Eaton Ellipse ECO 1200 Installation And User Manual - page 7
7
614-06803-00
E
N
gl
IS
h
Troubleshooting
(For further information, visit the www.
powerquality.
eaton.com site or contact after-sales
support.)
Advanced customizing of your UPS
Problem
Diagnostic
Solution
1
l
The battery backup outlets
9
are
not supplied with power.
l
Button
12
is not lighted on.
l
Press button
12
and check that it
turns green.
2
l
The connected devices are not
supplied when AC power fails.
l
The devices are not connected to
the battery backup outlets
9
.
l
Connect the devices to the battery
backup outlets
9
.
3
l
AC power is available, but the
UPS
operates on battery power.
l
Circuit breaker
13
, located under
the
UPS
, has been tripped by an
overload on the
UPS
output.
l
Disconnect excess equipment
and reset the circuit breaker
13
by
pressing the corresponding button.
4
l
The filtered outlets
8
are not
supplied.
l
The wall outlet is not supplied.
l
Circuit breaker
13
, located under
the
UPS
, has been tripped by an
overload on the
UPS
output.
l
Supply power to the wall outlet.
l
Disconnect excess equipment
and reset the circuit breaker
13
by
pressing the corresponding button.
5
l
Green button
12
flashes
frequently and audio alarm beeps.
l
The
UPS
frequently operates
on battery power because the AC
power source is of poor quality.
l
Have the electrical installation
checked by a professional or use
another wall outlet.
6
l
Green button
12
flashes and audio
alarm beeps continuously.
l
The
UPS
battery backup outlets
9
are overloaded.
l
Disconnect excess equipment
connected to the battery backup
outlets
9
.
7
l
Red LED
11
is on and the audio
alarm beeps every 30 seconds.
l
A fault has occurred on the
UPS
.
The battery backup outlets
9
are
no longer supplied.
l
Call after-sales support.
8
l
Green LED
10
is off and the
filtered outlets
8
are supplied.
l
Surge protection is no longer
provided.
l
Call after-sales support.
9
l
The telephone line is disturbed or
modem access is not possible.
l
Surge protection on the telephone
line is no longer provided.
l
Disconnect the telephone line
from the wall outlet.
l
Call after-sales support.
10
l
Red LED
11
flashes.
l
The battery has reached the end
of its service life.
l
Have the battery replaced.
11
l
EcoControl outlets keep powered
when main application (Master
outlet) is stopped.
l
EcoControl function is not
activated or not properly set.
l
Activate or set properly
EcoControl function using the
software provided with the product.
Sensitivity to variations of the AC power supply
Audio alarm
l
Only to be used
if frequent switching to the
UPS
battery due to large variations in the AC supply
voltage.
l
Accessing the programming mode: with the device
switched off, press button
12
for 6 s and release it
once LEDs
10
11
have come on.
l
Display of the 3 possible voltage ranges according to
the status of LEDs
10
and
11
:
l
Possibility of deactivating the audio alarm when the
UPS
is operating on the battery.
l
Accessing the programming mode: with the device
switched off, press button
12
for 11 s and release it
when the audio alarm sounds.
l
Display of the 2 possible audio alarm modes:
Normal mode
(factory
configuration):
AC supply
between 184V
and 264V
Low range
mode:
AC supply
between
161V
and 264V
Low and high
range mode:
AC supply
between
161V
and
284V
Normal mode (factory
configuration):
the
UPS
emits a beep
every 10 s when operating
on its battery.
Silent mode:
the
UPS
emits a single
beep when switching to
battery operation and
then remains silent.
12
11 10
11
12
11
12
11
12
12
11 10
12
11 10
Normal mode
activated:
programming by
continuous beep.
Silent mode
activated:
programming by a
beep every second.
Change from one mode to another by successively
pressing button
12
.
Change from one mode to another by successively
pressing button
12
.
l
Memorizing the mode: 10 s after the last press of the
button.
l
Memorizing the mode: 5 s after the last press of the
button.
614-06803-00.indd 7
10/12/2010 11:15:08