eaton 9e 6-20kva.

  • Page 2: Content:

    Content: 1. Introduction ............................................................................... 1 1.1 safety instruction ............................................................... 1 1.2 certification standards ....................................................... 3 1.3 special symbol...

  • Page 3: 1. Introduction

    1 1. Introduction 1.1 safety instruction the ups must be installed and maintained exclusively by quailified staff. See installation and operation instructions before connecting to the supply. The ups must be installed with an earth connection. It has a high leakage current. The first wire to be conn...

  • Page 4

    2 all battery installation and maintenance operations entail gaining access to the inside of the ups and require the use of tools: these operations are to be performed exclusively by qualified staff. The batteries replaced are to be considered as toxic waste and treated accordingly. Dispose of used ...

  • Page 5: 1.2 Certification Standards

    3 1.2 certification standards safety iec 62040-1:2008 iec 60950-1:2005 (modified) emc conducted emission: iec 62040-2. Category c3 radiated emission: iec 62040-2. Category c3 esd:iec 61000-4-2. Contact: level 2, air discharge: level 3 rs:iec 61000-4-3. Level 3 eft:iec/en 61000-4-4. Level 4 surge:iec...

  • Page 6: 1.3 Special Symbols

    4 1.3 special symbols the following are examples of symbols used on the ups or accessories to show you the important information:.

  • Page 7: 2.Presentation

    5 2.Presentation 9e series ups uses on-line double conversion technology, resulting in the highest levels of reliability and maximum protection for critical loads. 2.1 model list model power ratings pf voltage (output) 9e6ki 6kva/4.8kw 0.8 230v (220/240) 9e10ki 10kva/8kw combo 0.8 230v (220/240) 9e1...

  • Page 8

    6 9e10ki, 9e10kixl input output n l n l2 l1 l3 input filter ac/dc—dc/ac output filter internal power charger battery input switch bypass maintain switch ` output switch main power wiring 9e15ki, 9e20ki, 9e20kixl input output n l n l2 l1 l3 input filter ac-dc dc-ac output filter internal power charge...

  • Page 9: 2.3 Ups Views

    7 2.3 ups views 2.3.1 ups front view ① display ② multipurpose buttons ③ wheels (front wheels swivel and can be locked, fixed rear wheels).

  • Page 10: 2.3.2 Ups Rear View

    8 2.3.2 ups rear view 9e6ki with backpanel cover 9e6ki without backpanel cover ④ usb communication port ⑩ input switch ⑤ rs232 communication port ⑪ cover for terminals ⑥ slot for optional communication card ⑫ fuse ⑦ cooling fan(s) ⑬ terminals for i/o cable connection (refer to related section) ⑧ out...

  • Page 11

    9 ④ usb communication port ⑩ input switch ⑤ rs232 communication port ⑪ cover for terminals ⑥ slot for optional communication card ⑫ fuse ⑦ cooling fan(s) ⑬ terminals for i/o cable connection (refer to related section) ⑧ output switch ⑭ earthing screws ⑨ manual bypass for maintenance ⑮ tie wrap hold-...

  • Page 12: Ups Rear View

    10 ups rear view 9e15ki/9e15kixl/9e20ki/9e20kixl with backpanel cover 9e15ki/9e15kixl/9e20ki/9e20kixl without backpanel cover ④ rs232 communication port ⑩ input switch ⑤ usb communication port ⑪ cover for terminals ⑥ slot for optional communication card ⑫ terminals for i/o cable connection (refer to...

  • Page 13: 2.3.3 Ebm Rear View

    11 2.3.3 ebm rear view ① fuse ② cover for terminals ③ tie wrap hold-down ④ wheels (front wheels swivel and can be locked, fixed rear wheels) ⑤ terminals for i/o cable connection (refer to related section) ⑥ earthing screws.

  • Page 14: 3.Installation

    12 3.Installation 3.1 unpacking 1. Cut the straps 2. Open the carton, take off wood board, accessory pack and pe form. 3. Remove carton upward and take out front pe form. 4. Put the wood board (removed at step2) as figure showed. Make sure that the slide rests firmly against the pallet so it remains...

  • Page 15: 3.2 Package Content

    13 3.2 package content after opening the packaging, it is first necessary to check the contents. The package must contain: 3.3 connection 3.3.1 installation requirements warning: installation must be performed by qualified personnel. The first connection to perform is the protective conductor (earth...

  • Page 16

    14 a differential switch upstream will also be triggered for a fault occurring downstream of the ups. In calculating reactivity of this switch, account must be taken of the leakage current of the ups (approx. 8 ma) plus that of the load which come together on the ups’s earth conductor. Ups input dif...

  • Page 17

    15 notice: it is required to install an external isolating device against current backfeed between mains input and ups. After the device is installed, it must add a warning label with the following wording or the equivalent on the external ac contactor: risk of voltage backfeed. Isolate the ups befo...

  • Page 18

    16 1. Install a magneto-thermal switch ( 63a for 6 & 10kva versions, 125a for 15 and 20kva versions ) with intervention curve d upstream of the machine (4 poles for three-phase versions, 2 poles for single-phase versions). 2. The connection terminals to use for the input and output lines are located...

  • Page 19: Combo Version

    17 r.E.P.O. A - the repo connection (between terminal 5 and 6) is normally open. For more information please refer to the repo section of this manual fig.3-4 6k terminal view 6. Tighten the terminals well, close the backpanel cover and secure it with the screws taken out earlier. The suggested tight...

  • Page 20

    18 5. Short-circuit the input terminals (1, 2 and 3) with the jumper provided in the accessories kit. Connect the wires to the respective terminals, following exactly the instructions below: input line a - ensure that the upstream magneto-thermal switch is open. B - connect the earth wire to screw a...

  • Page 21: Three-Phase Connection

    19 three-phase connection 1. (three-phase connection 9e10ki, 9e10kixl ): use 2 cables of cross-section 4 mm 2 (l2 and l3) and 3 with cross-section 10 mm 2 (earth, n, l1) for the input (n.B.: l1 and n are of greater cross- section because in bypass operation they have to carry all of the input curren...

  • Page 22: R.E.P.O.

    20 fig.3-6 10~20k three phase input terminal view 3. Tighten the terminals well, close the backpanel cover and secure it with the screws taken out earlier. For 10 to 15kva the suggested tighten force is 1.2~1.6nm. For 20kva, the suggested tighten force is 2.5~3 nm. R.E.P.O. The terminal block on the...

  • Page 23

    21 1. Use a 2x0.75mm 2 cable to make the connection with the r.E.P.O. Terminals. 2. Insert the screw driver in the square hole and press down to make the round hole terminal open. Then insert the wire into the round hole. Then pull out the screw driver. Connect the two wires of the cable to terminal...

  • Page 24

    22 3.3.3 ebm wiring connection it is possible to connect more than one ebm in order to achieve any level of autonomy without mains power. In order to ensure the battery runtime displayed is accurate, please set your battery configuration through ups configuration tool (download available here: http:...

  • Page 25

    23 versions 9e6ki, 9e10ki, 9e10kixl note: for 9e15ki, 9e20ki, 9e20kixl ebm wiring connection, you should check the 9eebm manual in ebm package. Fig.3-10 ebm terminal connection for 9e6ki, 9e10ki, 9e10kixl with mutliple ebm fig.3-9 ebm terminal connection for 9e6ki, 9e10ki, 9e10kixl with single ebm.

  • Page 26: 4.Operation

    24 4.Operation 4.1 display and buttons fig. 4-1 control panel the following tables shows the buttons, lcd indicator and led indicator status and description: table 4-1 control buttons functions the button function illustration turn on if the ups is in standby or bypass mode, press >2s, the buzzer wi...

  • Page 27

    25 table 4-2 led indicator led name colour description line green it indicates the utility is normal battery yellow it indicates the input is connected with battery, and the input power is supplied from the battery. Bypass yellow it indicates the ups is in bypass mode, the load current is directly s...

  • Page 28: Interface

    26 table 4-3 buzzer priority ups condition buzzer 1 ups fault and failure continuous 2 normal mode no beep 3 battery/battery test mode one beep per 4 sec (one beep per 1s when battery low) 4 bypass mode one beep per 2 minutes 5 overload one beep per 500ms 6 other alarm one beep per 1s 7 manual bypas...

  • Page 29

    27 icon icon name description measureme nts display values, eg: voltage, frequency, load percentage, etc. Dc voltage battery voltage percentage the percentage, eg: load percentage and battery capacity percentage output it indicates information for output. Input it indicates information for input. Lo...

  • Page 30: 4.2 Operating Ups

    28 4.2 operating ups notice: please switch off the connected loads first before turning on the ups, and switch on the loads one by one after the ups is turned on. Switch off all of the connected loads before turning off the ups. Notice: power on for the first time 1. Close the magnetothermic switch ...

  • Page 31: 4.2.5 Transfer To Bypass

    29 4.2.4 turning off ups without mains to power off the ups press button continuously for more than 3s, and the buzzer beep once. The ups will cut off the output. A few seconds later, lcd shuts down and no voltage is available from the ups output. 4.2.5 transfer to bypass to transfer the ups in inte...

  • Page 32: 4.3 Configuration

    30 4.3 configuration 4.3.1 ups parameters in order to change ups parameters (output voltage, number of ebm, ....) please use ups configuration tool (download available here: http://pqsoftware.Eaton.Com ). 4.3.2 communication ports on the back of the ups (see ups views), the following communication p...

  • Page 33: 4.3.3

    31 connectivity cards the ups is equipped with an expansion slot for optional connectivity cards (see figure on right). It is not necessary to shutdown the ups before installing a communication card. 1. Remove the slot cover secured by screws. 2. Insert the communication card in the slot. 3. Secure ...

  • Page 34: 4.4 Trouble Shooting

    32 each 9e ups ships with eaton intelligent power software suite. To begin installing, see the instructions accompanying the software suite cd. Eaton software suite provides up-to-date graphics of ups power and system data and power flow. It also gives you a complete record of critical power events,...

  • Page 35

    33 the buzzer sounds continuously and the display shows one of the following codes: a80e, a810, f808 the load applied to the ups is too high reduce the load to within the threshold of 100% (or user threshold in the case of code a80e). If the display shows an fault: remove the load and switch the ups...

  • Page 36: 4.5 Alarm Codes

    34 4.5 alarm codes using a sophisticated self-diagnosis system, the ups is able to check its own status and any anomalies and/or faults which may occur during normal operation and display them on the display panel. If there is a problem, the ups signals the event by showing the code and the type of ...

  • Page 37: 5.Technical Data

    35 f704 failed inverter soft start f70c inverter undervoltage f808 output overload fault f811 negative output power 5.Technical data ups models 9e6ki 9e10ki, 9e10kixl 9e15ki 9e20ki, 9e20kixl input nominal voltage [vac] 220 - 230 - 240 220 - 230 – 240 / 380 – 400 - 415 maximum operating voltage [vac]...

  • Page 38

    36 bypass line not available: locks after 10 s overload load > 150% bypass line available: activates the bypass after 100 ms, then locks after 1 s bypass line not available: locks after 1 s other leakage current to earth [ma] ambient temperature [°c] 0 – 40 humidity protection devices batteries deep...