Eaton i-on1000EX Installation Manual - Step 9. Fit And Connect
i-on1000EX
Installation
Page 23
Line Fail Input
This input is designed to allow a plug-by
communicator to indicate to the control unit that
the communications link has failed. The
communicator should have an output capable of
applying +12V to the Line Fail input while a line
fault is present and 0V when the fault is absent.
Remote Reset (Tell Back) Input
This input
(marked “RR”) is designed to allow a
plug-by communicator to indicate to the control
unit that the user can reset the system after a
system tamper. The communicator should have
an output that, when triggered remotely, can apply
+12V for at least 100ms
to the input. See “Remote
Reset (Redcare Reset)” in the Engineering Guide
for more information.
Line Monitoring for a Dual-Path Communicator
If a standalone dual-path (landline and mobile)
communication device, such as a RedCARE STU,
is connected to the plug-by connector, you need
to do the following to obtain correct line fault
reporting that complies with BSIA Form No.175,
April 2005 (this is not necessary if you are using a
plug-on module):
1. Reprogram one of the plug by outputs to type
“ATS Test” and wire that output to the ATS
Test input of the communicator.
2. Wire the Line Fault output of the
communicator to the Line Fault input of the
plug-by connector. The communicator must
provide +12Vdc to indicate a line fault (for
example, if the Line Fault output at the
communicator uses a relay, connect the
common terminal of the relay to +12Vdc and
the normally-open terminal to the Line Fault
input of the plug-by connector).
The control unit will generate an "ATE L.F. Single"
alert if only one of the networks is not available, or
"ATE L.F. All" if both networks are not available.
Step 9. Fit and Connect
Battery
Fit either one to two 17Ah lead-acid batteries into
the battery compartment in the bottom of the
control unit (see Figure 48). Use batteries whose
case material has a minimum rating of UL94V-2 in
order to comply with EN60950 (this standard
applies because of the energy content of 17Ah
batteries).
See page 10 for example calculations of battery
requirements.
WARNING 17Ah lead-acid batteries weigh 6kg
each. Do NOT drop. Ensure that the fixings of the
control unit case to the wall, and the wall itself, are
strong enough to support the weight of the control
unit, its lid and up to two 17Ah lead-acid batteries.
The total weight of the control unit plus batteries
can be up to 18kg.
Connect the battery leads, red to the positive,
black to the negative terminals of the battery.
Connect the other ends of the leads to either
BATT1 or BATT2 (item 14 in Figure 3).
If you are fitting only one battery, connect it to
BATT1 (the lower set of pins) and disable alerts
on BATT2 (see the Engineering Guide).
Figure 48 Fitting the Batteries
Note: Connecting the batteries without mains
power will not start the system. (See
“Programming Before Installation” in the
Engineering Guide.)
Step 10. Power-up, Select Main
Settings and Set Addresses
WARNING: During initial power-up all the keypad
sounders, internal loudspeakers and wired sirens
MAY give an alarm tone. If you are working at the
top of a ladder, make sure that the sudden noise
does not startle you and cause a fall.
Note: The following assumes that the control unit,
keypads and expanders are in the factory-default
state. That is, the control unit has not been
previously configured, and the keypads and
expanders have a "null" address (no address
previously allocated).
1. Apply mains power to the control unit.
The keypads and internal sounder may give
an alarm tone. The heartbeat LED on the
control unit PCB and the navigation keys on
keypads start flashing.
Wait until you see:
This message indicates that the keypad has a
"null" address.
2. Go to the keypad you want to use for initial
programming. Obtain an address for this
keypad by pressing and holding A and keys
simultaneously for at least three seconds
until the display shows the address allocated
by the control unit
, such as “b0-d51”(bus 0
device 51).